For each bit location:
0 = Sensor not present
1 = Sensor present
 
Bit 0 - Temperature Sensor
Bit 1 - RH sensor
N/A
For example, a value of 312 would represent 31.2 Degrees of the 
units selected in HR1.  Signed Integer.
For Example: A value of 429 would represent 42.9% Relative 
Humidity.

Temperature range Minimum value (Tenths). Signed Integer.

Temperature range Maximum value (Tenths). Signed Integer.

Relative Humidity range Minimum value (Tenths)
Relative Humidity range Maximum value (Tenths)
Always reads a value of 54321.  For testing proper communication 
and interpretation of values.

Always reads a value of -12345.  For testing proper communication 
and interpretation of values.
Always reads a string value of "-123.45" (Null terminated).   For 
testing proper communication and interpretation of values.
Non-null terminated character string of the Serial Number.  For 
example, "12345678”
Non-null terminated character string of the Firmware Version.  For 
example, "02.00.000.90"

Sensors Present

Reserved
Temperature Sensor 
Value
RH Sensor Value

Temperature Range 
Min
Temperature Range 
Max
RH Range Min
RH Range Max
Unsigned Integer 
Test Value

Signed Integer Test 
Value
Test String Test Value

Serial Number

Firmware Version

0

1
2

3

2000

2001

2002
2003
9000

9001

9002 Thru 
9005
9006 Thru 
9009
9010 Thru 
9015

1

2

3

Value - Units:
62 - Degrees Celsius
63 - Degrees Kelvin
64 - Degrees Fahrenheit
Temperature Offset Value (Tenths) Signed Integer.
User can set an offset that will be added to Temperature sensor and 
reflected in IR3.  Range of -5.0 to 5.0 degrees Celsius/degrees Kelvin 
(-9.0 to 9.0 degrees Fahrenheit).  
For example, writing -16 would add an offset of -1.6 degrees.
Relative Humidity Offset (Tenths)
User can set an offset that will be added to RH sensor and reflected 
in IR4.  Range of -10.0 to 10.0 %RH.  
For example, writing -16 would add an offset of -1.6 %RH.

Temperature Units

Temperature Offset 
Value

RH Offset Value

0

1

2

MODBUS RTU MAP

INPUT REGISTER (IR)

HOLDING REGISTER (HR)

Version: 2.0

I0000929

1001

0 = Disable Test Mode. IR3 and IR4 will read with current Sensor 

Value.

1 = Enable Test Mode. IR3 and IR4 will read with the values stored 

in HR1001 and HR1002 .

Test Mode Enable

1000

REFERENCE

DESCRIPTION

NAME

ADDRESS

COILS (CL)

Содержание BACnet / Modbus IMMERSION Series

Страница 1: ...tor shielded cable is recommended for powering the sensors ACI recommends using Belden 3105 or compatible cable for RS 485 communication wiring This wire has 120 ohm input impendence The terminal bloc...

Страница 2: ...no stratification Reference FIGURE 4 Make sure the entire thermowell is immersed If the thermowell is longer than the pipe diameter the thermowell should be installed in an elbow or Tee Apply thermal...

Страница 3: ...NPS process thread to be used with a machined thermowell or previously installed thermowell Verify the existing thermowell insertion length of the pipe is suitable for your selected Immersion If the...

Страница 4: ...a line When the jumper is set to DIS disable the resistance is not added By default the jumper is placed in the DIS disabled position SW4 OFF ON 1 ON 2 3 4 BACnet MS TP and Modbus RTU INTERFACE Contin...

Страница 5: ...when a change is made the device must be power cycled or reset for changes in address to be made DEVICE CONFIGURATION THROUGH BACnet DEVICE INSTANCE The Device Instance by default is 1035000 plus the...

Страница 6: ...NAME BN211x0 Temperature Sensor RH Sensor Temperature Calibration Offset RH Calibration Offset OBJECT ID AI 0 AI 1 AV 0 AV 1 TABLE 6 BACnet OBJECT TABLE DEVICE CONFIGURATION THROUGH MODBUS RTU MODBUS...

Страница 7: ...tring of the Firmware Version For example 02 00 000 90 Sensors Present Reserved Temperature Sensor Value RH Sensor Value Temperature Range Min Temperature Range Max RH Range Min RH Range Max Unsigned...

Страница 8: ...ite workaci com 1001 1002 9001 Thru 9016 9017 Thru 9048 9049 Thru 9080 User can set what temperature value Tenths that would be returned when reading IR3 and Test Mode is Enabled in CL1001 For Example...

Отзывы: