aci DUCT HUMIDITY SERIES Скачать руководство пользователя страница 7

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 7

Version 6.0

I0000546

TROUBLESHOOTING

TEMPERATURE (Optional) PROBLEM

Sensor reading is incorrect

Sensor reads infinity/very high resistance
Sensor reads low resistance
Erratic readings

SOLUTION(S)

Verify sensor wiring to controller is not damaged and has continuity 

Verify sensor or wires are not shorted together

Verify controller is setup for correct sensor curve

Disconnect sensor wires, and take a resistance (ohm) reading with a 

multimeter 

Compare the resistance reading to the Temperature Vs Resistance 

Curves online: 

http://www.workaci.com/content/thermistor-curves-0 

Verify proper mounting location to confirm no external factors

Sensor or wires are open

Sensor or wires are shorted together

Bad wire connections

HUMIDITY READING PROBLEM

No Reading

Erratic readings

Inaccurate readings

SOLUTION(S)

Check that you have the correct supply voltage at the power terminal blocks.

Check that wiring configurations and all DIP switch settings are as in 

FIGURE 5

 and 

7

.

Verify that the terminal screws are all connected tightly and that all 

of the wires are firmly in place.

Verify that all of the wires are terminated properly.

Make sure that there is no condensation on the board.

Check that the input power is clean.  In areas of high RF interference 

or noise, shielded cable may be necessary to stabilize signal.

Verify proper mounting location to confirm no external factors (see 

mounting locations above).

Check the output (voltage or current) against a highly accurate 

recently calibrated secondary reference.  Measue RH at the location of 
the sensor using the secondary reference, then calculate the RH 
percentage using the 

RH CONVERSION FORMULAS 

(p. 5).  Compare 

the calculated output to reference. 

If the sensor is brand new, leave the sensor powered for at least 30 

minutes to stabilize. 

If you suspect that the transmitter is not reading within the specified 

tolerance, please contact ACI for further assistance.

Содержание DUCT HUMIDITY SERIES

Страница 1: ...ns can cause sensing errors An example is downstream from a heating or cooling coil Duct probe should be placed 3 to 4 duct segments down from any bend or obstructions and away from 90 bends Mount the sensor on the top or sides of duct work mountingonthebottomrisksdamageduetomoisture MOUNTING INSTRUCTIONS The Euro enclosure EH requires a 0 875 22 23 mm hole in the duct and the Nema 4X enclosure 4X...

Страница 2: ...ransorbordiode connectstothepositiveside of the power supply Without these snubbers coils produce very large voltage spikes when de energizing that can cause malfunction or destruction of electronic circuits RELATIVE HUMIDITY WIRING INSTRUCTIONS Open the cover of the enclosure ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all transmitters Twisted pairmaybeusedfor2 wirecurren...

Страница 3: ...TROLLER ANALOG INPUT WIRING FROM CONTROLLER ANALOG INPUT FIGURE 6 TEMPERATURE WIRING 3 WIRE RTD WIRING 2 WIRE THERMISTOR or RTD WIRING FIGURE 5 OUTPUT SIGNALS OPTIONAL TEMP SENSOR CONNECT TO THE 2 or 3 22 AWG FLYING LEADS OPTIONAL TEMP SENSOR 4 20mA SUPPLY GROUND SIGNAL COMMON DC SUPPLY VOLTAGE 4 20 mA OUTPUT TB1 COM VIN VOUT OPTIONAL TEMP SENSOR VOLTAGE OUTPUT SIGNAL 3 WIRE CURRENT OUTPUT SIGNAL ...

Страница 4: ... 4 are ON When all calibration is completed remember to place the switches back into the positions that correspond to the output needed as shown in FIGURE 7 HUMIDITY REVERSE ACTING OUTPUT The output is direct acting and can be changed to reverse acting mode The output range stays the same but the corresponding RH value is opposite Example Direct Acting DA 0 10 V output mode 0 V 0 RH and 10 V 100 R...

Страница 5: ... The decrease goes into effect each time switch 6 is set to ON Reset RH Output This will reset the RH output back to the original calibration Switch 4 must be set to ON first After switch 4 is on toggle switches 5 and 6 ON then OFF After 5 and 6 are OFF slide switch 4 OFF When all calibration is completed remember to place the switches back into the positions that correspond to the output needed a...

Страница 6: ... C 0 36 F A 1K 1 KΩ nominal 60 C 140 F 0 27 C 0 49 F 21 1 C 70 F 0 17 C 0 34 F 54 4 C 130 F 0 56 C 1 00 F SENSOR SPECIFIC RH Supply Voltage Reverse Polarity Protected RH Supply Current VA RH Output Load Resistance RH Output Signal RH Accuracy 77 F 25 C RH Measurement Range Operating RH Range Operating Temperature Range Storage Temperature Range RH Stability Repeatability Sensitivity RH Response Ti...

Страница 7: ...dings SOLUTION S Checkthatyouhavethecorrectsupplyvoltageatthepowerterminalblocks Check that wiring configurations and all DIP switch settings are as in FIGURE 5 and 7 Verify that the terminal screws are all connected tightly and that all of the wires are firmly in place Verify that all of the wires are terminated properly Make sure that there is no condensation on the board Check that the input po...

Отзывы: