If installed near a furnace or where emergency heat coils could raise the
temperature inside the plenum, cycle the AC unit through three full heating
cycles assuring that the temperature never exceeds 200 °F
(93 °C). The ActivePure
®
Cell must not exceed 200 °F (93 °C).
WARNING
INSTALLATION REQUIREMENTS
CAUTION
• This unit must be installed by a licensed HVAC contractor or electrician;
failure to do so will void warranty of the product
• When the unit is installed in a roof mounted HVAC system, the unit must be
protected from the elements
1.
Unit should be installed after the air handler in the
HVAC system.
2.
The ductwork around the installation area should
be clean and dry to ensure proper adhesion of the
gasket materials and any tape used.
3.
When installing near a furnace or heating coils, run
the heating system through three (3) full heating
cycles to ensure the temperature of the INDUCT unit
does not exceed 200˚F.
4.
An approximate 3.5” (8.89 cm) opening will need to
be cut into the existing ductwork to install the unit
properly.
Min. 8” x 8” Metal
Ductwork
Min. 10” x 10”
Fiberglass
Ductwork
Air Handle
Max.
6 ft.
Installation Clearance