![Accutrol AVC5000 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/accutrol/avc5000/avc5000_installation-and-operation-manual_3846603041.webp)
Installation & Operation Manual - Model AVC5000
Contents of this Manual are Subject to Change Without Notification
Page 41
2.
Perform the face velocity adjustment procedure by following the step-by-step
instructions provided in the Face Velocity Calibration Window (shown below).
3.
The Controller information and Calibration Data can be saved to a .csv file once the
controller has been updated with the calibration adjustment has been saved.
4.
Complete a final face velocity measurement to insure the adjusted face velocity
reading correlates to the field measurement.
For this example, the field
measurement for the Face
Velocity is 105 FPM
The adjustment required to
correlate the display with the
field measurement is -5%
These parameters are
captured during the
calibration process and can
be saved to a .csv file for
record.