Frequently Asked Questions

What temperature is the thermostat set from the 
factory?

 95º 

Fahrenheit.

Will the temperature interlock automatically start/
stop the fans?

 

When connected properly to fan starters the 
temperature interlock will automatically control 
the fans without input from the user. However, it is 
intended to be used as a back-up to manual control.

May I connect the power going to my fan directly 
through the control box?

 

No, the control box should only use control voltage 
only (24-115 VAC), and a separate 115 VAC power 
source is required to run the temperature interlock 
controls. Accurex recommends the use of starters 
sized for each fan.

What is the purpose of the timed relay in the control 
box?

 

The timed relay is used to delay the shut down 
of the fans to prevent fan on/off cycling while the 
temperature in the exhaust duct can reach steady 
state. Without the delay, cycling could occur both on 
startup or shutdown of cooking equipment. The delay 
is typically set at 20 minutes.

Can I use one control box for multiple hood systems?

 

This can be done, however, it is not recommended. 
Any one of the thermostats would turn on all hoods 
running on that control box. It is better to have one 
hood/fan per control box, plus a significant energy 
savings can be obtained if one or more of the hoods 
is not in operation.

Can I still turn my fan on and off?

  

Yes, the temperature interlock is designed to be 
operated with a typical on/off switch. The fan may not 
turn off immediately after turning the fan switch off, it 
will sense when the cooking operations have cooled 
and then turn off.

Replacement Parts

Part 

Number

Description

383923

Thermostat, Vulcan  
1C2B9 5/8-inch Type C

451168

Evergreen Quik-Seal, 1/2-inch  
#171 (1-1/8 inch hole size)

830125

Extension, Octagon (drilled)  
SC55151-1/2 (380928)

380926

Cover, Octagon Box  
SC#54-C-1RACO 722

732396

J-Box Plate

384905

Terminal Block, Single Pole, 
DIN-RAIL MT, ABB ZS6

384908

Jumper, DIN-RAIL  
Terminal Block 2 Pole ABB JB6-2

383271

Time Delay Relay SSAC  
#KRDB424 SPST 1-100 min.

452614

Evergreen Compression Seal,  
5/8-inch, #302

Codes and Standards Compliance

• UL 

710

•  National Fire Protection Association (NFPA 96)

•  International Mechanical Code (IMC)

Temperature Interlock

11

Содержание Temperature Interlock

Страница 1: ...r before working on or near the product Lock and tag the disconnect switch or breaker to prevent accidental power up CAUTION It is the responsibility of the installer to make sure both electrical and gas appliances shut down in the event of a fire or in the event of a power loss to the building when this sequence is required by the authority having jurisdiction General Safety Information Only qual...

Страница 2: ...consists of a time delay relay adjustable thermostat junction box and a UL Listed liquid tight fitting The relay can be contained in a stand alone box or can be added to a pre engineered fan control center Purpose To meet IMC an interlock between exhaust fans and cooking equipment must be present for all Type I hood systems This product will utilize a thermostat in the exhaust duct collar or in the...

Страница 3: ...ntrol Box Mounting Installation Locate an area with enough space to mount the control box and fasten to the wall Avoid installing the control box in environments with high magnetic and or radio frequency interference Hood Plan View 19 525 inches 495 9 mm 3 inch air space 76 2 mm 2 inch typical 50 8 mm Exhaust Area Supply Area optional Sensor Install cut out area 2 Find a suitable location for the ...

Страница 4: ...e suppression nozzles or other items installed in the ducts If an exhaust fire damper is present in the hood exhaust collar it must be removed prior to temperature sensor installation A 11 8 to 1 inch 28 6 to 31 8 mm diameter hole must be cut into the duct 2 inches 50 8 mm above the hood top 2 Place the J box plate inside the octagon extension ring and place over the hole in the exhaust collar 3 Di...

Страница 5: ...all exhaust fan starter coils to terminal block CP2 5 Wire common C of dedicated fire system microswitch to terminal block CP2 6 Wire normally open NO to fire system microswitch mentioned in item 5 above to terminal block CP1 7 Wire normally close NC of fire system microswitch mentioned in item 5 above to one side of all supply fan starter coils 8 Wire the other side of all exhaust fan and supply fan...

Страница 6: ...pen NO of fire system microswitch mentioned in item 3 above to terminal block CP1 5 Run three 3 low voltage wires 18 gauge from MUA unit control center down to temperature interlock panel a Terminal block R in MUA connects to terminal block CP1 in temperature interlock panel b Terminal block H in MUA connects to terminal block CP2 in temperature interlock panel c Terminal block G in MUA connects to...

Страница 7: ... back of the thermostat Use a small blade screwdriver to make the adjustments 1 Turn counterclockwise to increase the temperature set point turn clockwise to decrease the temperature set point 2 Quarter revolution in either direction corresponds to a 22 5 F 5 3 C adjustment Be sure to make small adjustments about 1 16 of a turn 6 F or less at one time 3 Do not exceed more than one half revolution ...

Страница 8: ...D red PR purple FIELD WIRING BK black BL blue UNLESS SPECIFIED BR brown FACTORY WIRING Shunt Trip Breaker Neutral Starter Switch Light Ground Fire MicroSwitch Exhaust Fan Supply Fan Overload Contactor TDR TS1 12 Time Delay Relay Temperature Sensor LABEL DESCRIPTION WIRE COLOR ALL WIRING 90 C 14 GA USE MINIMUM 60 Copper Wire FIELD WIRING S1 CP1 CP2 FS FIELD WIRE FIRE SYSTEM MICROSWITCH NO NC C ST T...

Страница 9: ...a note as to where the time relay was originally set 3 Heat up cooking equipment with fans off Once the temperature reaches the set point of the thermostat the fans will start preferably within 5 to 10 minutes If the fans take more than 15 minutes to start decrease the temperature set point by turning the adjustment screw 1 16 turn clockwise Do not apply direct flame to the thermostat 4 If an adjus...

Страница 10: ...y Fans do not turn on quick enough Decrease temperature set point Maintenance Daily Clean thermostat with cloth and degreaser Keep clean for best performance Can clean weekly depending upon grease accumulation Weekly Dependant on grease production and grease filter type clean thermostat Seasonal May have to change temperature setting on back of thermostat if ambient kitchen temperatures fluctuate be...

Страница 11: ...se one control box for multiple hood systems This can be done however it is not recommended Any one of the thermostats would turn on all hoods running on that control box It is better to have one hood fan per control box plus a significant energy savings can be obtained if one or more of the hoods is not in operation Can I still turn my fan on and off Yes the temperature interlock is designed to be...

Страница 12: ... Accurex reserves the right to change specifications without notice Product warranties can be found online at accurex com either on the specific product page or in the Warranty section of the website at Accurex com Resources Warranty Our Commitment P O Box 410 Schofield WI 54476 Phone 800 333 1400 Fax 715 241 6191 Parts 800 355 5354 accurex com ...

Отзывы: