background image

 

 
 

ACS Control-System GmbH | www.acs-controlsystem.de | [email protected] | Eggenfelden | Germany 

   

 

 

 

 

 

   KAK / KLK 
 

page 11 of 16 

 

 

 

Technical data 

 

Materials 

 

Electrode rod: 

Steel 1.4404 (AISI 316L) / 1.4571 (AISI 316Ti) / Hastelloy B4, C22 / Titan 

(medium contact) 

 

 

Electrode isolation: 

KAK 

 

 

 

 

   

 

  PA / ETFE resp. E-CTFE 

(medium contact)

 

KLK 

 

 

 

 

   

 

  ETFE, FDA-listed

 

 

Process connection: 

Steel 1.4404 (AISI 316L) / 1.4571 (AISI 316Ti) 

(medium contact)

 

 

 

Terminal enclosure:   

 

 

 

CrNi-steel + PC / POM + PC / PP + PC / PTFE + PC 

 

Cable gland: 

 

Terminal enclosure CrNi-steel

 

Enclosure CrNi-steel / Gasket CR, NBR

 

Terminal enclosure POM / PP / PTFE

 

Enclosure PA / Gasket CR, NBR

 

 

Device plug M12x1: 

Socket CrNi-steel, insert PUR, contacts gold-plated 

 

Gaskets: 

medium contact:

  

KAK

 

FPM

 

KLK

 

EPDM, FDA listed

 

 

 

Others: FPM, silicone

 

 

Environmental conditions 

 

Environmental temperature: 

– 40°C...+85°C 

 

Process temperature: 

– 40°C...+100°C 

 

Process pressure range: 

– 1 bar ...10 bar 

 

Weight: 

Terminal enclosure steel   

   

 

 

0,5 kg 

 

Terminal enclosure PTFE / POM / PP   

0,2 kg 

 

Electrode rod  diameter 4 mm     

 

 

0,1 kg / 1000 mm 

 

Electrode rod  diameter 8 mm     

 

 

0,4 kg / 1000 mm

 

 

Torque strength: 

 80 Nm 

 

Protection classification: 

IP65 

 

 

DIN EN 60529 

 

EM 

– compatibility: 

Emission 

DIN EN 61326-1    

operation device class B 

 

Immunity  

 

DIN EN 61326-1     

industrial range

 

 
 

Operation 

 

Indication limit value: 

1 resp. 2 LED, yellow 

at version UB / UC with relay output 

 

1 LED, red 

 

 

at version GA with PNP switching output

 

 

Configuration: 

3 jumper  

 

 

at version UB / UC with relay output 

 

1 jumper  

 

 

at version GA with PNP switching output

 

 

Sensitivity adjustment: 

1 trimmer 12-turn   

at version UB / UC with relay output 

 

1 trimmer 20-turn   

at version GA with PNP switching output

 

 
 

Connection terminals 

 

Version UB / UC with relay output

 

Number: 

8 terminals, everlasting screws 

 

Connection cross-section: 

maximum 1x 1,5 mm

2

 rigid / flexible 

 

Version GA with PNP switching output 

Number: 

3 terminals, everlasting screws 

 

Connection cross-section: 

maximum 1x 2,5 mm

2

 rigid / flexible 

Содержание KAK

Страница 1: ...for pumps in pipelines for two position control in plants Wide application range for process temperatures from 40 C to 100 C for process pressures from 1 bar to 10 bar materials for aggressive filling...

Страница 2: ...de Eggenfelden Germany KAK KLK page 2 of 16 Index Application field 3 Function 3 4 5 Safety notes 6 Installation 6 7 Maintenance 7 Repair 7 Electrical connection 8 Operation and display elements 9 Tec...

Страница 3: ...ed by the integrated electronic is than applied either between the electrode rods or between the electrode rods and the metallic wall of the container resp pipe that is connected to the metallic proce...

Страница 4: ...underrun no liquid connection between measuring and reference electrode REF or the power supply fails For both channels CH1 and CH2 the safety function can be set separately This can be carried out b...

Страница 5: ...nnection between electrode CH1 and reference electrode REF or the power supply fails Minimum safety The output signal switches off if the switching level is underrun no liquid connection between elect...

Страница 6: ...uction of the device and to the resulting dangers The sensors may not be used as sole device for prevention of dangerous conditions in machines and plants Using the device in a manner that does not fa...

Страница 7: ...d by that way that in a empty pipe also in the case of liquid residues the electrically conductive liquid connection between electrode and wall resp between the two electrode rods can disconnect Other...

Страница 8: ...circuit Due to this the installation of a fine protection is not necessary Inductive loads at the relay contacts e g auxiliary contactors or magnetic vents may only be used with a free wheeling diode...

Страница 9: ...e connection between measuring and reference electrode Turn adjustment trimmer to the right clockwise till the output switches off LED off Turn adjustment trimmer to the left counterclockwise till the...

Страница 10: ...ry II acc to DIN EN 61010 1 Protection classification II double or reinforced insulation Isolation voltage 1kV auxiliary power PNP switching output to electrode circuit Relay output UB UC Function 1x...

Страница 11: ...re range 1 bar 10 bar Weight Terminal enclosure steel 0 5 kg Terminal enclosure PTFE POM PP 0 2 kg Electrode rod diameter 4 mm 0 1 kg 1000 mm Electrode rod diameter 8 mm 0 4 kg 1000 mm Torque strength...

Страница 12: ...ACS Control System GmbH www acs controlsystem de info acs controlsystem de Eggenfelden Germany KAK KLK page 12 of 16 Dimension drawing KAK KAK _ _1G12_ _ _ _ KAK _ _2G10_ _ _ _ KAK _ _3G15_ _ _ _...

Страница 13: ...ACS Control System GmbH www acs controlsystem de info acs controlsystem de Eggenfelden Germany KAK KLK page 13 of 16 Dimension drawing KLK KLK _ _2G10_ _ _ _ KLK _ _1G12_ _ _ _ KLK _ _3G15_ _ _ _...

Страница 14: ...ACS Control System GmbH www acs controlsystem de info acs controlsystem de Eggenfelden Germany KAK KLK page 14 of 16 Dimension drawing KLK KLK _ _2D40_ _ _ _ KLK _ _1D25_ _ _ _ KLK _ _3D50_ _ _ _...

Страница 15: ...ontrolsystem de Eggenfelden Germany KAK KLK page 15 of 16 BEFC 62 for KLK DN25 BEFB 62 for KLK DN40 BEFA 62 for KLK DN50 acc to DIN 11851 acc to DIN 11851 acc to DIN 11851 SEM12 for KLK G1 2 SEM10 for...

Страница 16: ...value Reference electrode REF process connection Process connection material CrNi steel medium contact G12 Thread ISO 228 1 G 1 rod G10 Thread ISO 228 1 G 1 2 rod G15 Thread ISO 228 1 G 1 3 rod D25 Da...

Отзывы: