13. Wall Control and Temperature Sensor Wiring Connections for ESP
Plus Only
SPECIAL NOTES
1. For better responding temperature control it is recommended fitting remote wall mounted or return sensors.
2. Data cable must be 4 core 14/0.20 Screened cable.
3. Remote sensor cables must be screened .
A. One On Board Sensor Only
ACT
NEUT
EARTH
DATA/R
COM/BL
S-2
S-1/G
KEY/Y
PWR/R
COM/BK
SCRN
INDOOR BOARD
(AMIB)
WALL
CONTROL
TO
OUTDOOR
UNIT
SENSOR
K
EY
C
OM
PO
WER
DO NOT CONNECT
TRACE WIRE AT
WALL CONTROL
WC-1
B. One On Board and One Remote Sensor
OPTIONAL
SENSOR
ACT
NEUT
EARTH
DATA/R
COM/BL
S-2
S-1/G
KEY/Y
PWR/R
COM/BK
SCRN
INDOOR BOARD
(AMIB)
WALL
CONTROL
TO
OUTDOOR
UNIT
SENSOR
K
EY
C
OM
PO
WER
DO NOT CONNECT
TRACE WIRE AT
WALL CONTROL
WC-1
C: Two Remote Sensors With Two Wall Controls - Mimic Logic
OPTIONAL
SENSOR 1
OPTIONAL
SENSOR 2
ACT
NEUT
EARTH
DATA/R
COM/BL
S-2
S-1/G
KEY/Y
PWR/R
COM/BK
SCRN
INDOOR BOARD
(AMIB)
TO
OUTDOOR
UNIT
DO NOT CONNECT
TRACE WIRE AT
WALL CONTROL
WALL
CONTROL 1
SENSOR
K
EY
C
OM
PO
WER
WC-1
OPTIONAL WALL
CONTROL 2
SENSOR
K
EY
C
OM
PO
WER
WC-1
NOTES:
1. When using 2 Wall Controls, the second Wall Control’s on board sensor must
be wired from the indoor board and cannot be looped from the other Wall
Control’s sensor terminal.
2. Use only one 7-day controller with dual (MIMIC LOGIC) controller set up.
NOTES
1. With zoned system using two sensors, such as in domestic applications:
Zone 1 is always assigned to sensor 1 (either Wall Control on board sensor or remote sensor 1).
Zone 2 trough 8 can be assigned to sensor 1 or sensor 2. Selection entry via Wall Control Insert document 9590-3025. When two
sensors are in circuit, the combined temperature readings will be averaged.
2. Non zoned systems using two sensors, such as commercial application:
The combined temperature readings of the two sensors will be averaged.