A5LCY_(i)
Troubleshooting
Error
Codes
Error Description
Action
H8
AC current sensor error
1. Restart the system.
2. Check capacitor voltage.
3. Measure the recti
fi
er input voltage.
4. Check compressor harness wire.
5. Check with inverter checker.
H9
Outdoor air thermistor short / open
1. Check the sensor connection.
2. Check the sensor resistance value.
J1
Pressure sensor error
1. Check pressure sensor connection.
2. Check pressure and voltage level.
J3
Compressor discharge pipe
thermistor short / open / misplaced
1. Check the sensor connection.
2. Check the sensor resistance value.
3. Check indoor coil sensor resistance value.
J5
Suction pipe thermistor short / open Same as H9.
J6
Outdoor heat exchanger
Same as H9.
J7
Subcooling heat exchanger
thermistor short / open
Same as H9.
J8
Liquid pipe thermistor short / open
Same as H9.
J9
Gas pipe thermistor abnormality
Same as H9.
LC
Communication Error (control PCB
and inverter PCB)
1. Check fan motor connection.
2. Check if LED blinking normally at outdoor PCB.
L1
Outdoor PCB error
1. Check the range of power supply.
2. Check connection between compressor and PCB.
3. Check fan motor resistance.
4. Check the power supply waveform.
L3
Electrical box temperature rise
1. Restart the system.
2. Check sensor resistance value.
3. Check heat sink temperature and conditions.
4. Check outdoor fan.
5. Check the installation condition.
L4
Heat sink overheat
1. Restart the system.
2. Check the silicon grease condition on heat sink.
3. Check sensor resistance value.
4. Check heat sink temperature and conditions.
5. Check outdoor fan.
6. Check the installation condition.
L5
IPM error / IGBT error
1. Check stop valve.
2. Check with inverter checker.
3. Check the power transistor.
4. Check the supply voltage.
5. Check the compressor phase.
6. Check the discharge pressure.
7. Check the installation condition.
L8
Electrical thermal switch
Contact dealers for assistance.
L9
Stall prevention
1. Check installation conditions.
2. Check stop valve.
3. Check difference between high and low pressure side.
4. Check continuity on the power transistor.
5. Check the output voltage.
P1
Open phase or voltage unbalance
1. Check LED on outdoor PCB.
2. Check open phase of power supply voltage.
3. Check voltage balance between phases.
P4
Heat sink thermistor short / open
Same as H9.
PJ
Capacity setting error
1. Check the connection between capacitor and Outdoor PCB.
Содержание A5CCY-C Series
Страница 1: ...Inverter Y Single Split Series I A5LCY_ i A5LCY 10DR A5LCY 15DR A5LCY 20CR A5LCY 25CR Models...
Страница 2: ......
Страница 25: ...22 A5LCY_ i Wiring Diagram Outdoor Unit Indoor Unit Model A5LCY 20 25CR Model A5WMY 20 25JR...
Страница 27: ...24 A5LCY_ i Wiring Diagram Heat Pump Outdoor Unit Indoor Unit Model A5LCY 20CR Model A5CKY 20CR...
Страница 31: ...28 A5LCY_ i Wiring Diagram Heat Pump Outdoor Unit Indoor Unit Model A5LCY 15DR Model A5CMY 15ER 70034108591...
Страница 57: ...A5LCY_ i Sound Data NC Curve Part Number 000353103G1010 Part Number 000353103G1515 A5CKY 10CR A5CKY 15CR...
Страница 58: ...Sound Data A5LCY_ i Part Number 000353103H2020 Part Number 000353103H2020 A5CKY 20CR A5CKY 20ER...
Страница 59: ...A5LCY_ i Sound Data Part Number 000353103N2525 A5CKY 25ER...
Страница 61: ...A5LCY_ i Sound Data NC Curve Part Number 000353103K1010 Part Number 000353103K1515 A5CCY 10CR A5CCY 15CR...
Страница 62: ...Sound Data A5LCY_ i Part Number 000353103K2020 Part Number 000353103K2525 A5CCY 20CR A5CCY 25CR...
Страница 64: ...A5LCY_ i Sound Data NC Curve Part Number 000353103M1515 Part Number 000353103M2020 A5CMY 15ER A5CMY 20ER...
Страница 65: ...Sound Data A5LCY_ i Part Number 000353103M2525 A5CMY 25ER...