Version : 17.0
I0000756
Page 5 of 5
Product Specifications
Supply Voltage
4-20mA Output: 250 Ohm Load 16-36 VDC
4-20mA Output: 500 Ohm Load 20-36 VDC
0-5 VDC Output: 16-36 VDC / 24VAC (+/-10%)
0-10 VDC Output: 16-36 VDC / 24VAC (+/-10%)
Supply Current
24mA minimum
Output
2-wire, 4 to 20mA DC Current (500 Ohm Load Max.)
or 3-wire, 0-5 or 0-10VDC (5K Ohm Min.)
Sensor Accuracy
1
+/- 1.5% FSO for
0-
10PSI and 0-30PSI ranges
+/- 1% FSO for all other ranges
Output Update Rate
1 Second Interval
Response Time (0-100%)
8 Seconds
Operating Temperature Range
Sensor: -40 to 230°F (-40 to 110°C)
Enclosure: 5 to 176°F(-15 to 80°C)
Sensor Cable: 0 to +75°C (32 to 167°F)
Compensated Temperature Range
32 to 140°F (0 to 60°C)
Humidity
10 to 90% RH, non-condensing
Thermal Effects
2
+/-2%FSO (0 to 60°C)
Proof Pressure
3 x F.S. for WPR2 Series
Burst Pressure
1500 PSI
Media
Gases, refrigerants, ammonia and water-based fluids *
Features
Depluggable terminal blocks
Push button/Remote Auto Zero
DIP switch selectable ranges and output modes
Out-Of-Range Diagnostic Output
Enclosure
IP66 Rated (Mounting Flanges & Screws Included)
Approvals
RoHS
Display
Optional LCD display
Note 1: Accuracy includes linearity,
hysteresis and repeatability.
Note 2: Shift is relative to 77°F
(25°C).
*Please contact ACI for petrol chemical compatible versions.
Table 2: Product Specifications
Warranty Specification
The ACI WPR2 Series is covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of
ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s web site: