PRODUCT SPECIFICATIONS

Version 6.0

I0000546

4-20 mA:

 250 Ω Load: 15 - 40 VDC / 18 - 28 VAC  |  

500 

Ω 

Load:

 18 - 40 VDC / 18 - 28 VAC

0-5 VDC:

 12 - 40 VDC / 18 - 28 VAC  |  

0-10 VDC:

 18 - 40 VDC / 18 - 28 VAC

Voltage Output:

 8 mA max (0.32 VA)  |  

Current Output:

 24 mA max (0.83 VA)

4-20 mA: 

700 Ω maximum  |  

0-5 VDC or 0-10 VDC:

 4K Ω Minimum

2-wire:

 4 - 20 mA (Default)  |  

3-wire:

 0-5 or 0-10 VDC and 4 - 20 mA (Field Selectable)

+/- 1% over 20% RH Range between 20 to 90%  |  +/- 2%, 3%, or 5% from 10 to 95%
0-100%
0 to 95% RH, non-condensing (Conformally Coated PCB’s)
-40 to 140 °F (-40 to 60 °C)
-40 to 149 °F (-40 to 65 °C)
Less than 2% drift / 5 years | 0.5% RH | 0.1% RH
20 Seconds Typical
Capacitive with Hydrophobic Filter
30 Minutes (Recommended time before doing accuracy verification)
Screw Terminal Blocks (Polarity Sensitive)  |  16 (1.31 mm²) to 26 AWG (0.129 mm²)
4.43 to 5.31 lb-in (0.5 to 0.6 Nm)

“-4X” Enclosure: 

Polystyrene Plastic, UL94-V2, NEMA 4X (IP 66)

“-EH” Enclosure:

 ABS Plastic with UV Protectant, UL94-VO

“-EH” Enclosure:

 304 Series Stainless Steel  |  304 Series Stainless Steel

“-4X” Enclosure:

 Schedule 40 PVC (White)  |  Slotted PVC without filter

A/CSI: 

10 KΩ nominal (Green/Yellow)

A/10KS: 

10 KΩ nominal (White/Blue)

A/10K-E1:

 10 KΩ nominal (Gray/Orange)

A/20K:

 20 KΩ nominal (Brown/Blue)

A/100KS: 

100 KΩ nominal (Black/Yellow)

A/10K-E1 Series:

 +/- 0.3 °C (+/- 0.54 °F)

All Else:

 +/- 0.2 °C (+/- 0.36 °F) 

A/1K:

 1 KΩ nominal

@ 60 °C (140 °F):  

+/- 0.27 °C  (+/- 0.49 °F)

@ 21.1 °C (70 °F):

 +/- 0.17 °C (+/- 0.34 °F)

@ 54.4 °C (130 °F):

 +/- 0.56 °C  (+/- 1. 00°F)

SENSOR SPECIFIC

RH Supply Voltage: 
(Reverse Polarity Protected)
RH Supply Current (VA): 
RH Output Load Resistance: 
RH Output Signal: 

 

RH Accuracy @ 77°F (25°C): 
RH Measurement Range:
Operating RH Range: 
Operating Temperature Range:
Storage Temperature Range:
RH Stability | Repeatability | Sensitivity:
RH Response Time (T63):
RH Sensor Type:
RH Transmitter Stabilization Time:
RH Connections | Wire Size:
RH Terminal Block Torque Rating:
Enclosure Specifications (Flammability, 
Temperature, NEMA/IP Rating): 
Sensing Tube Material | Filter Material:
  

SENSOR NON-SPECIFIC

Lead Wire Length
Insulation Rating

THERMISTOR 

Sensor Output @ 25 °C (77 °F):

(Lead Wire Colors)

Accuracy @ 0-70 °C (32 - 158 °F):

PLATINUM

Sensor Output @ 0 °C (32 °F):
Accuracy:

NICKEL 

Sensor Output @ 21.1 °C (70 °F):
Accuracy:

BALCO 

Sensor Output @ 21.1 °C (70 °F):
Accuracy:

14” (35.6 cm) | 22 AWG (0.65 mm)
Etched Teflon (PTFE) Colored Leads | Mil Spec 1678/4 Type E

A/1.8K: 

1.8 KΩ nominal (Red/Yellow) 

A/3K:

 3 KΩ nominal (White/Brown)

A/AN (Type III):

 10 KΩ nominal (White/White)

A/AN-BC: 

5.238 KΩ nominal (White/Yellow)

A/CP (Type II):

 10 KΩ nominal (White/Green)

A/1.8K Series:

 +/- 0.5 °C @ 25 °C (77 °F)

 

 and (+/-1.0 °C) (+/-1.8 °F) 

A/100: 

100 Ω nominal 

+/- 0.06% Class A (Tolerance Formula: +/- °C = (0.15 °C + (0.002 * |t|))
 

where |t| is the absolute value of Temperature above or below 0 °C in °C)

@ -40 °C (-40 °F):

  +/- 0.23ºC (+/- 0.414ºF)

@ 0 °C (32 °F):

  +/- 0.15 °C (+/- 0.27 °F)

1 KΩ nominal (Red/Red)

@ -40 °C (-40 °F):

 +/- 1.52 °C (+/- 2.73 °F)

@ 0 °C (32 °F): 

+/- 0.4 °C (+/- 0.72 °F)

1 KΩ nominal (Orange/Yellow)

@ 21.1 °C (70 °F): 

+/- 1%

REL

A

TIVE HUMIDITY SPECIFIC

A

TIONS

TEMPER

A

TURE SENSOR SPECIFIC

A

TIONS (

OPTIONAL)

Содержание DUCT HUMIDITY SERIES

Страница 1: ...ns can cause sensing errors An example is downstream from a heating or cooling coil Duct probe should be placed 3 to 4 duct segments down from any bend or obstructions and away from 90 bends Mount the sensor on the top or sides of duct work mountingonthebottomrisksdamageduetomoisture MOUNTING INSTRUCTIONS The Euro enclosure EH requires a 0 875 22 23 mm hole in the duct and the Nema 4X enclosure 4X...

Страница 2: ...ransorbordiode connectstothepositiveside of the power supply Without these snubbers coils produce very large voltage spikes when de energizing that can cause malfunction or destruction of electronic circuits RELATIVE HUMIDITY WIRING INSTRUCTIONS Open the cover of the enclosure ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all transmitters Twisted pairmaybeusedfor2 wirecurren...

Страница 3: ...TROLLER ANALOG INPUT WIRING FROM CONTROLLER ANALOG INPUT FIGURE 6 TEMPERATURE WIRING 3 WIRE RTD WIRING 2 WIRE THERMISTOR or RTD WIRING FIGURE 5 OUTPUT SIGNALS OPTIONAL TEMP SENSOR CONNECT TO THE 2 or 3 22 AWG FLYING LEADS OPTIONAL TEMP SENSOR 4 20mA SUPPLY GROUND SIGNAL COMMON DC SUPPLY VOLTAGE 4 20 mA OUTPUT TB1 COM VIN VOUT OPTIONAL TEMP SENSOR VOLTAGE OUTPUT SIGNAL 3 WIRE CURRENT OUTPUT SIGNAL ...

Страница 4: ... 4 are ON When all calibration is completed remember to place the switches back into the positions that correspond to the output needed as shown in FIGURE 7 HUMIDITY REVERSE ACTING OUTPUT The output is direct acting and can be changed to reverse acting mode The output range stays the same but the corresponding RH value is opposite Example Direct Acting DA 0 10 V output mode 0 V 0 RH and 10 V 100 R...

Страница 5: ... The decrease goes into effect each time switch 6 is set to ON Reset RH Output This will reset the RH output back to the original calibration Switch 4 must be set to ON first After switch 4 is on toggle switches 5 and 6 ON then OFF After 5 and 6 are OFF slide switch 4 OFF When all calibration is completed remember to place the switches back into the positions that correspond to the output needed a...

Страница 6: ... C 0 36 F A 1K 1 KΩ nominal 60 C 140 F 0 27 C 0 49 F 21 1 C 70 F 0 17 C 0 34 F 54 4 C 130 F 0 56 C 1 00 F SENSOR SPECIFIC RH Supply Voltage Reverse Polarity Protected RH Supply Current VA RH Output Load Resistance RH Output Signal RH Accuracy 77 F 25 C RH Measurement Range Operating RH Range Operating Temperature Range Storage Temperature Range RH Stability Repeatability Sensitivity RH Response Ti...

Страница 7: ...dings SOLUTION S Checkthatyouhavethecorrectsupplyvoltageatthepowerterminalblocks Check that wiring configurations and all DIP switch settings are as in FIGURE 5 and 7 Verify that the terminal screws are all connected tightly and that all of the wires are firmly in place Verify that all of the wires are terminated properly Make sure that there is no condensation on the board Check that the input po...