21
A5MSX-2009
Vacuuming And Charging
Purging The Piping And Indoor Unit
Except for the outdoor unit which is pre-charged with refrigerant R22, the indoor unit and the refrigerant
connection pipes must be air-purged because the air containing moisture that remains in the refrigerant cycle
may cause malfunction of the compressor.
• Make sure all pipes are connected securely to the outdoor and indoor valves.
• Remove the caps from the flare valve and the service. Take note that there are a total of two service ports
for A5MSX20A/AR, three service ports for A5MSX25A/AR and four service ports for A5MSX30A/AR.
• Connect the center of the charging gauge to the vacuum pump.
• Starting from the bottom 3-way valve (labeled A), connect the charging gauge to the 3-way valve’s service
port. (The numbers of service ports depend on the O/D unit model).
• Start the vacuum pump. Evacuate for approximately 30 minutes. The evacuation time varies with different
vacuum pump capacity. Confirm that the charging gauge needle has moved towards -760mmHg.
• Proceed to the next 3-way valve and repeat the steps above.
Caution
• If the gauge needle does not move to - 760mmHg, be ure to check for gas leaks (using the refrigerant
detector) at flare type connection of the indoor and outdoor unit and repair the leak before proceeding
to the next step.
• Close the valve of the charging gauge and stop the vacuum pump.
• On the outdoor unit, open the suction valve (3 way) and liquid valve (2 way) (in anti-clockwise direction) with
4mm key for hexagon sacked screw.
Additional Charge
The refrigerant is pre-charged in the outdoor unit for specific piping length. Please refer to page 1-5 for further
detail on additional charge.
Service Port
Outdoor Unit 3 ways valve
Flare nut
Refrigerant Piping
Allen key
Suction
valve
Discharge
Valve
Indoor Unit
Outdoor Unit
Liquid side
Gas side
Vacuum
pump
Open
Close
Close
Close
Hi
Low
Application Information
Содержание A5MSX 20 A
Страница 1: ...DC Inverter Multi Split A5MSX 2009 Models A5MSX 20 A AR A5MSX 25 A AR A5MSX 30 A AR...
Страница 2: ......
Страница 11: ...8 A5MSX 2009 Application Information Model A5MSX25A A5WMX10 20G Model A5MSX25AR A5WMX10 15 20GR...
Страница 12: ...9 A5MSX 2009 Model A5MSX30A A5WMX10 20G Model A5MSX30AR A5WMX10 20GR Application Information...
Страница 48: ...45 A5MSX 2009 Outline and Dimension Indoor Unit Model A5WMX10 15G GR m m n i n o i s n e m i D e t o N...
Страница 49: ...46 A5MSX 2009 Outline and Dimension Indoor Unit Model A5WMX20G GR m m n i n o i s n e m i D e t o N...
Страница 55: ...52 A5MSX 2009 Wiring Diagram Indoor Unit Model A5WMX10 15 20G GR Outdoor Unit Model A5MSX25A AR 70 03 4 088704...
Страница 56: ...53 A5MSX 2009 Wiring Diagram Indoor Unit Model A5WMX10 15 20G GR Outdoor Unit Model A5MSX30A AR 70 03 4 089435...