G3 REQUIREMENTS AND GUIDANCE   

Discharge pipe from safety valves

The 

Building Regulation G3

 requires that any discharge from an unvented system is con-

veyed to where it is visible, but will not cause danger to persons in or about the building. 
The tundish and discharge pipes should be fi tted in accordance with the requirements and 

guidance notes of Building Regulation G3. The G3 Requirements and Guidance sections 

3.50 - 3.63 are detailed below.
For discharge pipe arrangements not covered by G3 Guidance advice should be sought 

from your local Building Control Offi  cer. 
Main characteristics :

• 

Any discharge pipe connected to the pressure relief devices (Expansion Valve and 

Temperature/Pressure Relief Valve) must be installed in a continuously downward di-

rection and in a frost free environment. 

• 

Water may drip from the discharge pipe of the pressure relief device. 

• 

This pipe must be left open to the atmosphere. 

• 

The pressure relief device is to be operated regularly to remove lime deposits and to 

verify that it is not blocked.

A typical discharge pipe arrangement is shown on next page. 

General remarks
• 

Discharge pipe-work D2 can now be a plastic pipe but only pipes that have 

been tested to a minimum 110°C must be used.

• 

Discharge pipe D2 can now be plumbed into the soil stack but only soil stacks 

that can handle temperatures of 99°C or greater should be used.

Extract from “The Building Regulation G3” :

Discharge pipe D1

3.50   Safety devices such as temperature relief valves or combined temperature and pres-

sure and pressure relief valves (see paragraphs 3.13 or 3.18) should discharge either 

directly or by way of a manifold via a short length of metal pipe (D1) to a tundish.

3.51   The diameter of discharge pipe (D1) should be not less than the nominal outlet size of 

the temperature relief valve.

3.52   Where a manifold is used it should be sized to accept and discharge the total di-

scharge from the discharge pipes connected to it.

3.53   Where valves other than the temperature and pressure relief valve from a single 

unvented hot water system discharge by way of the same manifold that is used by the 

safety devices, the manifold should be factory fitted as part of the hot water storage 

system unit or package.

Tundish
3.54   The tundish should be vertical, located in the same space as the unvented hot water 

storage system and be fitted as close as possible to, and lower than, the valve, with 

no more than 600mm of pipe between the valve outlet and the tundish.

Note:  To comply with the Water Supply (Water Fittings) Regulations, the tundish should in-

corporate a suitable air gap.

UK

SLE - SLE Plus: A1007847 - 661Y2100 • D

Installation

EN

16

Содержание 06627301

Страница 1: ...Smart E 130 160 210 240 300 Smart E Plus 210 240 300 Installation Operation Maintenance Instructions for the User and the Installer A1007847 661Y2100 D...

Страница 2: ...g connections 10 Domestic hot water connections 10 Main characteristics 11 Domestic hot water performances 11 Electrical characteristics 12 INSTALLATION 13 Package contents 13 Tools required for the i...

Страница 3: ...ING UP 25 Safety instructions to fill the tank 25 Filling 26 Checks before starting up 28 Starting up 28 MAINTENANCE 29 Periodic checks by the user 29 Annual maintenance 29 Draining 30 Bringing back i...

Страница 4: ...only be replaced by genuine parts Our water heaters are designed and manufactured for the exclusive purpose of heating and storing domestic hot water The domestic hot water heaters must only be heate...

Страница 5: ...SLE SLE Plus A1007847 661Y2100 D Product Information ENERGY LABELLING 5 EN...

Страница 6: ...SLE SLE Plus A1007847 661Y2100 D Product Information RATING PLATE EN 6...

Страница 7: ...ostat 60 80 C to set the domestic hot water DHW temperature 2 Manual reset high limit thermostat to restart the tank after overheating of the primary circuit 3 Connection plug to connect the electrica...

Страница 8: ...to heat by transfer fluid or independently with an optional electric resistance 1 Manual air bleed valve 2 Polypropylene shell 3 Dip tube 4 Electrical heating element optional 5 Outer steel tank prim...

Страница 9: ...20 1280 F mm 430 430 525 G mm 320 320 405 320 320 380 H mm 240 240 230 240 240 235 Smart E 130 Smart E 160 Smart E Smart E Plus 210 Smart E Smart E Plus 240 Smart E Smart E Plus 300 Max operating pres...

Страница 10: ...electrical heating element connection 6 Heating return connection heat pump 7 Flow heating circuit except Smart E 130 160 8 Return heating circuit except Smart E 130 160 1 Cold water inlet connection...

Страница 11: ...e temperature 10 C MAIN CHARACTERISTICS Main Characteristics Smart E 130 Smart E 160 Smart E Smart E Plus 210 Smart E Smart E Plus 240 Smart E Smart E Plus 300 Total capacity L 130 161 203 242 293 Pri...

Страница 12: ...thermostat of the tank cannot control the heating element To be mounted with an external box with a switch and a circuit breaker not included in the delivery Volt Amp Power Code 1 x 230 V 13 3 kW 1080...

Страница 13: ...fter removal of pack aging check the package contents and that the appliance is free of damages Contents packaging A domestic hot water tank A technical manual One energy label TOOLS REQUIRED FOR THE...

Страница 14: ...ion connect the stainless steel tank directly to the earth Use an adjustable earth clamp see example below on one of the DHW connections to connect to the earth Advised copper wire section 2 5mm Make...

Страница 15: ...eria exists including Legionella pneumophila if a minimum temperature of 60 C is not maintained in both the DHW tank and the hot water distribution network Essential instructions for the electrical sa...

Страница 16: ...used Discharge pipe D2 can now be plumbed into the soil stack but only soil stacks that can handle temperatures of 99 C or greater should be used Extract from The Building Regulation G3 Discharge pip...

Страница 17: ...e pipe size larger than the largest individual discharge pipe D2 to be connec ted 3 60 The discharge pipe should not be connected to a soil discharge stack unless it can be demonstrated that that the...

Страница 18: ...2 tundish with continuous fall See 3 56 Table G3 and worked example Tundish Discharge below fixed grating 3 61 gives alternative points of discharge Fixed grating Trapped gulley V a l v e o u t l e t...

Страница 19: ...t largest size Maximum resistance allowed for a straight length of 28mm pipe D2 from a G1 2 temperature relief valves equates to 18m Subtract the resistance of 4 No 28mm elbows at 1 0m each 4 0m There...

Страница 20: ...he appropriate size Make sure that the circuit between the tank and the safety valve is always open The third DHW tank connection if any can be used for the auxiliary DHW loop If the connection is not...

Страница 21: ...ixing valve 12 Air vent Cold water Hot water Domestic hot water kit option 1 Thermostatic mixing valve 2 Mixed water outlet 3 4 M 3 DHW expansion vessel connection 3 4 M 4 Safety unit 7 bar 5 Outlet h...

Страница 22: ...ON TO THE PRIMARY CIRCUIT 1 Primary circuit filling valve 2 Charging pump 3 Check valve 4 Primary circuit stop valve 5 Expansion vessel 6 Pressure gauge 7 Safety valve set at 3 bar 8 Drain valve 9 Sto...

Страница 23: ...0 D Installation EXAMPLES OF POSSIBLE COMBINATIONS OF THE SMART E AND SMART E PLUS Smart E Plus combined with a heat pump and floor heating system Smart E 210 240 300 combined with a boiler and floor...

Страница 24: ...bled 1 System filling valve 2 Safety valve set at 3 bar 3 Expansion vessel 4 Isolation valve heating system 5 Pressure gauge Essential instruction for the correct operation of the installation Connect...

Страница 25: ...to the ratio recommended in the local regulations Consult the manufacturer to determine the compatibility of the antifreeze with the tank s construction materials Essential instructions for the correc...

Страница 26: ...oiler 3 Open the air bleed valve 4 located on the top of the hot water tank 4 When the air is eliminated close the air bleed valve 4 Make sure the air bleed valve is tight FILLING Essential instructio...

Страница 27: ...SLE SLE Plus A1007847 661Y2100 D Starting Up 27 EN Cold water Hot water Figure 1 1 3 3 2 Figure 2 1 2 4 3 1 2...

Страница 28: ...orrectly connected and not leaking Check that the sensor of the thermostat is correctly positioned in the dry well see figures below STARTING UP If the tank is used as electric DHW tank only 1 Put the...

Страница 29: ...y unit drips periodically it may be due to an expansion problem or clogging of the valve For internal inspections the hand hole can be used If there is none use one of the water connections to insert...

Страница 30: ...ain the primary circuit of the hot water heater 1 Stop the charging pump 2 Isolate the primary circuit by closing the stop valves 1 3 Connect the drain valve 2 to the sewer using a flexible hose 4 Ope...

Страница 31: ...op valve 4 3 Connect the drain valve 2 to the sewer using a flexible hose 4 Open the drain valve 2 and the air vent 5 to drain the water from the DHW tank to the sewer 5 Close the drain valve 2 and th...

Страница 32: ...stat of the tank 3 Check if the charging pump works properly and replace if necessary 4 Check the safety thermostat on the tank and or the electric heating element and reset or replace if neces sary 5...

Страница 33: ...SLE SLE Plus A1007847 661Y2100 D 33 EN...

Страница 34: ...SLE SLE Plus A1007847 661Y2100 D EN 34...

Страница 35: ...SLE SLE Plus A1007847 661Y2100 D 35 EN...

Страница 36: ......

Отзывы: