A Wall Control can not be used if the ActronAir AC system is configured for Advanced BMS Control.
Additional information for controlling the unit in Advanced BMS Control can be found in Section 05.02.
04.07.05. UNO Configuration
To configure the ActronAir AC system for Advanced BMS Control, follow the procedure using the 7-segment display on
the UNO Board below:
Step 1. Press the
MENU
button to navigate to
SEt
(Settings), press the
ENTER
button to enter sub-menu.
Step 2. Press the
MENU
button to navigate to
CtrS
(Control Source), press the
ENTER
button to enter sub-menu,
Step 3. Press the
MENU
button to navigate to
4
(Advanced BMS), press the
ENTER
button to accept.
Step 4. Press the
BACK
button twice to return to Main Screen.
04.08. Troubleshooting
The LEDs on the board indicate the status of the BMS Card. Use the troubleshooting table on the following page to resolve
any issues.
STATUS
LEDS
BMS CARD STATUS
LED INDICATION
Power to BMS Card
Red Power LED ON
Successful communication with A/C unit
Amber Status LED ON
Successful communication with BMS controller
White Status LED ON