Step 2
> Pull the sealing over the measuring stick.
> Push the screw joint over the measuring stick.
Sealing
Measuring stick
Screw joint
Step 3
> Push the sealing and the screw joint through the
bore up to the dead stop.
> Push the counter nut over the measuring stick, turn
it to the thread neck of screw joint and firmly tighten
up the connection.
Sealing
Measuring stick
Counter nut
Screw joint
Step 4
Table
A
Grease separator
Nominal size
Groove
Shape
NS
no.
oval
1 - 4
1
oval
5 - 10
2
round
2 - 4
2
round
7 - 10
2
round
15 + 20
3
In the case of separators with high-pressure
(HP) internal cleaning (fig
A), sensors (1) point
towards HP Orbital cleaning head (2) and with
separators without HP internal cleaning (fig. B),
towards a maintenance opening (2) - Reason:
effective sensor cleaning
.
> Depending on grease separator type, adjust the
measuring stick by setting relevant groove (see table
A) to zero water level height (= static water level,
water reaches up to pipe bottom of outlet or overflow
edge).
Zero water level
Groove 3
Groove 2
Groove 1
1
1
1
3
2
Step 5
> Reinsert the half-shell into the screw joint.
> Retighten the bolts of the gripper clamp.
Half-shell
Bolts
Gripper clamp
Step 6
> Click the evaluation device or the gripper clamps
again to the measuring stick.
Evaluation device
Gripper clamps
Measuring stick
Assembly
Fig.
A
Fig
B
NOTICE