Installation and Operation Instructions 

                                                           

WPR2 Series (Max. Line Pressure < 300 PSI) 

                                                                        Wet to Wet Differential Pressure                      

 

 

                                                                                                                                          Version : 17.0 

                                                                                                                                                                        I0000756 

                                          

          Page 1 of 5                                   

  

                                                                                                                                                       

 

 

 

 

 

Figure 1: WPR2 Dimensions and Hardware 

Precautions 

 

REMOVE

 

POWER

 

BEFORE

 

WIRING.

 

NEVER

 

CONNECT

 

OR

 

DISCONNECT

 

WIRING

 

WITH

 

THE

 

POWER

 

APPLIED.

 

DO

 

NOT

 

ALLOW

 

LIVE

 

WIRES

 

TO

 

TOUCH

 

THE

 

CIRCUIT

 

BOARD. 

 

AN

 

ISOLATION

 

TRANSFORMER

 

IS

 

RECOMMENDED

 

WHEN

 

POWERING

 

THE

 

DEVICE

 

WITH

 

24VAC. 

 

DO

 

NOT

 

RUN

 

THE

 

WIRING

 

IN

 

ANY

 

CONDUIT

 

WITH

 

LINE

 

VOLTAGE. 

 

FAILURE

 

TO

 

WIRE

 

DEVICES

 

WITH

 

THE

 

CORRECT

 

POLARITY

 

WHEN

 

USING

 

A

 

SHARED

 

TRANSFORMER

 

MAY

 

RESULT

 

IN

 

DAMAGE

 

TO

 

ANY

 

DEVICE

 

POWERED

 

BY

 

THE

 

SHARED

 

TRANSFORMER. 

 

DO

 

NOT

 

SWITCH

 

PRESSURE

 

RANGE

 

AND

 

OUTPUT

 

MODE

 

WHEN

 

POWER

 

IS

 

ON.

 

MAKE

 

SURE

 

TO

 

POWER

 

OFF

 

THE

 

UNIT

 

FIRST,

 

THEN

 

MOVE

 

JUMPERS

 

TO

 

THE

 

RIGHT

 

POSITIONS

 

AND

 

THEN

 

POWER

 

ON

 

THE

 

TRANSMITTER. 

 

DO

 

NOT

 

APPLY

 

ANY

 

EXTERNAL

 

VOLTAGE

 

TO

 

ZERO

 

TERMINALS. 

 

DO

 

NOT

 

REPLACE

 

PRESSURE

 

SENSORS

 

WITH

 

ANY

 

OTHER

 

SENSORS.

 

 DO

 

NOT

 

INTERCHANGE

 

THE

 

HIGH

 

AND

 

LOW

 

SENSORS.

 

THE

 

HIGH

 

AND

 

LOW

 

SENSORS

 

ARE

 

SPECIFICALLY

 

CALIBRATED

 

TO

 

THE

 

WPR2

 

UNIT.

 

 

ANY

 

CHANGES

 

TO

 

THE

 

SENSORS

 

WILL

 

VOID

 

THE

 

PRODUCT

 

WARRANTY

 

 

2.60"

5.47"

3.00"

4.47"

5.28"

Ø0.200"

Содержание WPR2 Series

Страница 1: ... LINE VOLTAGE FAILURE TO WIRE DEVICES WITH THE CORRECT POLARITY WHEN USING A SHARED TRANSFORMER MAY RESULT IN DAMAGE TO ANY DEVICE POWERED BY THE SHARED TRANSFORMER DO NOT SWITCH PRESSURE RANGE AND OUTPUT MODE WHEN POWER IS ON MAKE SURE TO POWER OFF THE UNIT FIRST THEN MOVE JUMPERS TO THE RIGHT POSITIONS AND THEN POWER ON THE TRANSMITTER DO NOT APPLY ANY EXTERNAL VOLTAGE TO ZERO TERMINALS DO NOT R...

Страница 2: ...warm up time before adjustment to the ZERO The Auto Zero adjustment should only be performed with NO pressure applied to both sensors Shut off your main pressure valve and open a shutoff valve with hose drain to equalize the pressure in the line to your atmosphere Remove the sensors from the system to remove pressure from each sensor to achieve equal pressure Push ZERO button or SHORT ZERO PIN for...

Страница 3: ...N POWER IS ON o MAKE SURE POWER TO THE UNIT IS OFF FAILURE TO DO SO WILL NOT ALLOW ANY NEW SWITCH SETTINGS TO TAKE PLACE CHOOSE DIFFERENTIAL RANGE BASED ON THE EXPECTED DIFFERENTIAL PRESSURE IN YOUR APPLICATION o MOVE SWITCHES TO THE CORRECT POSITIONS AND THEN POWER ON THE TRANSMITTER MAXIMUM LINE PRESSURE ACI Part No Maximum Line Pressure WPR2 30 30 PSI WPR2 100 100 PSI The WPR2 can operate in ei...

Страница 4: ...he input pressure is than Max Line Pressure Check pressure input with a gauge or other test instrument The WPR2 300 Series is available for pressures over 100 PSI 1 Verify the HIGH Sensor Voltage is between 0 5 VDC 0 PSI and 4 5 VDC Max Line Pressure When measuring from the HIGH Sensor terminal Block GND to OUT If out of range call ACI for Technical support 2 Verify the LOW Sensor Voltage is betwe...

Страница 5: ... 32 to 140 F 0 to 60 C Humidity 10 to 90 RH non condensing Thermal Effects2 2 FSO 0 to 60 C Proof Pressure 3 x F S for WPR2 Series Burst Pressure 1500 PSI Media Gases refrigerants ammonia and water based fluids Features Depluggable terminal blocks Push button Remote Auto Zero DIP switch selectable ranges and output modes Out Of Range Diagnostic Output Enclosure IP66 Rated Mounting Flanges Screws I...