Worked example of discharge pipe sizing
Figure on the left shows a G1/2 temperature relief valve with a discharge pipe (D2) having 4
No. elbows and length of 7m from the tundish to the point of discharge.
From Table:
Maximum resistance allowed for a straight length of 22mm copper discharge pipe (D2) from
a G1/2 temperature relief valve is 9.0m.
•
Subtract the resistance for 4 No. 22mm elbows at 0.8m each = 3.2m
•
Therefore the permitted length equates to: 5.8m
•
5.8m is less than the actual length of 7m therefore calculates the next largest size.
Maximum resistance allowed for a straight length of 28mm pipe (D2) from a G1/2 temperature
relief valves equates to 18m.
•
Subtract the resistance of 4 No. 28mm elbows at 1.0m each = 4.0m
•
Therefore the maximum permitted length equates to: 14m
•
As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
Essential recommendations for safety
•
The temperature/pressure relief valve should only be replaced by a competent
person.
•
No control or safety valves should be tampered with or used for any other
purpose.
•
The discharge pipe should not be blocked or used for any other purpose.
•
The tundish should not be located adjacent to any electrical components
UK
SLE - SLE Plus: A1007847 - 661Y2100 • D
Installation
19
EN
Содержание 06627301
Страница 5: ...SLE SLE Plus A1007847 661Y2100 D Product Information ENERGY LABELLING 5 EN...
Страница 6: ...SLE SLE Plus A1007847 661Y2100 D Product Information RATING PLATE EN 6...
Страница 27: ...SLE SLE Plus A1007847 661Y2100 D Starting Up 27 EN Cold water Hot water Figure 1 1 3 3 2 Figure 2 1 2 4 3 1 2...
Страница 33: ...SLE SLE Plus A1007847 661Y2100 D 33 EN...
Страница 34: ...SLE SLE Plus A1007847 661Y2100 D EN 34...
Страница 35: ...SLE SLE Plus A1007847 661Y2100 D 35 EN...
Страница 36: ......