background image

__________________________________________________________________________________ 

Superdryer 62 Owner’s Manual 

 

6

 

 

 

 

Operation 

 
During normal operation, the dehumidifier will automatically cycle “on” and “off” to maintain 

your desired set point.  If it should need to run for extended periods of time, the 

dehumidifier features an automatic defrost cycle to melt any ice that accumulates on 
evaporator coil.  Approximately every 35 minutes of continuous operation, the unit will test 

for the need for a defrost cycle.  If required, it will defrost for approximately 3 minutes. 
 

Warning

:  Never apply an external source of heat to melt ice off coil.   

 

Maintenance

 – Annual Inspection of Coils and drain line is required. 

 

1.

 

Unplug Unit 

2.

 

Filter may be cleaned by 

a.

 

Vacuuming 

b.

 

Washing with warm, soapy water. Rinse and shake dry. 

3.

 

Coils may be cleaned by 

a.

 

Vacuuming the external surfaces of coil 

b.

 

Blowing compressed air from behind coils.  Hold air nozzle 6” away from coil to 

avoid damage.

 

Warning

:  Do not steam clean refrigerant coils. 

 

4.

 

Plug in Unit 

5.

 

Test Refrigerant Charge 

a.

 

Confirm compressor is running and allow to run for minimum of 15 minutes 

i.

 

If under 70

°

F, a layer of ice will form on evaporator coils 

ii.

 

If over 70

°

F, a layer of frost or water droplets will form on coil 

6.

 

Test Defrost System 

a.

 

Leave unit running for approximately 35 minutes (45-55 minutes).  The unit 

should enter a defrost mode for approximately 3 minutes.  The unit will run fan 
only for a period of time and then check the temperature of the coil.  If 

necessary, the unit will enter a defrost mode with the compressor operating 

and fan off to defrost the coil  If the unit will not defrost, either 

i.

 

Control board may be defective 

ii.

 

Bypass valve may be defective 

7.

 

After routine maintenance has been completed, return humidistat to desired setting. 

8.

 

When you are ready to move unit, depress button on condensate pump (while unit is 

“on”) to drain condensate or empty water tank prior to moving.  This will prevent 
water from splashing on inside of unit. 

 
If any problems occur during routine maintenance, contact your contractor or the factory.

 

 

 

Содержание Superdryer 62

Страница 1: ...midifiers I In ns st ta al ll la at ti io on n a an nd d O Op pe er ra at ti io on ns s M Ma an nu ua al l R Re ea ad d a an nd d S Sa av ve e T Th he es se e I In ns st tr ru uc ct ti io on ns s Distributed Exclusively By Manufactured by Air Cleaning Equipment Inc Broadway NC 27505 Phone 919 258 3330 www AirCleaningEquipment com ...

Страница 2: ...um of 12 clearance and the discharge needs a minimum of 48 clearance If the unit is utilized in a narrow room the unit should be positioned so that the inlet and discharge are facing the longest straight runs Do not insert any objects into the inlet or discharge If service is required call a qualified technician All work on unit should be done with the unit off and unplugged Do not use water to cl...

Страница 3: ...e serious injury from electric shock 1 Disconnect electrical power before servicing or moving 2 Plug unit only into grounded electrical outlet 3 Do not use extension cord 4 Do not use plug adapter Power Supply 115V 60 Hz Single Phase Outlet Requirement 3 Prong Circuit Protector 15 Amp Time Delay Fuse or Circuit Breaker Principle of Operation The Superdryer Series Dehumidifier utilizes its integral...

Страница 4: ...mum of 2 hours before turning the unit on Route drain line 3 4 ID tubing on gravity drain 3 8 ID tubing on units with condensate pump to drain or outside of the area Note On units with gravity drain Drain line must have a downward slope to drain Not applicable to units with reservoirs Reference Fig 1 2 De humidistat 7 starts the functioning of the dehumidifier when the humidity is higher than the ...

Страница 5: ...tion Position of Dehumidistat Knob 1 2 3 4 5___________________ Approximate Room Setpoint 70 60 48 35 25 Relative Humidity In OFF the machine will never start In CONT the machine will never stop NOTE Humidistat settings are approximate only For critical applications you may want to confirm actual settings with a psychrometer and adjust according Display Panel Indications Power Indication Red light...

Страница 6: ... coil to avoid damage Warning Do not steam clean refrigerant coils 4 Plug in Unit 5 Test Refrigerant Charge a Confirm compressor is running and allow to run for minimum of 15 minutes i If under 70 F a layer of ice will form on evaporator coils ii If over 70 F a layer of frost or water droplets will form on coil 6 Test Defrost System a Leave unit running for approximately 35 minutes 45 55 minutes T...

Страница 7: ...mp AMPS FULL LOAD AT 80F 60 5 8 FLA POWER CORD 20 GROUNDED PLUG FILTER SIZE 13 5 x 12 Troubleshooting 1 Unit will not operate a Insure unit is plugged in and red power lamp is illuminated b Insure humidistat is set to high enough level to operate c If unit plugged in and red power lamp is off check fuse or breaker for outlet to make sure power is getting to unit 2 If green full light is on a On un...

Страница 8: ...rranty Seller s liability is limited to replacement of defective parts or components and does not include any cost of labor including but not limited to labor to remove and or reinstall any defective part ACE Fral shall not be responsible for loss of use of any product loss of time inconvenience or damage to other equipment or any other indirect or consequential damage with respect to property whe...

Отзывы: