Refrigerant Piping
Copper Pipe Connection
Do not use contaminated, dented or used copper tubing. Do not use copper tubes with less than 0.8mm
thickness. Remove burns from cut edges of the pipes with remover. Hold the end of the pipe downwards
to prevent metal chips from entering the pipe. Use proper torgue wrench to tight the flare nuts. If the
torque strength is weak, gas leakage may occur. If it is too tight the flare nut may crack and it may be non-
removable. Insulate the piping to prevent capacity losses and water.
Flare Work
Head projection dimension may differ according to type of flare tool. Refer to table below:
Flare section should be uniform or even. Crack on the flare section or burr on the flare edge is not
acceptable. Make new flare tubing again to prevent potential gas leak.
Diameter
in
1/4
3/8
1/2
5/8
3/4
mm
6.35
9.52
12.70
15.88
19.05
Imperial
1.3
1.6
1.9
2.2
2.5
Rigid
0.7
1.0
1.3
1.7
2.0
A(mm)
Diameter D
in
1/4
3/8
1/2
5/8
3/4
mm
6.35
9.52
12.70
15.88
19.05
9.1
13.2
16.6
19.7
24.0
Flare End Diameter
FLARE DIE
COPPER TUBE
HEAD PROJECTION DIMENSION
A
B
D
COPPER TUBE
FLARE UNIT
Содержание AWSS30A
Страница 1: ...Technical Manual WATER COOLED SINGLE SPLIT AWSS30A AWSS40A AWSS50A AWSS60A...
Страница 13: ...13 Refrigerant Circuit Diagrams Model AWSS 30 40 50 60A...
Страница 63: ...107 Indoor Unit MODEL ACC30C Outdoor Unit MODEL AWSS30A 10 WIRING DIAGRAMS...
Страница 64: ...108 Indoor Unit Model ACC40 50 60C Outdoor Unit Model AWSS40 50 60A...
Страница 65: ...110 Indoor Unit Model ACK30A Outdoor Unit MODEL AWSS30A...
Страница 66: ...111 Indoor Unit Model ACK40 50A Outdoor Unit MODEL AWSS40 50A...