57
A5MSX-2009
Troubleshooting
Blinks Blinking
Indication
1
Normal running, with no limitation
2
Voltage limit
3
Cooling unit : Outdoor coil temperature limit
Heating unit : Indoor coil temperature limit
4
Total current limit
5
Discharge temperature unit
6
Cooling unit : Indoor coil temperature limit
7
Indoor fan control
8
Outdoor frequency adjustment
Blink
n
o
it
c
A
e
v
it
c
e
r
r
o
C
n
o
it
a
c
i
d
n
I
tl
u
a
F
RED
LED
LED
0
1
Outdoor ambient sensor error
Check outdoor ambient sensor wire and connection
0
2
Outdoor coil sensor error
Check outdoor coil sensor wire and connection
0
3
Outdoor discharge sensor error/
Check outdoor discharge sensor wire and connection/
Compressor overheat indication
Check pressure and compressor/Not enough refrigerant/
indoor overload
0
4
DC compressor feedback error
Check compressor wire and feedback wire
0
5
Commnication error
Check communication wire and connection for both
indoor and outdoor
0
6
Over current error
Check total current:check pressure and compressor
e
r
o
n
g
I
d
a
o
l
o
N
7
0
0
8
Over/ under voltage
Check power supply
0
9
DC compressor start failure
Check compressor wire and feedback wire;check
compresor
1
0
Cooling overload
Check whether outdoor unit is blocked or not;check pressure
e
r
o
n
g
I
t
s
o
rf
e
D
1
1
1
2
IPM Proctection
Check power supply; check main board/filter board; check
bridge diode; check IPM board; check compressor
1
3
EEPROM
Check EEPROM chip connection
1
4
EEPROM write error
Check EEPROM chip connection
1
5
DC fan motor no feed back
Check fan motor wire connection
1
6
AC peak current error
1
7
Outdoor suction sensor error
Check outdoor suction sensor wire and connection
1
9
DC compressor speed control error Check IPM board; check compressor
2
1
Outdoor suction A sensor error
Check suction sensor wire pipe A and connection
2
2
Outdoor suction B sensor error
Check suction sensor wire pipe B and connection
2
3
Outdoor suction C sensor error
Check suction sensor wire pipe C and connection
2
4
Outdoor suction D sensor error
Check suction sensor wire pipe D and connection
3
1
Indoor A communication error
Check communication wire and connection with indoor A
3
2
Indoor B communication error
Check communication wire and connection with indoor B
3
3
Indoor C communication error
Check communication wire and connection with indoor C
3
4
Indoor D communication error
Check communication wire and connection with indoor D
Normal Running Mode Condition
If the air conditioner unit has no faulty indications and the compressor is running at normal mode, the outdoor
P.C. Board’s LED indication will blink at a slower pace. The table below shows the significant meaning of
different running mode and limitation for this air conditioner unit.One must not attempt to see the LED
indication blinking unless instructed to do so.
Compressor Stopped Error Indication And Troubleshooting Guide
If the compressor stop unexpectedly, the outdoor P.C.Board’s LED indication will blink accordingly to the
error it detects. The table below shows the meaning according to the number of LED blinking and the
corrective action that one should take.
YELLOW
Содержание A5MSX 20 A
Страница 1: ...DC Inverter Multi Split A5MSX 2009 Models A5MSX 20 A AR A5MSX 25 A AR A5MSX 30 A AR...
Страница 2: ......
Страница 11: ...8 A5MSX 2009 Application Information Model A5MSX25A A5WMX10 20G Model A5MSX25AR A5WMX10 15 20GR...
Страница 12: ...9 A5MSX 2009 Model A5MSX30A A5WMX10 20G Model A5MSX30AR A5WMX10 20GR Application Information...
Страница 48: ...45 A5MSX 2009 Outline and Dimension Indoor Unit Model A5WMX10 15G GR m m n i n o i s n e m i D e t o N...
Страница 49: ...46 A5MSX 2009 Outline and Dimension Indoor Unit Model A5WMX20G GR m m n i n o i s n e m i D e t o N...
Страница 55: ...52 A5MSX 2009 Wiring Diagram Indoor Unit Model A5WMX10 15 20G GR Outdoor Unit Model A5MSX25A AR 70 03 4 088704...
Страница 56: ...53 A5MSX 2009 Wiring Diagram Indoor Unit Model A5WMX10 15 20G GR Outdoor Unit Model A5MSX30A AR 70 03 4 089435...