Direct Gas Make-Up Air
4
Clearance to Combustibles
Clearance to combustibles is defined as the minimum
distance required between the unit and adjacent
combustible surfaces to ensure the adjacent surface
temperature does not exceed 90ºF above the ambient
temperature.
General
Model Number Code
Floor
Top
Sides
Ends
Insulated/Units
0
0
0
0
Non Insulated Units
0
6 (16)
6 (16)
6 (16)
All measurements are shown in inches (cm).
The model number code provides basic identification
of the unit. The serial number can be used by the
manufacturer’s representative or the factory to identify
the specific unit configuration. The serial number
of the unit must be provided when consulting the
manufacturer’s representative or the factory.
Installation
Required Clearances
Recommended Minimum Service Clearances
Model
Housing
A inches (cm)
XDG
H05
36 (92)
H10
36 (92)
H20
37 (94)*
H30
48 (122)
XDGX
H12
33 (84)
H22
44 (112)**
H32
52 (132)
H35
78 (198)
H38
96 (244)
H42
101 (255)
* 67 in. (170 cm) when equipped with evaporative cooling module
** 61 in. (155 cm) when equipped with evaporative cooling module over
4800 cfm
Service Clearances
Service clearances are factory recommendations for
ease of servicing
.
All deviations must still adhere to
clearance to combustibles requirements. All deviations
from the service clearance recommendations are at
the discretion of the end-user as this may impede
component removal.
Reference the
Start-Up: Optional Features,
Other,
PDX Cooling Module
section in this Installation,
Operation and Maintenance Manual for further
clearance requirements, if applicable.
Not all models listed will incorporate access on both
sides; this will vary based on supply fan type and
options selected.
Note: If XDG-H05 is equipped with an evaporative
cooling module, access to the filters, media, sump,
and water connections
is accomplished through
the roof of the evaporative
cooling module. A
minimum service clearance
of 24 inches (61cm) is
recommended above this
module.
Required Clearances
SUPPLY
FAN
SECTION
DIRECT GAS
SECTION
OPTIONAL
COOLING
COIL
SECTION
OPTIONAL
FILTER
SECTION
OPTIONAL
WEATHERHOOD
EVAPORATIVE COOLING
SECTION
OPTIONAL INLET
DAMPER SECTION
OPTIONAL DG ACCESS
CONTROL CENTER
36 inches (91.4 cm)
36 inc
hes (91.4 cm)
36 inc
hes (91.4 cm)
A
Measure from widest point of unit
Model Parent
XDG and XDGX
XDGX - P1 2 0 - H32 - MF
Fan Quantity
1-2
Housing Size
10-50
Wheel Diameter (in.)
8 - 36
Optional Fan
*P - Plenum Supply Fan
*If no P is shown, then a forward-curved fan is provided.
Mixed Flow