Ceiling Concealed Fan Coil Unit (R22)
Sound Pressure
Microphone position: 1.4m below the centre of the unit. (GB Standard - GB/D17758)
Tested with 2m length duct at the air discharge outlet and air return inlet.
Measuring Location:
Test Unit
2m length test duct
2m length test duct
Air
1.4m
Microphone
Ext. Static
Overall
Noise
(mmAq)
125Hz
250Hz
500Hz
1kHz
2kHz
4kHz
8kHz
A (dBA) Criteria
ACC 30C
21
Super High
54
50
46
45
40
34
30
49
44
17
High
50
45
43
42
37
31
26
46
41
13
Medium
45
40
40
38
32
26
20
42
37
9
Low
42
36
37
33
28
22
15
38
32
ACC 40C
21
Super High
56
49
49
46
41
37
32
51
45
18
High
54
47
47
45
39
35
29
49
44
13
Medium
49
42
43
41
35
31
24
45
40
9.5
Low
45
39
41
37
30
26
18
41
36
ACC 50C
18
Super High
56
50
50
49
44
38
33
53
48
16
High
54
49
49
48
43
37
32
52
47
14
Medium
53
47
46
47
40
35
29
50
46
11
Low
51
45
44
44
36
32
26
47
43
ACC 60C
18
Super High
57
50
51
51
46
39
35
55
50
16
High
55
49
49
50
44
37
33
53
49
14
Medium
53
46
47
47
39
34
28
50
46
10
Low
51
43
44
43
35
30
24
47
42
1/1 Octave A-weighted Sound Pressure (dBA), ref 20µPa
Model
Speed
Содержание AWSS30A
Страница 1: ...Technical Manual WATER COOLED SINGLE SPLIT AWSS30A AWSS40A AWSS50A AWSS60A...
Страница 13: ...13 Refrigerant Circuit Diagrams Model AWSS 30 40 50 60A...
Страница 63: ...107 Indoor Unit MODEL ACC30C Outdoor Unit MODEL AWSS30A 10 WIRING DIAGRAMS...
Страница 64: ...108 Indoor Unit Model ACC40 50 60C Outdoor Unit Model AWSS40 50 60A...
Страница 65: ...110 Indoor Unit Model ACK30A Outdoor Unit MODEL AWSS30A...
Страница 66: ...111 Indoor Unit Model ACK40 50A Outdoor Unit MODEL AWSS40 50A...