Installation and Commissioning Guide

Split Ducted ESP Indoor Unit

Installation and Commissioning Guide - Split Ducted ESP Plus/Ultima Indoor Unit

Doc. No.0525-078   

Ver. 2  190925

08. Safety Drain Tray 

 NOTES

•  Refer to indoor unit dimension page for specification of drain connectors.
•  Test condensate drain installation to ensure that water flows freely and does not leak. Also check that the drain tray does 

not overflow.

Suggested Minimum Slope To Ensure Correct Drainage

INDOOR COIL

RETURN AIR

INDOOR COIL

CONDENSATE DRAIN MUST BE

RUN SEPERATLY FROM THE

SAFETY TRAY DRAIN

SAFETY TRAY DRAIN

CONNECTION

CONDENSATE DRAIN

CONNECTION

SUPPLY AIR

INTERNAL CONDENSATE TRAY

THE TOP OF THE P-TRAP

MUST BE 50MM BELOW THE

TOP OF THE CONDENSATE

DRAIN CONNECTION

THE TOP OF THE P-TRAP

MUST BE 50MM BELOW THE

TOP OF THE CONDENSATE

DRAIN CONNECTION

INSTALL A T-PIECE AS AN

AIR VENT FOR LONG DRAIN RUNS.

CLEAR

PLASTIC

INSPECTION

TUBE

P.V.C

ELBOW

CLAMP

BANDS

SEAL WITH

SILICONE

SEALANT

PREFERRED METHOD

OF CONNECTING P-TRAP

P.V.C

ELBOW

25MM

15MM

P-TRAP

ENSURE DRAIN PIPES

SLOPE DOWN FROM THE

FAN COIL AT A MINIMUM

OF 10MM PER METRE

CONDENSATE AND SAFETY TRAY

DRAINAGE

DFDRAIN - 100505

05 - 05 - 2010

REVISION DATE

DRAWING NUMBER

DESIGNS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Suggested P-Trap Connection With Limited Height Clearance

Suggested P-Trap Connection With Long Drain Runs

Содержание ESP Plus Series

Страница 1: ...Guide Indoor Model Numbers ESP Plus ESP Ultima SRV131E SRV151E SRV171E SRV191E SRV201E SRV231E SRM151E SRM171E SRM191E SRM201E SRM231E IMPORTANT NOTE Please read this manual carefully before installin...

Страница 2: ...SRV201E SRM201E 11 05 04 SRV231E SRM231E 12 06 Installation Instructions 13 07 Unit Lifting Procedures 15 07 01 Crane Lifting Method 15 07 02 Fork Lift Method 16 08 Safety Drain Tray 17 09 Zone Barre...

Страница 3: ...our shipment Inspect the unit components and accessories for any sign of damage If there is any damage to the unit contact ActronAir Customer Care Department immediately on 1300 522 722 Check the unit...

Страница 4: ...e that they can use the appliance safely Young children should be supervised to ensure that they do not play with the appliance Installer must incorporate a means of electrical disconnection isolator...

Страница 5: ...door Unit Doc No 0525 078 Ver 2 190925 03 Components Overview 03 01 Indoor Unit Components Overview EC MOTOR INDOOR UNIT LID CONTROL PANEL ID COIL INDOOR CONTROL PANEL 8 ZONE MODULE 03 02 Indoor Unit...

Страница 6: ...ATA COM White Black SCRN Blue 8Z 24V M SERIES 8 ZONE MODULE Part No 2020 170 WARNING DAMAGE DUE TO INCORRECT WIRING VOIDS WARRANTY ON OFF ZONING INTERNAL 2A FUSE N A E 04 02 ESP Ultima Standard Parts...

Страница 7: ...B 14 350 14 350 mm 290 mm ZB 16 400 16 400 mm 290 mm Cat5e Zone Cable Sold Separately For ESP Plus Part Number Length Connector 4070 020 7 metres RJ45 4070 021 20 metres RJ45 For ESP Ultima Part Numbe...

Страница 8: ...art Number LM ZC 2W White LM ZC 2G Grey Voltage 24 VAC Connections RJ45 Socket Dimensions mm 72 5 x 101 5 x 12 W x H x D Zone Sensor Sold separately Part Number LM ZS 2W White LM ZS 2G Grey Connection...

Страница 9: ...50 115 247 5 247 5 575 SUPPLY AIR RETURN AIR 1290 O A 40 535 70 50 EC INDOOR FAN EC INDOOR FAN SUPPLY AIR MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES NOTES 1 Do not scale drawing All dimensio...

Страница 10: ...perimeter is available 4 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJ...

Страница 11: ...ess clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION EC ID FAN EC ID FAN INDOOR COIL HEIGH...

Страница 12: ...or any extra charge incurred due to lack of access THIRD ANGLE PROJECTION EC ID FAN EC ID FAN HEIGHT CLEARANCE 410mm DUCT WORK DUCT WORK 890 mm SERVICE CLEARANCE 890 mm SERVICE CLEARANCE ELECTRICALS R...

Страница 13: ...der to minimize the transfer of noise and vibration into building structures An optional hanging bracket assembly and rubber grommet supplied as standard with SRV231E and SRM231E are also available to...

Страница 14: ...by both of the supply air plenum and the twin spigot duct plate Fan Coil With Vertical Discharge Optional An upright Fan Coil with vertical supply air discharge is also available wherein installation...

Страница 15: ...ommended that installer observe current industry safe rigging and lifting procedure DETAIL A PALLET INDOOR UNIT Slip nylon slings through the pallet SRD175C S SELECTION DATA DIGITAL SCROLL COMPRESSOR...

Страница 16: ...Hz POWER SUPPLY INDOOR 240V 1 Ph 50 Hz RATED LOAD AMPS OUTDOOR INDOOR TOTAL 22 0 3 1 25 1 FULL LOAD AMPS OUTDOOR INDOOR TOTAL 32 6 4 0 36 6 CIRCUIT BREAKER AND CABLE AMPS 40 0 APPROXIMATE STARTING AM...

Страница 17: ...ONNECTION CONDENSATE DRAIN CONNECTION SUPPLY AIR INTERNAL CONDENSATE TRAY THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION THE TOP OF THE P TRAP MUST BE 50MM BELOW T...

Страница 18: ...E PARTS INTEGRATED ZONE BARRELS OPERATE WITH M SERIES CONTROLS ONLY 24 VOLT 8 ZONE KIT 8Z 24V AMZ 24V ZONE CARD 20VA 240 TO 24 VOLT TRANSFORMER INSTALLATION INSTRUCTIONS MOUNTING SCREWS LENGTH OF ALL...

Страница 19: ...slot at the top and the bottom of the Control Interface Do this procedure alternately between the four slots until the back cover of the control separates Use large enough flat blade screwdriver to fi...

Страница 20: ...e buttons for zone name to be allocated BUTTON PAD 7 Assign and attach zones Attach the desired zone buttons and assign names to each zone Ensure the buttons make a click sound when attached to the PC...

Страница 21: ...directly below the supply air grille or near other additional heat load sources as these locations may alter sensor readings 1 Remove cover plate as shown below Use small flat blade screwdriver to fi...

Страница 22: ...ONE CONTROLLER 4 Mount back cover to the wall using the provided mounting screws Mount the back cover to the wall with screws via screw holes It is recommended to use Wall Mates to secure mounting scr...

Страница 23: ...ay alter sensor readings Use of 8 Zone Sensors on the ESP Ultima System is not allowed Install Sensor at approximately 1 5m above the floor 1 Remove cover plate as shown below Use small flat blade scr...

Страница 24: ...Controls COVER PLATE 3 Connect cable plug to Sensor Zone Sensor LM ZS 2 Feed the sensor cable through the wall opening make sure not to damage the barb Protect the RJ45 connector barb by using tape WA...

Страница 25: ...es It is recommended to use Wall Mates to secure mounting screws tightly against the wall Ensure that the sensor is aligned and leveled on the wall before tightening the screws MOUNTING SCREWS WALL WA...

Страница 26: ...URE IN THE FAN COIL UNIT BEFORE REMOVING COPPER END CAPS ENSURE 3670 043 Sensor 4 CAUTION LIVE ELECTRICAL WIRING AUTHORISED TECHNICIANS ONLY INTERNAL CONTROL ISOLATOR FITTED MODEL MEPS CERTIFIED A U S...

Страница 27: ...Maximum Cumulative Cable Length per individual zone must not exceed 100 m per zone For Example 2 to 4A Optional 8 Zones Piggy Back Configuration if 2 to 4 is 75 m then 3 to 3A must be less than or eq...

Страница 28: ...ngth per individual zone must not exceed 100 m per zone For Example 2 to 3A Optional Zone Barrel with optional Zone Control if 2 to 3 is 75m then 3 to 3A must be less than or equal to 25m to be within...

Страница 29: ...TROL WC 1 C Two Remote Sensors With Two Wall Controls Mimic Logic OPTIONAL SENSOR 1 OPTIONAL SENSOR 2 ACT NEUT EARTH DATA R COM BL S 2 S 1 G KEY Y PWR R COM BK SCRN INDOOR BOARD AMIB TO OUTDOOR UNIT D...

Страница 30: ...One Zone Sensor Zone Temperature Averaging RJ45 3 WAY CABLE HOLDER IMPORTANT SEE NOTE BELOW MODULATION ZONING ZONE 4 ZONE 3 ZONE 2 ZONE 1 ZONE 8 ZONE 7 ZONE 6 ZONE 5 ULTIMA MODULE Part No 8Z VAV AMIB...

Страница 31: ...all Control and Secondary Wall Control Master Wall Control LM7 2 Optional Secondary Wall Control LM24 2 Optional NOTES Minimum 1 controller required For detailed identification and operation please re...

Страница 32: ...5 HEAT Mode Indicator Indicates that the zone is providing heating to your area 6 Temperature Display Indicates the set temperature or actual temperature during operation 7 Zone Indicator 8 ESP AUTO...

Страница 33: ...l be shown During power up horizontal bar will move back and forth for several seconds ROOM TEMP MODE ON OFF SET TEMP Z O N E C O N T R O L ROOM TEMP MODE ON OFF SET ZONE TEMP Z O N E C O N T R O L RO...

Страница 34: ...button on Master Control 2 When several zones are pressed in quick succession a delay will occur before all zone damper blades will fully open Press the ZONE button to turn off the zone and the zone L...

Страница 35: ...d ESP Auto To bring up different modes of operation press the button ROOM TEMP MODE ON OFF SET ZONE COOL ESP AUTO C TEMP Z O N E C O N T R O L ROOM TEMP MODE ON OFF SET ZONE OFF C TEMP Z O N E C O N T...

Страница 36: ...or a cooler room temperature press the button The number of vertical stripes damper blade position indicator may vary from time to time chasing your desired conditions IMPORTANT NOTE ESP Auto mode in...

Страница 37: ...Room Temperature Normally the Zone Control will show the setpoint temperature of the zones To check the actual temperature of the zone see below 1 Press the button to display the actual Room Zone temp...

Страница 38: ...NE button while the previous zone LED and are flashing NOTE Room temperature displayed can be the temperature at a Zone Control or at a remote sensor or the average of both depending on your installat...

Страница 39: ...25 078 Ver 2 190925 15 Zone Control And Sensor Mounting Dimensions 15 01 Zone Control LM ZC 2 ESP Ultima Only Note Drawn not to scale 101 5 mm 60mm 24mm 17mm 25mm 72 5 mm 12 mm 60mm 25mm 24mm 17mm 15...

Страница 40: ...ce and release NOTES Self Learn Mode should not be activated when there are obstructions in duct system layout When system layout of duct design is changed Self Learn Mode should be reactivated This w...

Страница 41: ...akes approx 30 seconds to reach set speed The above graph represents the approximate time taken for the fan to achieve its set speed upon selection In ESP mode the time will vary depending on the duct...

Страница 42: ...reas that may be on the same zone Q Is the sensor on the master control operational A No it s disregarded Q Would an in line fan cause any operational problems if installed A Yes it would An in line f...

Страница 43: ...umber my Zone Control is from the Zone Control A Yes When the system is first powered up the zone number is displayed on the Zone Control display You can also check the Zone number by holding the butt...

Страница 44: ...ns off at approximately 6 seconds after any button is pressed Note that the back light is not set to remain On Q Does the LM7 2 come standard with all R 410A ESP Plus units A Yes it does Q How can you...

Страница 45: ...etails Q Can the Wall Control show the room temperature as main display instead of setpoint A No the setpoint is always on display to prevent any confusion in the temperature setting To view the curre...

Страница 46: ...h 6 Mth 1 Yr 2 Yrs 3 Yrs 4 Yrs 5 Yrs Casing Panels and Frames Visual check for damage rust and dust accumulation For highly corrosive environment wash panels quarterly with water and neutral detergent...

Страница 47: ...040 159 1 1 1040 169 1 1040 177 1 1 1 1 3 Sensor Indoor Coil In 2060 016 1 1 1 1 1 1 1 1 1 1 1 4 Sensor Indoor Coil Out 2060 021 1 1 1 1 1 1 1 1 1 1 1 5 Coil Piston 4540 076 1 4540 110 1 1 4540 128 1...

Страница 48: ...d Trade Marks of Actron Engineering Pty Limited ActronAir is constantly seeking ways to improve the design of it s products therefore specifications are subject to change without notice Document 0525...

Отзывы: