Installation and Commissioning Guide

Split Ducted ESP Indoor Unit

Installation and Commissioning Guide - Split Ducted ESP Plus/Ultima Indoor Unit

Doc. No.0525-078   

Ver. 2  190925

07. Unit Lifting Procedures

07.01.  Crane Lifting Method 

 

  WARNING

WH&S regulations must be observed and will take precedence during lifting process.

 DANGER

Make sure rigging equipment, accessories and plant are sufficiently and safely capable to lift the unit in order to prevent 
potential damage to property, severe personal injury or death. Please check unit weight and weight distribution points on unit 
drawing dimensions section. 

 

 NOTE

•  Crane lifting method is recommended for high rise lifting.
•  Refer to catalogue for unit weight before selecting shackles and slings.
•  Lifting procedure and unit model shown are suggestions and for illustration purposes only. 
•  It is highly recommended that installer observe current industry safe rigging and lifting procedure.

DETAIL A

PALLET

INDOOR 

UNIT

Slip nylon slings 

through the pallet

SRD175C / SRD175E

 TECHNICAL & SELECTION DATA

UNIT FEATURES

Digital Scroll Compressor

10-100% Variable Refrigeration Capacity

Multiple Speed Outdoor Fans

Louvre Outdoor Coil Guard

Pre-charged with R410A Refrigerant

AM7-D8 Wall Controller Supplied as Standard

20 m of Data Cable Included

EXV (Electronic Expansion Valve)

Integral Fan Coil Safety Tray with Drain Kit 

Indoor Coil Overheat Protection

Indoor Coil Anti-Freeze Protection

Smart Defrost Function

CONTROL FEATURES (AM7-D8)

7-Day Programmable Controller with 2 Events/Day 

24- Hour ON/OFF Timer

Auto, Heat & Cool Modes

Auto/Continuous Indoor Fan Operation

3 Speed Indoor Fan Setting

Hot Start Feature

Home/Building Automation ON/OFF Capability

CONTROL OPTIONS

Remote Temperature Sensors

Zone Kit for Control up to 8 Zones 

    (See Integrated Zones, Barrels & Plenums Section)

Secondary Wall Controller with Mimic Logic

PLENUMS (Optional)

Supply Air Plenums are Available in a 2 way or 3 way

    Con

 guration (See Integrated Zones, Barrels and Plenums

    Section for details of Spigots availability)

Return Air Plenums are Available with 2 x 400 mm Spigots 

or                    

2 x 450 mm Spigots

SPECIFICATION SUMMARY

TOTAL *

NETT **

COOLING CAPACITY (kW) *** 

18.12

17.40

SENSIBLE CAPACITY (kW) ***

14.81

14.09

HEATING CAPACITY (kW) ^

17.60

18.30

COOLING INPUT POWER (kW) ^^

6.07

HEATING INPUT POWER (kW) ^^

5.44

EER

2.99

2.87

COP

3.24

3.37

INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^

740 / 920 / 1100

OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH

52.0 / 54.0

OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH

69.0 / 71.0

POWER SUPPLY - OUTDOOR 

 240 V / 1 Ph / 50 Hz

POWER SUPPLY - INDOOR

240V / 1 Ph / 50 Hz

RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **

22.0 / 3.1 / 25.1

FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^

32.6 / 4.0 / 36.6

CIRCUIT BREAKER AND CABLE AMPS 

40.0

APPROXIMATE STARTING AMPS

<45.0

WEIGHT (kg) -- INDOOR / OUTDOOR

75.0 / 180.0

OUTDOOR UNIT MODEL

SRD175C

INDOOR UNIT MODEL

SRD175E

Based on unit rating excluding indoor fan kW.

Measured and tested in accordance with AS/NZS 3823.1.2.

At 27

0

C DB / 19

0

C WB entering air temperatures and 35

0

C ambient.

At 20

0

C DB entering air temperature and 7

0

C DB / 6

0

C WB ambient.

Input power includes indoor fan kW.

Max. - Min. air

 ow application range.

Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.

See Speci

 cations sheet for Cable Size and Circuit Breaker Size details.

Note: Use input power to estimate running cost.

*

**

***

^

^^

^^^

^^^^

ActronAir is constantly seeking ways to improve the design of it’s products, therefore speci

 cations are subject to change without notice, Please check prior to purchase.

SRD175C-

0100

 / SRD175E-

0100

 -P1- 090326

R

R410A

DIGITAL SCROLL

COMPRESSOR

ESP SPLIT DUCTED UNIT

SRD175C / SRD175E

 TECHNICAL & SELECTION DATA

UNIT FEATURES

Digital Scroll Compressor

10-100% Variable Refrigeration Capacity

Multiple Speed Outdoor Fans

Louvre Outdoor Coil Guard

Pre-charged with R410A Refrigerant

AM7-D8 Wall Controller Supplied as Standard

20 m of Data Cable Included

EXV (Electronic Expansion Valve)

Integral Fan Coil Safety Tray with Drain Kit 

Indoor Coil Overheat Protection

Indoor Coil Anti-Freeze Protection

Smart Defrost Function

CONTROL FEATURES (AM7-D8)

7-Day Programmable Controller with 2 Events/Day 

24- Hour ON/OFF Timer

Auto, Heat & Cool Modes

Auto/Continuous Indoor Fan Operation

3 Speed Indoor Fan Setting

Hot Start Feature

Home/Building Automation ON/OFF Capability

CONTROL OPTIONS

Remote Temperature Sensors

Zone Kit for Control up to 8 Zones 

    (See Integrated Zones, Barrels & Plenums Section)

Secondary Wall Controller with Mimic Logic

PLENUMS (Optional)

Supply Air Plenums are Available in a 2 way or 3 way

    Con

 guration (See Integrated Zones, Barrels and Plenums

    Section for details of Spigots availability)

Return Air Plenums are Available with 2 x 400 mm Spigots 

or                    

2 x 450 mm Spigots

SPECIFICATION SUMMARY

TOTAL *

NETT **

COOLING CAPACITY (kW) *** 

18.12

17.40

SENSIBLE CAPACITY (kW) ***

14.81

14.09

HEATING CAPACITY (kW) ^

17.60

18.30

COOLING INPUT POWER (kW) ^^

6.07

HEATING INPUT POWER (kW) ^^

5.44

EER

2.99

2.87

COP

3.24

3.37

INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^

740 / 920 / 1100

OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH

52.0 / 54.0

OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH

69.0 / 71.0

POWER SUPPLY - OUTDOOR 

 240 V / 1 Ph / 50 Hz

POWER SUPPLY - INDOOR

240V / 1 Ph / 50 Hz

RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **

22.0 / 3.1 / 25.1

FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^

32.6 / 4.0 / 36.6

CIRCUIT BREAKER AND CABLE AMPS 

40.0

APPROXIMATE STARTING AMPS

<45.0

WEIGHT (kg) -- INDOOR / OUTDOOR

75.0 / 180.0

OUTDOOR UNIT MODEL

SRD175C

INDOOR UNIT MODEL

SRD175E

Based on unit rating excluding indoor fan kW.

Measured and tested in accordance with AS/NZS 3823.1.2.

At 27

0

C DB / 19

0

C WB entering air temperatures and 35

0

C ambient.

At 20

0

C DB entering air temperature and 7

0

C DB / 6

0

C WB ambient.

Input power includes indoor fan kW.

Max. - Min. air

 ow application range.

Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.

See Speci

 cations sheet for Cable Size and Circuit Breaker Size details.

Note: Use input power to estimate running cost.

*

**

***

^

^^

^^^

^^^^

ActronAir is constantly seeking ways to improve the design of it’s products, therefore speci

 cations are subject to change without notice, Please check prior to purchase.

SRD175C-

0100

 / SRD175E-

0100

 -P1- 090326

R

R410A

DIGITAL SCROLL

COMPRESSOR

ESP SPLIT DUCTED UNIT

Connect the loop ends 

of slings into shackle

FIG. 1

A

Provide rubber pads 

to prevent damage 

to the unit

Equipment Required For Crane Lifting:

 

1 x Shackle

 

2 x Nylon Slings

 

4 x Rubber pads

 NOTE

Refer to catalogue for unit weight before selecting shackles and slings.

Procedure:

1.  Slip nylon slings through the pallet as shown in Fig. 1.
2.  Use Bow or Dee shackle to connect the slings.
3.  Ensure slings are protected by rubber pads or similar if slings are draped across unit edges, corners, or air grilles . This will 

prevent the unit from being damaged during lifting.

4.  Test lift the unit to determine exact unit balance and stability before hoisting it to the installation location. 

Содержание ESP Plus Series

Страница 1: ...Guide Indoor Model Numbers ESP Plus ESP Ultima SRV131E SRV151E SRV171E SRV191E SRV201E SRV231E SRM151E SRM171E SRM191E SRM201E SRM231E IMPORTANT NOTE Please read this manual carefully before installin...

Страница 2: ...SRV201E SRM201E 11 05 04 SRV231E SRM231E 12 06 Installation Instructions 13 07 Unit Lifting Procedures 15 07 01 Crane Lifting Method 15 07 02 Fork Lift Method 16 08 Safety Drain Tray 17 09 Zone Barre...

Страница 3: ...our shipment Inspect the unit components and accessories for any sign of damage If there is any damage to the unit contact ActronAir Customer Care Department immediately on 1300 522 722 Check the unit...

Страница 4: ...e that they can use the appliance safely Young children should be supervised to ensure that they do not play with the appliance Installer must incorporate a means of electrical disconnection isolator...

Страница 5: ...door Unit Doc No 0525 078 Ver 2 190925 03 Components Overview 03 01 Indoor Unit Components Overview EC MOTOR INDOOR UNIT LID CONTROL PANEL ID COIL INDOOR CONTROL PANEL 8 ZONE MODULE 03 02 Indoor Unit...

Страница 6: ...ATA COM White Black SCRN Blue 8Z 24V M SERIES 8 ZONE MODULE Part No 2020 170 WARNING DAMAGE DUE TO INCORRECT WIRING VOIDS WARRANTY ON OFF ZONING INTERNAL 2A FUSE N A E 04 02 ESP Ultima Standard Parts...

Страница 7: ...B 14 350 14 350 mm 290 mm ZB 16 400 16 400 mm 290 mm Cat5e Zone Cable Sold Separately For ESP Plus Part Number Length Connector 4070 020 7 metres RJ45 4070 021 20 metres RJ45 For ESP Ultima Part Numbe...

Страница 8: ...art Number LM ZC 2W White LM ZC 2G Grey Voltage 24 VAC Connections RJ45 Socket Dimensions mm 72 5 x 101 5 x 12 W x H x D Zone Sensor Sold separately Part Number LM ZS 2W White LM ZS 2G Grey Connection...

Страница 9: ...50 115 247 5 247 5 575 SUPPLY AIR RETURN AIR 1290 O A 40 535 70 50 EC INDOOR FAN EC INDOOR FAN SUPPLY AIR MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES NOTES 1 Do not scale drawing All dimensio...

Страница 10: ...perimeter is available 4 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJ...

Страница 11: ...ess clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION EC ID FAN EC ID FAN INDOOR COIL HEIGH...

Страница 12: ...or any extra charge incurred due to lack of access THIRD ANGLE PROJECTION EC ID FAN EC ID FAN HEIGHT CLEARANCE 410mm DUCT WORK DUCT WORK 890 mm SERVICE CLEARANCE 890 mm SERVICE CLEARANCE ELECTRICALS R...

Страница 13: ...der to minimize the transfer of noise and vibration into building structures An optional hanging bracket assembly and rubber grommet supplied as standard with SRV231E and SRM231E are also available to...

Страница 14: ...by both of the supply air plenum and the twin spigot duct plate Fan Coil With Vertical Discharge Optional An upright Fan Coil with vertical supply air discharge is also available wherein installation...

Страница 15: ...ommended that installer observe current industry safe rigging and lifting procedure DETAIL A PALLET INDOOR UNIT Slip nylon slings through the pallet SRD175C S SELECTION DATA DIGITAL SCROLL COMPRESSOR...

Страница 16: ...Hz POWER SUPPLY INDOOR 240V 1 Ph 50 Hz RATED LOAD AMPS OUTDOOR INDOOR TOTAL 22 0 3 1 25 1 FULL LOAD AMPS OUTDOOR INDOOR TOTAL 32 6 4 0 36 6 CIRCUIT BREAKER AND CABLE AMPS 40 0 APPROXIMATE STARTING AM...

Страница 17: ...ONNECTION CONDENSATE DRAIN CONNECTION SUPPLY AIR INTERNAL CONDENSATE TRAY THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION THE TOP OF THE P TRAP MUST BE 50MM BELOW T...

Страница 18: ...E PARTS INTEGRATED ZONE BARRELS OPERATE WITH M SERIES CONTROLS ONLY 24 VOLT 8 ZONE KIT 8Z 24V AMZ 24V ZONE CARD 20VA 240 TO 24 VOLT TRANSFORMER INSTALLATION INSTRUCTIONS MOUNTING SCREWS LENGTH OF ALL...

Страница 19: ...slot at the top and the bottom of the Control Interface Do this procedure alternately between the four slots until the back cover of the control separates Use large enough flat blade screwdriver to fi...

Страница 20: ...e buttons for zone name to be allocated BUTTON PAD 7 Assign and attach zones Attach the desired zone buttons and assign names to each zone Ensure the buttons make a click sound when attached to the PC...

Страница 21: ...directly below the supply air grille or near other additional heat load sources as these locations may alter sensor readings 1 Remove cover plate as shown below Use small flat blade screwdriver to fi...

Страница 22: ...ONE CONTROLLER 4 Mount back cover to the wall using the provided mounting screws Mount the back cover to the wall with screws via screw holes It is recommended to use Wall Mates to secure mounting scr...

Страница 23: ...ay alter sensor readings Use of 8 Zone Sensors on the ESP Ultima System is not allowed Install Sensor at approximately 1 5m above the floor 1 Remove cover plate as shown below Use small flat blade scr...

Страница 24: ...Controls COVER PLATE 3 Connect cable plug to Sensor Zone Sensor LM ZS 2 Feed the sensor cable through the wall opening make sure not to damage the barb Protect the RJ45 connector barb by using tape WA...

Страница 25: ...es It is recommended to use Wall Mates to secure mounting screws tightly against the wall Ensure that the sensor is aligned and leveled on the wall before tightening the screws MOUNTING SCREWS WALL WA...

Страница 26: ...URE IN THE FAN COIL UNIT BEFORE REMOVING COPPER END CAPS ENSURE 3670 043 Sensor 4 CAUTION LIVE ELECTRICAL WIRING AUTHORISED TECHNICIANS ONLY INTERNAL CONTROL ISOLATOR FITTED MODEL MEPS CERTIFIED A U S...

Страница 27: ...Maximum Cumulative Cable Length per individual zone must not exceed 100 m per zone For Example 2 to 4A Optional 8 Zones Piggy Back Configuration if 2 to 4 is 75 m then 3 to 3A must be less than or eq...

Страница 28: ...ngth per individual zone must not exceed 100 m per zone For Example 2 to 3A Optional Zone Barrel with optional Zone Control if 2 to 3 is 75m then 3 to 3A must be less than or equal to 25m to be within...

Страница 29: ...TROL WC 1 C Two Remote Sensors With Two Wall Controls Mimic Logic OPTIONAL SENSOR 1 OPTIONAL SENSOR 2 ACT NEUT EARTH DATA R COM BL S 2 S 1 G KEY Y PWR R COM BK SCRN INDOOR BOARD AMIB TO OUTDOOR UNIT D...

Страница 30: ...One Zone Sensor Zone Temperature Averaging RJ45 3 WAY CABLE HOLDER IMPORTANT SEE NOTE BELOW MODULATION ZONING ZONE 4 ZONE 3 ZONE 2 ZONE 1 ZONE 8 ZONE 7 ZONE 6 ZONE 5 ULTIMA MODULE Part No 8Z VAV AMIB...

Страница 31: ...all Control and Secondary Wall Control Master Wall Control LM7 2 Optional Secondary Wall Control LM24 2 Optional NOTES Minimum 1 controller required For detailed identification and operation please re...

Страница 32: ...5 HEAT Mode Indicator Indicates that the zone is providing heating to your area 6 Temperature Display Indicates the set temperature or actual temperature during operation 7 Zone Indicator 8 ESP AUTO...

Страница 33: ...l be shown During power up horizontal bar will move back and forth for several seconds ROOM TEMP MODE ON OFF SET TEMP Z O N E C O N T R O L ROOM TEMP MODE ON OFF SET ZONE TEMP Z O N E C O N T R O L RO...

Страница 34: ...button on Master Control 2 When several zones are pressed in quick succession a delay will occur before all zone damper blades will fully open Press the ZONE button to turn off the zone and the zone L...

Страница 35: ...d ESP Auto To bring up different modes of operation press the button ROOM TEMP MODE ON OFF SET ZONE COOL ESP AUTO C TEMP Z O N E C O N T R O L ROOM TEMP MODE ON OFF SET ZONE OFF C TEMP Z O N E C O N T...

Страница 36: ...or a cooler room temperature press the button The number of vertical stripes damper blade position indicator may vary from time to time chasing your desired conditions IMPORTANT NOTE ESP Auto mode in...

Страница 37: ...Room Temperature Normally the Zone Control will show the setpoint temperature of the zones To check the actual temperature of the zone see below 1 Press the button to display the actual Room Zone temp...

Страница 38: ...NE button while the previous zone LED and are flashing NOTE Room temperature displayed can be the temperature at a Zone Control or at a remote sensor or the average of both depending on your installat...

Страница 39: ...25 078 Ver 2 190925 15 Zone Control And Sensor Mounting Dimensions 15 01 Zone Control LM ZC 2 ESP Ultima Only Note Drawn not to scale 101 5 mm 60mm 24mm 17mm 25mm 72 5 mm 12 mm 60mm 25mm 24mm 17mm 15...

Страница 40: ...ce and release NOTES Self Learn Mode should not be activated when there are obstructions in duct system layout When system layout of duct design is changed Self Learn Mode should be reactivated This w...

Страница 41: ...akes approx 30 seconds to reach set speed The above graph represents the approximate time taken for the fan to achieve its set speed upon selection In ESP mode the time will vary depending on the duct...

Страница 42: ...reas that may be on the same zone Q Is the sensor on the master control operational A No it s disregarded Q Would an in line fan cause any operational problems if installed A Yes it would An in line f...

Страница 43: ...umber my Zone Control is from the Zone Control A Yes When the system is first powered up the zone number is displayed on the Zone Control display You can also check the Zone number by holding the butt...

Страница 44: ...ns off at approximately 6 seconds after any button is pressed Note that the back light is not set to remain On Q Does the LM7 2 come standard with all R 410A ESP Plus units A Yes it does Q How can you...

Страница 45: ...etails Q Can the Wall Control show the room temperature as main display instead of setpoint A No the setpoint is always on display to prevent any confusion in the temperature setting To view the curre...

Страница 46: ...h 6 Mth 1 Yr 2 Yrs 3 Yrs 4 Yrs 5 Yrs Casing Panels and Frames Visual check for damage rust and dust accumulation For highly corrosive environment wash panels quarterly with water and neutral detergent...

Страница 47: ...040 159 1 1 1040 169 1 1040 177 1 1 1 1 3 Sensor Indoor Coil In 2060 016 1 1 1 1 1 1 1 1 1 1 1 4 Sensor Indoor Coil Out 2060 021 1 1 1 1 1 1 1 1 1 1 1 5 Coil Piston 4540 076 1 4540 110 1 1 4540 128 1...

Страница 48: ...d Trade Marks of Actron Engineering Pty Limited ActronAir is constantly seeking ways to improve the design of it s products therefore specifications are subject to change without notice Document 0525...