background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

BACnet MS/TP and Modbus RTU INTERFACE

The BACnet Master-Slave/Token-Passing (MS/TP) and Modbus Remote Terminal Unit (RTU) data link 
protocol uses EIA-485 as a two-wire, daisy chain network. A branch is a discrete chain of devices connected 
to a controller. The max number of devices per segment is 32, as per the BACnet and Modbus 
specifications. 4000 ft (1219.2 m) is the maximum recommended length for a segment, which includes all 
devices from the controller to the last device in the daisy chain. 

BAUD RATE SELECTION

By default, BACnet Protocol and Auto-Baud is 
factory set.  If the sensor is field adjusted for 
Modbus RTU, the baud rate should be selected at 
this time to match the Master configuration.  If 
Modbus RTU protocol is selected it is 
recommended the sensor unique address is 
selected at this time.  Switches 8-10 are used to set 
the BACnet and Modbus baud rate. Refer to 

TABLE 

for switch settings. Where (0) is OFF and (1) is ON. 

If the system’s baud rate is known, it is 
recommended to set the specific baud rate to 
match the system. 

If the device is powered when a 

change is made, the device must be power cycled 
or reset for changes in baud rate to be made.

BAUD RATE

Auto-Baud
9600
19200
38400
57600
76800
Reserved

SW 8

0
0
0
0
1
1
1

SW 9

0
0
1
1
0
0
1

SW 10

0
1
0
1
0
1
0

TABLE 3: 

BAUD RATE SELECTION

FIGURE 8: 

SW4 DIPSWITCH

SETTINGS

**Note: Auto-Baud not available for Modbus RTU.

DIP 1 – PAR2 (only applies to Modbus)

DIP 2 – PAR1(only applies to Modbus)

DIP 3 – OPEN (For Future Use)

DIP 4 -- OFF is BACNET, ON is MODBUS

EOL TERMINATION RESISTANCE 

SELECTION

RS-485 requires that the last device in a chain have 
a termination resistor. This is controlled using a 
jumper in the EN (enabled) position marked on 

FIGURE 9

. When the jumper is set to EN (enabled), a 

120Ω resistance is added in parallel to the data line. 
When the jumper is set to DIS (disable), the 
resistance is not added. By default, the jumper is 
placed in the DIS (disabled) position.

SW4

OFF

ON

1

ON

2
3
4

BACnet MS/TP and Modbus 

RTU INTERFACE 

 

(Continued)

BACnet or Modbus RTU protocol selection is 
done via SW4 switch.  Place dipswitch #4 to the 
OFF position for BACnet and the ON position 
for Modbus.  Refer to 

FIGURE 8

.

ACI’s BACnet sensors are master devices. Only 
master nodes are allowed to send and receive 
tokens on the MSTP network.  

ACI’s Modbus RTU sensors are slave devices.  
Only one master is connected to the bus and 
several slave nodes are connected to the same 
trunk.  The Master initiates communication. The 
slave nodes only respond to a request from the 
Master. Slave nodes do not communicate with 
each other.

Each branch must have all devices connected 
with (+) connected to (+) and (-) connected to 
(-). If a shielded cable is used, this is not to be 
connected to the devices. The shield cable 
should only be connected on one end to earth 
ground, usually at the controller. The start and 
end of each branch should have a termination 
resistor at the device level or at the controller.

Each device must be configured for the correct 
baud rate and have a unique address in each 
branch. The baud rate for the branch is set by 
the controller. This product has auto-baud for 
ease of network configuration but setting the 
baud rate using the DIP switches is 
recommended.  

Note: 

Auto-baud feature does 

not function when Modbus is the selected 
protocol.

FIGURE 9: 

EOL TERMINATION 

JUMPERS

END OF LINE 

TERMINATION ENABLED

END OF LINE 

TERMINATION DISABLED

EN

DIS

EN

DIS

Version: 2.0

I0000929

Содержание BACnet / Modbus IMMERSION Series

Страница 1: ...tor shielded cable is recommended for powering the sensors ACI recommends using Belden 3105 or compatible cable for RS 485 communication wiring This wire has 120 ohm input impendence The terminal bloc...

Страница 2: ...no stratification Reference FIGURE 4 Make sure the entire thermowell is immersed If the thermowell is longer than the pipe diameter the thermowell should be installed in an elbow or Tee Apply thermal...

Страница 3: ...NPS process thread to be used with a machined thermowell or previously installed thermowell Verify the existing thermowell insertion length of the pipe is suitable for your selected Immersion If the...

Страница 4: ...a line When the jumper is set to DIS disable the resistance is not added By default the jumper is placed in the DIS disabled position SW4 OFF ON 1 ON 2 3 4 BACnet MS TP and Modbus RTU INTERFACE Contin...

Страница 5: ...when a change is made the device must be power cycled or reset for changes in address to be made DEVICE CONFIGURATION THROUGH BACnet DEVICE INSTANCE The Device Instance by default is 1035000 plus the...

Страница 6: ...NAME BN211x0 Temperature Sensor RH Sensor Temperature Calibration Offset RH Calibration Offset OBJECT ID AI 0 AI 1 AV 0 AV 1 TABLE 6 BACnet OBJECT TABLE DEVICE CONFIGURATION THROUGH MODBUS RTU MODBUS...

Страница 7: ...tring of the Firmware Version For example 02 00 000 90 Sensors Present Reserved Temperature Sensor Value RH Sensor Value Temperature Range Min Temperature Range Max RH Range Min RH Range Max Unsigned...

Страница 8: ...ite workaci com 1001 1002 9001 Thru 9016 9017 Thru 9048 9049 Thru 9080 User can set what temperature value Tenths that would be returned when reading IR3 and Test Mode is Enabled in CL1001 For Example...

Отзывы: