The most common causes of air conditioner failure to “start" are:
a) Voltage not within
±
10% of rated voltage.
b) Power supply interrupted.
c) Control settings improper.
d) Air conditioner is disconnected from main power source.
e) Fuse blown or circuit breaker off.
ii) DIAGNOSIS OF REFRIGERANT CIRCUIT / APPLICATION
There might be some cases where the unit starts running but does not perform satisfactory, i.e.
insufficient cooling. Judgement could be made by measuring temperature difference of indoor
unit's intake and discharge air as well as running current.
Insufficient Cooling
Unit Starts
Excessive heat
source e.g. electric
kettle
High heat load
Refrigerant circuit
Leakage
Restriction e.g. at
strainer, capillary,
filter dryer, etc.
Compressor
Less or no compression
(Low running current)
Room overcrowded
with people
Windows / doors
wide open
Check air circulation
Indoor/Outdoor coil dirty
(clogged)
Air filters dirty
Fan Malfunction
Obstruction at air inlet/outlet
of indoor/outdoor unit
Satisfactory operation with temperature difference of
air intake & discharge of indoor unit 10°C - 15°C
Insufficient Heating
Unit Starts
High heat load
Refrigerant circuit
Leakage
Restriction e.g. at
strainer, capillary,
filter dryer, etc.
Compressor
Less or no compression
(Low running current)
Windows / doors
wide open
Check air circulation
Indoor/Outdoor coil dirty (clogged)
Air filters dirty
Fan Malfunction
Obstruction at air inlet/outlet
of indoor/outdoor unit
Satisfactory operation with temperature difference of
air intake & discharge of indoor unit 16°C - 25°C
Содержание ACC 10 C/CR
Страница 16: ...15 MODEL ACC50C MODEL ACC60C...
Страница 20: ...19 MODEL ALC 30 40 50 60 C CR A4LC 30 40 50 C CR Note Dimension in mm MODEL AMC 60 C CR Note Dimension in mm...
Страница 25: ...24 MODEL ACC 40C 50C ALC A4LC 40C 50C FOR LOCAL SPEC MODEL ACC 60C ALC 60C FOR EXPORT SPEC WITH MC SLM C3 0BCC...
Страница 26: ...25 MODEL ACC 60 ALC 60C FOR EXPORT SPEC WITH MC MODEL ACC 60C ALC 60C FOR LOCAL SPEC...
Страница 27: ...26 MODEL ACC 60C AMC 60C FOR EXPORT SPEC WITH SLM CONTROL C3 0BCC...
Страница 28: ...27 MODEL ACC 10CR 15CR ALC A4LC 10BR 15BR...
Страница 29: ...28 MODEL ACC 20CR 25CR ALC A4LC 20BR 25BR...
Страница 30: ...29 MODEL ACC 30CR ALC A4LC 30CR...
Страница 31: ...30 MODEL ACC 40CR 50CR ALC A4LC 40CR 50CR...
Страница 32: ...31 MODEL ACC 60CR ALC 60CR...
Страница 33: ...32 MODEL ACC 60CR AMC 60CR FOR EXPORT SPEC WITH SLM CONTROL C3 0BCC...
Страница 37: ...36 MODEL ACC 60C AMC 60C FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 38: ...37 MODEL ACC 10 15CR ALC A4LC 10 15BR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 39: ...38 MODEL ACC 20 25CR ALC A4LC 20 25BR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 40: ...39 MODEL ACC 30CR ALC A4LC 30CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 41: ...40 MODEL ACC 40 50CR ALC A4LC 40 50CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 42: ...41 MODEL ACC 60CR ALC 60CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 43: ...42 MODEL ACC 60CR AMC 60CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 46: ...45 MODEL ALC 20 25BR HEAT PUMP 3 PHASE 50HZ 380 415V MODEL ALC 30CR HEAT PUMP 3 PHASE 50HZ 380 415V...
Страница 49: ...48 LOW AMBIENT UNIT OPTIONAL OUTDOOR UNIT MODEL ALC 10B 15B 50HZ OUTDOOR UNIT MODEL ALC 20B 25B 50HZ...