HE Series Central Chillers
Chapter 8: 67 of 83
5.
Drain the flushing fluid and connect a fresh water source to the ball valves and
flush the evaporator with clean water for a minimum of 5 minutes.
Evaporator Process Strainer
The evaporator strainer requires periodic cleaning of its screen to insure the proper
flow through the evaporator. To clean the
strainer screen,
1.
Close the evaporator inlet and
outlet butterfly valves on the back
of the unit.
2.
Open the ball valves on the sensor
caps to drain the evaporator.
3.
Remove the clip that holds the top
sensor cap to the evaporator.
4.
Remove the sensor cap off the
evaporator.
5.
Remove the strainer out of the
evaporator.
2
1
Содержание HE Series
Страница 22: ...HE Series Central Chillers 882 03862 00 12 02 2021 22 Fork Lift...
Страница 30: ...HE Series Central Chillers 882 03862 00 12 02 2021 30...
Страница 31: ...HE Series Central Chillers 882 03862 00 12 02 2021 31...
Страница 33: ...HE Series Central Chillers 882 03862 00 12 02 2021 33...
Страница 57: ...HE Series Central Chillers Chapter 6 57 of 83...
Страница 60: ...HE Series Central Chillers Chapter 7 60 of 83 Updating a C pCO s Program Using a USB Stick...
Страница 61: ...HE Series Central Chillers Chapter 7 61 of 83 Saving or Restoring Settings to a USB Stick...
Страница 62: ...HE Series Central Chillers Chapter 7 62 of 83 Updating an Exor HMI Program using a USB Stick...
Страница 63: ...HE Series Central Chillers Chapter 7 63 of 83 Downloading Alarm History to a USB Stick...
Страница 64: ...HE Series Central Chillers Chapter 7 64 of 83 Downloading Chiller Logs to a USB Stick...
Страница 65: ...HE Series Central Chillers Chapter 7 65 of 83 Changing the Exor IP Address...
Страница 75: ...HE Series Central Chillers Chapter 10 75 of 83 10 2 Piping Schematic for Remote Cooled Chiller...
Страница 76: ...HE Series Central Chillers Chapter 10 76 of 83...