51
c)
Ensure that the compressor is not expose to open air for more than the recommended time specified by
its manufacturer (typically less than 10 minutes). Removed the seal-plugs only when the compressor is
about to be brazed.
d)
The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e)
When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
Composition of R407C in vapour phase
is different from liquid phase.
f) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if
the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
g) When servicing leak, the top-up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made-up of three different components, may have changed during the leak. Consequently, a
top-up may not ensure that the R407C in the system is of original composition. This composition shift
may adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.
R32/R125/R134
33% / 33% / 34%
23% / 25% / 52%
Dip-pipe
Invert cylinder
without dip-pipe
Liquid
withdrawal
Содержание ACC 10 C/CR
Страница 16: ...15 MODEL ACC50C MODEL ACC60C...
Страница 20: ...19 MODEL ALC 30 40 50 60 C CR A4LC 30 40 50 C CR Note Dimension in mm MODEL AMC 60 C CR Note Dimension in mm...
Страница 25: ...24 MODEL ACC 40C 50C ALC A4LC 40C 50C FOR LOCAL SPEC MODEL ACC 60C ALC 60C FOR EXPORT SPEC WITH MC SLM C3 0BCC...
Страница 26: ...25 MODEL ACC 60 ALC 60C FOR EXPORT SPEC WITH MC MODEL ACC 60C ALC 60C FOR LOCAL SPEC...
Страница 27: ...26 MODEL ACC 60C AMC 60C FOR EXPORT SPEC WITH SLM CONTROL C3 0BCC...
Страница 28: ...27 MODEL ACC 10CR 15CR ALC A4LC 10BR 15BR...
Страница 29: ...28 MODEL ACC 20CR 25CR ALC A4LC 20BR 25BR...
Страница 30: ...29 MODEL ACC 30CR ALC A4LC 30CR...
Страница 31: ...30 MODEL ACC 40CR 50CR ALC A4LC 40CR 50CR...
Страница 32: ...31 MODEL ACC 60CR ALC 60CR...
Страница 33: ...32 MODEL ACC 60CR AMC 60CR FOR EXPORT SPEC WITH SLM CONTROL C3 0BCC...
Страница 37: ...36 MODEL ACC 60C AMC 60C FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 38: ...37 MODEL ACC 10 15CR ALC A4LC 10 15BR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 39: ...38 MODEL ACC 20 25CR ALC A4LC 20 25BR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 40: ...39 MODEL ACC 30CR ALC A4LC 30CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 41: ...40 MODEL ACC 40 50CR ALC A4LC 40 50CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 42: ...41 MODEL ACC 60CR ALC 60CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 43: ...42 MODEL ACC 60CR AMC 60CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 46: ...45 MODEL ALC 20 25BR HEAT PUMP 3 PHASE 50HZ 380 415V MODEL ALC 30CR HEAT PUMP 3 PHASE 50HZ 380 415V...
Страница 49: ...48 LOW AMBIENT UNIT OPTIONAL OUTDOOR UNIT MODEL ALC 10B 15B 50HZ OUTDOOR UNIT MODEL ALC 20B 25B 50HZ...