background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 3 

THERMOWELL INSTALLATION

ACI’s standard Immersion sensors are made to 
install into a ½” NPT female thread. Typically a 
Threadolet or Tee is installed into the pipe, but a 
hole can also be drilled and tapped. The 
pipe/system will need to be drained, unless a Hot 
Tap is being used. The recommend drill size is 
23/32 in. (18 mm). Drill the hole, and tap the hole 
with ½”-14NPT.

Always use proper thread sealants on tapered 
pipe threads of the thermowell. Screw the 
thermowell into the Threadolet, Tee, or tapped 
hole, using a wrench to tighten it firmly. Refill the 
system and check for leaks.

Best practice is to apply thermal grease to the end 
of the probe, but not required. Insert and push 
the sensor probe into the thermowell. Turn the 
sensor probe assembly clockwise to tighten 
down completely.

Open the cover of the enclosure. Refer to the 
wiring instructions (p. 1) to make necessary 
connections. After wiring, attach the cover to the 
enclosure. 

PROBE INSERTION

The “-INW”  includes a standard ½” NPS process 
thread to be used with a machined thermowell or 
previously installed thermowell. Verify the existing thermowell insertion length of the pipe is suitable for 
your selected Immersion.

If the length of the probe is too large, the probe may be pressed into its enclosure - up to an inch of 
clearance. 

Note: 

*Fabricated (welded) thermowells (-I) are not intended for moving water or high pressure service. 

Fluid velocity and wake frequency are primary factors in well failure. Machined thermowells (-IM) should be 
used in these types of applications. Fabricated thermowells are intended for tank, or low to no flow, 
applications.

FLOW DIRECTION

PIPE INSULATION

TIP OF THERMOWELL 

IN MIDDLE OF PIPE

THREADOLET

PIPE WALL

THERMOWELL

FIGURE 6: 

THREADOLET ASSEMBLY

FIGURE 7: 

ELBOW ASSEMBLY

BACnet MS/TP and Modbus RTU INTERFACE

The BACnet Master-Slave/Token-Passing (MS/TP) and Modbus Remote Terminal Unit (RTU) data link 
protocol uses EIA-485 as a two-wire, daisy chain network. A branch is a discrete chain of devices connected 
to a controller. The max number of devices per segment is 32, as per the BACnet and Modbus 
specifications. 4000 ft (1219.2 m) is the maximum recommended length for a segment, which includes all 
devices from the controller to the last device in the daisy chain. 

BACnet MS/TP and Modbus 

RTU INTERFACE 

 

(Continued)

BACnet or Modbus RTU protocol selection is 
done via SW4 switch.  Place dipswitch #4 to the 
OFF position for BACnet and the ON position 
for Modbus.  Refer to 

FIGURE 8

.

ACI’s BACnet sensors are master devices. Only 
master nodes are allowed to send and receive 
tokens on the MSTP network.  

ACI’s Modbus RTU sensors are slave devices.  
Only one master is connected to the bus and 
several slave nodes are connected to the same 
trunk.  The Master initiates communication. The 
slave nodes only respond to a request from the 
Master. Slave nodes do not communicate with 
each other.

Each branch must have all devices connected 
with (+) connected to (+) and (-) connected to 
(-). If a shielded cable is used, this is not to be 
connected to the devices. The shield cable 
should only be connected on one end to earth 
ground, usually at the controller. The start and 
end of each branch should have a termination 
resistor at the device level or at the controller.

Each device must be configured for the correct 
baud rate and have a unique address in each 
branch. The baud rate for the branch is set by 
the controller. This product has auto-baud for 
ease of network configuration but setting the 
baud rate using the DIP switches is 
recommended.  

Note: 

Auto-baud feature does 

not function when Modbus is the selected 
protocol.

Version: 2.0

I0000929

Содержание BACnet / Modbus IMMERSION Series

Страница 1: ...tor shielded cable is recommended for powering the sensors ACI recommends using Belden 3105 or compatible cable for RS 485 communication wiring This wire has 120 ohm input impendence The terminal bloc...

Страница 2: ...no stratification Reference FIGURE 4 Make sure the entire thermowell is immersed If the thermowell is longer than the pipe diameter the thermowell should be installed in an elbow or Tee Apply thermal...

Страница 3: ...NPS process thread to be used with a machined thermowell or previously installed thermowell Verify the existing thermowell insertion length of the pipe is suitable for your selected Immersion If the...

Страница 4: ...a line When the jumper is set to DIS disable the resistance is not added By default the jumper is placed in the DIS disabled position SW4 OFF ON 1 ON 2 3 4 BACnet MS TP and Modbus RTU INTERFACE Contin...

Страница 5: ...when a change is made the device must be power cycled or reset for changes in address to be made DEVICE CONFIGURATION THROUGH BACnet DEVICE INSTANCE The Device Instance by default is 1035000 plus the...

Страница 6: ...NAME BN211x0 Temperature Sensor RH Sensor Temperature Calibration Offset RH Calibration Offset OBJECT ID AI 0 AI 1 AV 0 AV 1 TABLE 6 BACnet OBJECT TABLE DEVICE CONFIGURATION THROUGH MODBUS RTU MODBUS...

Страница 7: ...tring of the Firmware Version For example 02 00 000 90 Sensors Present Reserved Temperature Sensor Value RH Sensor Value Temperature Range Min Temperature Range Max RH Range Min RH Range Max Unsigned...

Страница 8: ...ite workaci com 1001 1002 9001 Thru 9016 9017 Thru 9048 9049 Thru 9080 User can set what temperature value Tenths that would be returned when reading IR3 and Test Mode is Enabled in CL1001 For Example...

Отзывы: