37
Troubleshooting
A5LCY_(i)
Error
Codes
Error Description
Action
E3
High pressure protection
1. Check installation conditions.
2. Check stop valve.
3. Check HPS connection.
4. Check pressure level by pressure gauge.
5. Wait for 10 minutes then restart the system.
6. Check if H3 is displayed.
E4
Low pressure protection
1. Check stop valve.
2. Check low pressure sensor connection.
3. Check low side pressure and voltage.
4. Check outdoor coil sensor connection.
5. Check sensor resistance value.
6. Check refrigerant level.
E5
Compressor motor lock/overload
1. Check connection on discharge pipe sensor.
2. Check discharge pipe sensor resistance value.
3. Check the EXV.
4. Check the refrigerant line on blockage or shortage.
E6
Compressor lock/start-up error
1. Check with inverter checker.
2. Check the EXV.
E7
Outdoor DC fan motor lock
1. Check the fan motor connection.
2. Check if foreign matters exist around or in the fan.
E8
Ac input over current
1. Measure the input current.
2. Check the main circuit electrolytic capacitor.
3. Check with inverter checker.
4. Check discharge pressure.
5. Check the installation condition.
E9
EXV error
1. Restart the system.
2. Check the EXV connection.
3. Check EXV coil resistance.
4. Check sensors resistance value.
EA
4-way valve error
1. Check 4WV coil connection.
2. Check the continuity of the 4WV coil and harness.
3. Check the 4WV switching output.
4. Check sensor connection.
5. Check sensor resistance value.
6. Check the refrigerant line on blockage or shortage.
F3
Discharge pipe overheat
1. Check the discharge pipe sensor.
2. Check the EXV.
3. Check the refrigerant line on blockage or shortage.
F6
Heat exchanger overheat
1. Check the installation space.
2. Check the outdoor fan.
3. Check the EXV.
4. Check the coil sensor.
H0
Compressor sensor system
abnormality
1. Check the reactor connection.
2. Check the compressor connection.
3. Measure the resistance value between the reactor terminals.
4. Measure the resistance value between the compressor terminals.
H3
High pressure switch error
1. Check pressure sensor connection.
2. Check HPS continuity.
H6
Position sensor abnormality
1. Check for short circuit.
2. Check the electrolytic capacitor voltage.
3. Check compressor harness wire.
4. Check with inverter checker.
Содержание A5CCY-C Series
Страница 1: ...Inverter Y Single Split Series I A5LCY_ i A5LCY 10DR A5LCY 15DR A5LCY 20CR A5LCY 25CR Models...
Страница 2: ......
Страница 25: ...22 A5LCY_ i Wiring Diagram Outdoor Unit Indoor Unit Model A5LCY 20 25CR Model A5WMY 20 25JR...
Страница 27: ...24 A5LCY_ i Wiring Diagram Heat Pump Outdoor Unit Indoor Unit Model A5LCY 20CR Model A5CKY 20CR...
Страница 31: ...28 A5LCY_ i Wiring Diagram Heat Pump Outdoor Unit Indoor Unit Model A5LCY 15DR Model A5CMY 15ER 70034108591...
Страница 57: ...A5LCY_ i Sound Data NC Curve Part Number 000353103G1010 Part Number 000353103G1515 A5CKY 10CR A5CKY 15CR...
Страница 58: ...Sound Data A5LCY_ i Part Number 000353103H2020 Part Number 000353103H2020 A5CKY 20CR A5CKY 20ER...
Страница 59: ...A5LCY_ i Sound Data Part Number 000353103N2525 A5CKY 25ER...
Страница 61: ...A5LCY_ i Sound Data NC Curve Part Number 000353103K1010 Part Number 000353103K1515 A5CCY 10CR A5CCY 15CR...
Страница 62: ...Sound Data A5LCY_ i Part Number 000353103K2020 Part Number 000353103K2525 A5CCY 20CR A5CCY 25CR...
Страница 64: ...A5LCY_ i Sound Data NC Curve Part Number 000353103M1515 Part Number 000353103M2020 A5CMY 15ER A5CMY 20ER...
Страница 65: ...Sound Data A5LCY_ i Part Number 000353103M2525 A5CMY 25ER...