![Accutrol AVC5000 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/accutrol/avc5000/avc5000_installation-and-operation-manual_3846603006.webp)
Installation & Operation Manual - Model AVC5000
Contents of this Manual are Subject to Change Without Notification
Page 6
SECTION 2 - SPECIFICATIONS
PERFORMANCE
Accuracy +/- 5% of reading or 5 CFM, whichever is greater
Speed of Response <1 second
Shut-off Leakage Rate
@ 3”wc valve DP
Standard Round Valves (Model AVC51xx-xx) <1.5% FS max
Round Valves with Blade Seals (Model AVC51xx-xx-S) <0.5% FS max
Standard Rectangular Valves (Model AVC52xx-xx) <1.5% FS max
Rectangular Valves with Blade Seals (Model AVC52xx-xx-S) <1% FS max
Max Operating Pressure
3”wc
Differential Pressure Across Valve
Min Operating Pressure Reference Section 2.1
Airflow Range Reference Section 2.1
Failure Mode Fail Last Position or Fail Open/Closed (selectable by model code)
ENVIRONMENTAL
Temperature Airstream: -20 to 165 deg. F for all Standard Valve Models
-20 to 375 deg. F for the High Temp SS Valve Models
Ambient: -20 to 125 deg. F
Storage: -40 to 165 deg. F
Humidity 0 to 90% non-condensing
ELECTRICAL
Input Power 24VAC +/- 20% 50-60Hz, 28 VA max for single valves, 55VA max. for dual valves
24VDC +/-10%, 15W max. for single valves, 30W max for dual valves
Analog Inputs AI-1, AI-2 and AI-3: Jumper Configurable
Voltage: 0-10Vdc Range, 100K ohm Impedance
Current: 0-20mA Range, 500 ohm Impedance
Resistance: 20K ohm Range, 500uA Current Source
AI-2 and AI-3 also include 100K ohm Range, 100uA Current Source
12-bit Resolution
Digital Inputs 2 dry-contact inputs
Analog Outputs 0-20mA, 4-20mA, 0-10v, 2-10v, 0-5v or 1-5v (software configurable)
12-bit Resolution
V-out capable of driving 1K ohm load
Alarm Relay Output DPDT, NC/NO contacts, rated load 1A @ 30 vDC or 0.3A @ 125vac
Max operating voltage = 125VAC or 60 vDC
Max carry current = 1A
Max switching capacity = 37 VA, 30W
Network Com Port EIA 485 2-wire BACnet MS/TP
Full Master Node State Machine
Data Rates 9600, 19200, 38400, 57600, 76800 and 115200
DIP Switch provided for setting the MAC address
¼ Unit Load Receiver Input Impedance
Network bias and EOL Termination not provided within the AVC
Configuration Port USB 2.0, Isolated, Mini B Connector
Status Indicators LED Status Indicators for Power, Alarm, Analog Output, BACnet Communications, USB
Communications and AVC Status
I/O Terminal Blocks 2 and 3 position vertical pluggable screw terminal blocks
Electromagnetic
Compatibility
EMC Directive 2004/108/EC
Low Voltage Directive 2004/108/EEC
EN61326-1:2013
FCC Part 15 (Note 1)
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required
to correct the interference at the user’s own expense. This Class A digital apparatus meets all requirements of the Canadian
Interference-Causing Equipment Regulations
MATERIALS OF CONSTRUCTION
Reference Table 1