FIGURE 3: 

MOUNTING DIMENSIONS

FIGURE 2: 

TEMPERATURE WIRING

WIRING INSTRUCTIONS

PRECAUTIONS
• Do not run the temperature sensor wiring in any 

conduit with line voltage (24/120/230 VAC) if 
utilizing resistance temperature signal.

• Remove power before wiring. Never connect or 

disconnect wiring with power applied.

• When using a shielded cable, ground the shield only 

at the controller end. Grounding both ends can 
cause a ground loop.

• It is recommended you use an isolated UL-listed 

class 2 transformer when powering the unit with 24 
VAC. Failure to wire the devices with the correct 
polarity when sharing transformers may result in damage to any device powered by the shared transformer.

• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or other inductors, 

each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI Part: 142583), or diode placed 
across the coil or inductor. The cathode, or banded side of the DC Transorb or diode, connects to the positive side 
of the power supply. Without these snubbers, coils produce very large voltage spikes when de-energizing that 
can cause malfunction or destruction of electronic circuits.

RELATIVE HUMIDITY WIRING INSTRUCTIONS

Open the cover of the enclosure. ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all transmitters. Twisted 
pair may be used for 2-wire current output transmitters or 3-wire for voltage output. Refer to 

FIGURE 5 

(p. 3) for wiring diagrams.

TEMPERATURE WIRING INSTRUCTIONS

ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all temperature sensors. ACI recommends a separate 
cable be pulled for Temperature signal only. Temperature Signal wiring must be run separate from low and high voltage 
wires (24/120/230VAC). All ACI thermistors and RTD temperature sensors are both non-polarity and non-position sensitive. 
All thermistor type units are supplied with (2) flying lead wires, and all RTD’s are supplied with (2) or (3) flying lead wires – 
see 

FIGURE 6 

(p. 3).  The number of wires needed depends on the application. Connect thermistor/RTD wire leads to control-

ler analog input wires using wire nuts, terminal blocks, or crimp style connectors. All wiring must comply with local and 
National Electric Codes. After wiring, attach the cover to the enclosure.

TEMPERATURE

WIRE LEADS

TEMPERATURE

WIRE LEADS

Содержание DUCT HUMIDITY SERIES

Страница 1: ...ns can cause sensing errors An example is downstream from a heating or cooling coil Duct probe should be placed 3 to 4 duct segments down from any bend or obstructions and away from 90 bends Mount the sensor on the top or sides of duct work mountingonthebottomrisksdamageduetomoisture MOUNTING INSTRUCTIONS The Euro enclosure EH requires a 0 875 22 23 mm hole in the duct and the Nema 4X enclosure 4X...

Страница 2: ...ransorbordiode connectstothepositiveside of the power supply Without these snubbers coils produce very large voltage spikes when de energizing that can cause malfunction or destruction of electronic circuits RELATIVE HUMIDITY WIRING INSTRUCTIONS Open the cover of the enclosure ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all transmitters Twisted pairmaybeusedfor2 wirecurren...

Страница 3: ...TROLLER ANALOG INPUT WIRING FROM CONTROLLER ANALOG INPUT FIGURE 6 TEMPERATURE WIRING 3 WIRE RTD WIRING 2 WIRE THERMISTOR or RTD WIRING FIGURE 5 OUTPUT SIGNALS OPTIONAL TEMP SENSOR CONNECT TO THE 2 or 3 22 AWG FLYING LEADS OPTIONAL TEMP SENSOR 4 20mA SUPPLY GROUND SIGNAL COMMON DC SUPPLY VOLTAGE 4 20 mA OUTPUT TB1 COM VIN VOUT OPTIONAL TEMP SENSOR VOLTAGE OUTPUT SIGNAL 3 WIRE CURRENT OUTPUT SIGNAL ...

Страница 4: ... 4 are ON When all calibration is completed remember to place the switches back into the positions that correspond to the output needed as shown in FIGURE 7 HUMIDITY REVERSE ACTING OUTPUT The output is direct acting and can be changed to reverse acting mode The output range stays the same but the corresponding RH value is opposite Example Direct Acting DA 0 10 V output mode 0 V 0 RH and 10 V 100 R...

Страница 5: ... The decrease goes into effect each time switch 6 is set to ON Reset RH Output This will reset the RH output back to the original calibration Switch 4 must be set to ON first After switch 4 is on toggle switches 5 and 6 ON then OFF After 5 and 6 are OFF slide switch 4 OFF When all calibration is completed remember to place the switches back into the positions that correspond to the output needed a...

Страница 6: ... C 0 36 F A 1K 1 KΩ nominal 60 C 140 F 0 27 C 0 49 F 21 1 C 70 F 0 17 C 0 34 F 54 4 C 130 F 0 56 C 1 00 F SENSOR SPECIFIC RH Supply Voltage Reverse Polarity Protected RH Supply Current VA RH Output Load Resistance RH Output Signal RH Accuracy 77 F 25 C RH Measurement Range Operating RH Range Operating Temperature Range Storage Temperature Range RH Stability Repeatability Sensitivity RH Response Ti...

Страница 7: ...dings SOLUTION S Checkthatyouhavethecorrectsupplyvoltageatthepowerterminalblocks Check that wiring configurations and all DIP switch settings are as in FIGURE 5 and 7 Verify that the terminal screws are all connected tightly and that all of the wires are firmly in place Verify that all of the wires are terminated properly Make sure that there is no condensation on the board Check that the input po...

Отзывы: