                                                                                                                                          Version : 17.0 

                                                                                                                                                                        I0000756 

                                          

          Page 4 of 5                                   

  

                                                                                                                                                       

 

Note:   In Bidirectional mode, a value of 0 PSID will have an output equal to 50% of the full output range. 

ACI/Part No. 

SW7 Position 5: 1 

SW7 Position 5: 2 

 

Position 4: A 

Position 4: B 

Position 4: A 

Position 4: B 

A/WPR2-30 

±

30 PSI 

±

15 PSI 

±

7.5 PSI 

±

3 PSI 

A/WPR2-100 

±

100 PSI

±

50 PSI

±

25 PSI

±

10 PSI

1

3

4

2

5

ON

 

Figure 1

 

ENGINEERING UNITS ADJUSTMENT

  

This option is ONLY for units with LCD display. Switch DIP switch SW7 position 3 to select PSI or BAR. 

Advanced Features 

For units with LCD display: 

 

ERROR

” icon will be on when differential pressure is out of range. 

 

OVR

” icon will be on when gage pressure is out of range on either the high or low port. 

 

Trouble Shooting 

Problem

 

Trouble Shooting Steps

 

“ERROR” icon on Display will be on 
when differential pressure is out of range. 
The differential pressure could be lower or 
higher than the selected range. 
 
“OVR” icon on Display will be on when 
the input pressure is > than Max Line 
Pressure. Check pressure input with a 
gauge or other test instrument.  The 
WPR2-300 Series is available for 
pressures over 100 PSI. 

1.

 

Verify the HIGH Sensor Voltage is between 
 0.5 VDC (0 PSI) and 4.5 VDC (Max. Line Pressure) 
 When measuring from the HIGH Sensor terminal 
  Block “GND” to “OUT”. If out of range call ACI for   
  Technical support. 

2.

 

Verify the LOW Sensor Voltage is between 
0.5 VDC (0 PSI) and 4.5 VDC (Max. Line Pressure) 
 When measuring from the LOW Sensor terminal 
  Block “GND” to “OUT”. If out of range call ACI for 
  Technical support. 

3.

 

Verify in Uni-Directional Mode that the HIGH Sensor 
Voltage is ≥ the LOW Sensor Voltage. If voltage is 
anything different call ACI for Technical support. 

Output reading @ 4mA or 0 VDC 
all the time 
 

1.

 

Verify proper Supply Voltage at the transducer meets the 
Product Specifications. 

2.

 

Verify 5 VDC Reference voltage across “VIN” to “GND” 
terminals for both the HIGH & LOW Sensor  
terminal blocks.  If voltage is anything different than 
5VDC call ACI for Technical support. 

Erroneous Readings 

1.

 

Bleed Air from System. 

2.

 

Repeat the Auto Zero calibration on page 2. 

Содержание WPR2 Series

Страница 1: ... LINE VOLTAGE FAILURE TO WIRE DEVICES WITH THE CORRECT POLARITY WHEN USING A SHARED TRANSFORMER MAY RESULT IN DAMAGE TO ANY DEVICE POWERED BY THE SHARED TRANSFORMER DO NOT SWITCH PRESSURE RANGE AND OUTPUT MODE WHEN POWER IS ON MAKE SURE TO POWER OFF THE UNIT FIRST THEN MOVE JUMPERS TO THE RIGHT POSITIONS AND THEN POWER ON THE TRANSMITTER DO NOT APPLY ANY EXTERNAL VOLTAGE TO ZERO TERMINALS DO NOT R...

Страница 2: ...warm up time before adjustment to the ZERO The Auto Zero adjustment should only be performed with NO pressure applied to both sensors Shut off your main pressure valve and open a shutoff valve with hose drain to equalize the pressure in the line to your atmosphere Remove the sensors from the system to remove pressure from each sensor to achieve equal pressure Push ZERO button or SHORT ZERO PIN for...

Страница 3: ...N POWER IS ON o MAKE SURE POWER TO THE UNIT IS OFF FAILURE TO DO SO WILL NOT ALLOW ANY NEW SWITCH SETTINGS TO TAKE PLACE CHOOSE DIFFERENTIAL RANGE BASED ON THE EXPECTED DIFFERENTIAL PRESSURE IN YOUR APPLICATION o MOVE SWITCHES TO THE CORRECT POSITIONS AND THEN POWER ON THE TRANSMITTER MAXIMUM LINE PRESSURE ACI Part No Maximum Line Pressure WPR2 30 30 PSI WPR2 100 100 PSI The WPR2 can operate in ei...

Страница 4: ...he input pressure is than Max Line Pressure Check pressure input with a gauge or other test instrument The WPR2 300 Series is available for pressures over 100 PSI 1 Verify the HIGH Sensor Voltage is between 0 5 VDC 0 PSI and 4 5 VDC Max Line Pressure When measuring from the HIGH Sensor terminal Block GND to OUT If out of range call ACI for Technical support 2 Verify the LOW Sensor Voltage is betwe...

Страница 5: ... 32 to 140 F 0 to 60 C Humidity 10 to 90 RH non condensing Thermal Effects2 2 FSO 0 to 60 C Proof Pressure 3 x F S for WPR2 Series Burst Pressure 1500 PSI Media Gases refrigerants ammonia and water based fluids Features Depluggable terminal blocks Push button Remote Auto Zero DIP switch selectable ranges and output modes Out Of Range Diagnostic Output Enclosure IP66 Rated Mounting Flanges Screws I...