STANDARD OPERATING CONDITION
COOLING ONLY UNIT
Temperature
Ts °C
Th °C
minimum indoor temperature
19.4
13.9
maximum indoor temperature
26.7
19.4
minimum outdoor temperature
19.4
13.9
maximum- outdoor temperature
46.0
24.0
HEAT PUMP UNIT
Temperature
Ts °C
Th °C
minimum indoor temperature
10.0
-
maximum indoor temperature
26.7
-
minimum outdoor temperature
- 8.0
- 9.0
maximum- outdoor temperature
24
18
Ts : Dry bulb temperature
Th : Wet bulb temperature
OPERATING STATE AND FAULT TABLE
COOLING (C3B BOARD)
HIGH
FAN
MED.
FAN
LOW
FAN
COOL
SLEEP
TIMER
OPERATION / FAULTY INDICATION
ACTION
ROOM SENSOR CONTACT LOOSE / SHORT CALL YOUR DEALER
INDOOR COIL SENSOR CONTACT LOOSE /
SHORT
CALL YOUR DEALER
OUTDOOR COIL SENSOR CONTACT
LOOSE / SHORT
CALL YOUR DEALER
GAS LEAK
CALL YOUR DEALER
COMPRESSOR OVERLOAD
CALL YOUR DEALER
HEAT PUMP (C3B BOARD)
HIGH
FAN
MED.
FAN
LOW
FAN
COOL
SLEEP TIMER
HEAT
OPERATION / FAULTY INDICATION
ACTION
ROOM SENSOR CONTACT LOOSE / SHORT CALL YOUR DEALER
INDOOR COIL SENSOR CONTACT LOOSE /
SHORT
CALL YOUR DEALER
OUTDOOR COIL SENSOR CONTACT
LOOSE / SHORT
CALL YOUR DEALER
GAS LEAK
CALL YOUR DEALER
COMPRESSOR OVERLOAD
CALL YOUR DEALER
OUTDOOR DEFROST
-
m
ON
m
/
l
ON OR OFF
BLINKING
COOLING & HEATPUMP (UNIVERSAL BOARD)
ERROR CODE AT 7 SEGMENT DISPLAY
OPERATION / FAULTY INDICATION
E1 BLINKING
ROOM SENSOR CONTACT LOOSE / SHORT
E2 BLINKING
INDOOR COIL SENSOR CONTACT LOOSE / SHORT
E3 BLINKING
OUTDOOR COIL SENSOR CONTACT LOOSE / SHORT
E4 BLINKING
COMPRESSOR OVERLOAD
E5 BLINKING
GAS LEAK
E6 BLINKING
NA
HEAT LED BLINKING
OUTDOOR DEFROST (FOR HEAT PUMP ONLY)
Содержание ACC 10 C/CR
Страница 16: ...15 MODEL ACC50C MODEL ACC60C...
Страница 20: ...19 MODEL ALC 30 40 50 60 C CR A4LC 30 40 50 C CR Note Dimension in mm MODEL AMC 60 C CR Note Dimension in mm...
Страница 25: ...24 MODEL ACC 40C 50C ALC A4LC 40C 50C FOR LOCAL SPEC MODEL ACC 60C ALC 60C FOR EXPORT SPEC WITH MC SLM C3 0BCC...
Страница 26: ...25 MODEL ACC 60 ALC 60C FOR EXPORT SPEC WITH MC MODEL ACC 60C ALC 60C FOR LOCAL SPEC...
Страница 27: ...26 MODEL ACC 60C AMC 60C FOR EXPORT SPEC WITH SLM CONTROL C3 0BCC...
Страница 28: ...27 MODEL ACC 10CR 15CR ALC A4LC 10BR 15BR...
Страница 29: ...28 MODEL ACC 20CR 25CR ALC A4LC 20BR 25BR...
Страница 30: ...29 MODEL ACC 30CR ALC A4LC 30CR...
Страница 31: ...30 MODEL ACC 40CR 50CR ALC A4LC 40CR 50CR...
Страница 32: ...31 MODEL ACC 60CR ALC 60CR...
Страница 33: ...32 MODEL ACC 60CR AMC 60CR FOR EXPORT SPEC WITH SLM CONTROL C3 0BCC...
Страница 37: ...36 MODEL ACC 60C AMC 60C FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 38: ...37 MODEL ACC 10 15CR ALC A4LC 10 15BR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 39: ...38 MODEL ACC 20 25CR ALC A4LC 20 25BR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 40: ...39 MODEL ACC 30CR ALC A4LC 30CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 41: ...40 MODEL ACC 40 50CR ALC A4LC 40 50CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 42: ...41 MODEL ACC 60CR ALC 60CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 43: ...42 MODEL ACC 60CR AMC 60CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Страница 46: ...45 MODEL ALC 20 25BR HEAT PUMP 3 PHASE 50HZ 380 415V MODEL ALC 30CR HEAT PUMP 3 PHASE 50HZ 380 415V...
Страница 49: ...48 LOW AMBIENT UNIT OPTIONAL OUTDOOR UNIT MODEL ALC 10B 15B 50HZ OUTDOOR UNIT MODEL ALC 20B 25B 50HZ...