Page 5

WARRANTY

The ACI Duct Series RH sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S 
SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.

W.E.E.E. DIRECTIVE 

At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not 
dispose of with household waste. Do not burn.

Version 6.0

I0000546

RH CALIBRATION INSTRUCTIONS 

(Continued)

Increment RH Output 

This will shift the RH output linearly up in 0.5% steps. Switch 4 must be set to ON first. After switch 4 is on, each time switch 
5 is set ON the RH output will increase by 0.5%. The increase goes into effect each time switch 5 is set to ON. 

Decrement RH Output 

This will shift the RH output linearly down in 0.5% steps. Switch 4 must be set to ON first. After switch 4 is on, each time 
switch 6 is set ON the RH output will decrease by 0.5%. The decrease goes into effect each time switch 6 is set to ON. 

Reset RH Output 

This will reset the RH output back to the original calibration. Switch 4 must be set to ON first. After switch 4 is on, toggle 
switches 5 and 6 ON then OFF. After 5 and 6 are OFF, slide switch 4 OFF.

When all calibration is completed, remember to place the switches back into the positions that correspond to the output 
needed as shown in 

FIGURE 7

.

FIGURE 8: 

TEST SELECTION SWITCHES

TEST INSTRUCTIONS

Test mode will make the transmitter output a fixed 0%, 
50%, or 100% value. The sensor will not affect the 
transmitter output. This is used for troubleshooting or 
testing only. 

Switches 1, 2, and 3 are used for test mode. The output 
will be a fixed 0%, 50%, or 100% signal that corresponds 
to the output selected with switches 6, 7, and 8. Refer to 

FIGURE 8 

for switch settings.

 

ON

2

6

8

1

OFF

50% RH Output

100% RH Output

4

3

OFF

5

ON

7

ON

2

3

7

8

ON

1

4

5

6

OFF

ON

4

8

0% RH Output

1

ON

2

3

5

6

7

Figure #5

Formula:
Example:

RH CONVERSION FORMULAS

4-20 mA

([mA signal] -4) / 0.16 = percent RH
12 mA output signal
(12 - 4) / 0.16 = 50% RH

0-5 VDC

[VDC signal] / 0.05 = percent RH
1.25 vdc output signal
1.25 / 0.05 = 25% RH

0-10 VDC

[VDC signal] / 0.10 = percent RH
7.50 vdc output signal
7.50 / 0.10 = 75% RH

Содержание DUCT HUMIDITY SERIES

Страница 1: ...ns can cause sensing errors An example is downstream from a heating or cooling coil Duct probe should be placed 3 to 4 duct segments down from any bend or obstructions and away from 90 bends Mount the sensor on the top or sides of duct work mountingonthebottomrisksdamageduetomoisture MOUNTING INSTRUCTIONS The Euro enclosure EH requires a 0 875 22 23 mm hole in the duct and the Nema 4X enclosure 4X...

Страница 2: ...ransorbordiode connectstothepositiveside of the power supply Without these snubbers coils produce very large voltage spikes when de energizing that can cause malfunction or destruction of electronic circuits RELATIVE HUMIDITY WIRING INSTRUCTIONS Open the cover of the enclosure ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all transmitters Twisted pairmaybeusedfor2 wirecurren...

Страница 3: ...TROLLER ANALOG INPUT WIRING FROM CONTROLLER ANALOG INPUT FIGURE 6 TEMPERATURE WIRING 3 WIRE RTD WIRING 2 WIRE THERMISTOR or RTD WIRING FIGURE 5 OUTPUT SIGNALS OPTIONAL TEMP SENSOR CONNECT TO THE 2 or 3 22 AWG FLYING LEADS OPTIONAL TEMP SENSOR 4 20mA SUPPLY GROUND SIGNAL COMMON DC SUPPLY VOLTAGE 4 20 mA OUTPUT TB1 COM VIN VOUT OPTIONAL TEMP SENSOR VOLTAGE OUTPUT SIGNAL 3 WIRE CURRENT OUTPUT SIGNAL ...

Страница 4: ... 4 are ON When all calibration is completed remember to place the switches back into the positions that correspond to the output needed as shown in FIGURE 7 HUMIDITY REVERSE ACTING OUTPUT The output is direct acting and can be changed to reverse acting mode The output range stays the same but the corresponding RH value is opposite Example Direct Acting DA 0 10 V output mode 0 V 0 RH and 10 V 100 R...

Страница 5: ... The decrease goes into effect each time switch 6 is set to ON Reset RH Output This will reset the RH output back to the original calibration Switch 4 must be set to ON first After switch 4 is on toggle switches 5 and 6 ON then OFF After 5 and 6 are OFF slide switch 4 OFF When all calibration is completed remember to place the switches back into the positions that correspond to the output needed a...

Страница 6: ... C 0 36 F A 1K 1 KΩ nominal 60 C 140 F 0 27 C 0 49 F 21 1 C 70 F 0 17 C 0 34 F 54 4 C 130 F 0 56 C 1 00 F SENSOR SPECIFIC RH Supply Voltage Reverse Polarity Protected RH Supply Current VA RH Output Load Resistance RH Output Signal RH Accuracy 77 F 25 C RH Measurement Range Operating RH Range Operating Temperature Range Storage Temperature Range RH Stability Repeatability Sensitivity RH Response Ti...

Страница 7: ...dings SOLUTION S Checkthatyouhavethecorrectsupplyvoltageatthepowerterminalblocks Check that wiring configurations and all DIP switch settings are as in FIGURE 5 and 7 Verify that the terminal screws are all connected tightly and that all of the wires are firmly in place Verify that all of the wires are terminated properly Make sure that there is no condensation on the board Check that the input po...

Отзывы: