background image

Operation

1.  Turn fans on and off using the fan switch. It is normal 

for the fans to remain running after the switch is 
turned off. The exhaust thermostat will open after 
heat is no longer present under the hood which will 
activate the timed relay to begin its countdown. 
Once time has expired, fans will shut down. The 
timed relay is adjustable from 1-100 minutes. The 
recommended time delay setting is approximately 
20 minutes.

2.  In the event that the cooking equipment is started 

without turning the fans on manually, the fans will 
turn on automatically and remain running with the 
presence of heat under the hood. The exhaust 
thermostat will open after heat is no longer present 
under the hood which will activate the timed relay to 
begin its countdown. Once time has expired, fans 
will shut down.

Testing

1.  Turn fan switch on, then off to ensure proper fan 

operation before cooking equipment is started. Once 
this is verified, testing can proceed.

2.  For testing only, locate the time delay relay. Turn the 

time adjustment knob counterclockwise to the first 
mark in order to expedite the testing process. Make 
a note as to where the time relay was originally set.

3.  Heat up cooking equipment with fans off. Once the 

temperature reaches the set point of the thermostat 
the fans will start, preferably within 5 to 10 minutes. 
If the fans take more than 15 minutes to start, 
decrease the temperature set point by turning the 
adjustment screw 1/16 turn clockwise. Do not apply 
direct flame to the thermostat

4.  If an adjustment was made in Step 3, repeat now.

5.  After verification of fan start-up, shut down cooking 

equipment. The fan switch should still be in the off 
position. Once cooking equipment has cooled, the 
thermostat will open triggering the timer function in 
the time delay relay to begin. Once time has expired, 
the fans will shut down. Thermostat operation can 
be verified by checking voltage (115 VAC) between 
terminal blocks T1-B and N1 in the control panel.

6.  Once proper operation has been verified, set 

the dial on the timed relay to its original setting 
(approximately 20 minute delay).

CAUTION

The thermostats should never be exposed to direct 
flame. This can cause permanent damage to the 
thermostat.

NOTE

During testing, if fans do not start automatically in 
the first 15 minutes of cooking equipment activation, 
manually start fans to avoid accidental fire system 
dump due to heat build-up.

Temperature Interlock

9

Содержание Temperature Interlock

Страница 1: ...r before working on or near the product Lock and tag the disconnect switch or breaker to prevent accidental power up CAUTION It is the responsibility of the installer to make sure both electrical and gas appliances shut down in the event of a fire or in the event of a power loss to the building when this sequence is required by the authority having jurisdiction General Safety Information Only qual...

Страница 2: ...consists of a time delay relay adjustable thermostat junction box and a UL Listed liquid tight fitting The relay can be contained in a stand alone box or can be added to a pre engineered fan control center Purpose To meet IMC an interlock between exhaust fans and cooking equipment must be present for all Type I hood systems This product will utilize a thermostat in the exhaust duct collar or in the...

Страница 3: ...ntrol Box Mounting Installation Locate an area with enough space to mount the control box and fasten to the wall Avoid installing the control box in environments with high magnetic and or radio frequency interference Hood Plan View 19 525 inches 495 9 mm 3 inch air space 76 2 mm 2 inch typical 50 8 mm Exhaust Area Supply Area optional Sensor Install cut out area 2 Find a suitable location for the ...

Страница 4: ...e suppression nozzles or other items installed in the ducts If an exhaust fire damper is present in the hood exhaust collar it must be removed prior to temperature sensor installation A 11 8 to 1 inch 28 6 to 31 8 mm diameter hole must be cut into the duct 2 inches 50 8 mm above the hood top 2 Place the J box plate inside the octagon extension ring and place over the hole in the exhaust collar 3 Di...

Страница 5: ...all exhaust fan starter coils to terminal block CP2 5 Wire common C of dedicated fire system microswitch to terminal block CP2 6 Wire normally open NO to fire system microswitch mentioned in item 5 above to terminal block CP1 7 Wire normally close NC of fire system microswitch mentioned in item 5 above to one side of all supply fan starter coils 8 Wire the other side of all exhaust fan and supply fan...

Страница 6: ...pen NO of fire system microswitch mentioned in item 3 above to terminal block CP1 5 Run three 3 low voltage wires 18 gauge from MUA unit control center down to temperature interlock panel a Terminal block R in MUA connects to terminal block CP1 in temperature interlock panel b Terminal block H in MUA connects to terminal block CP2 in temperature interlock panel c Terminal block G in MUA connects to...

Страница 7: ... back of the thermostat Use a small blade screwdriver to make the adjustments 1 Turn counterclockwise to increase the temperature set point turn clockwise to decrease the temperature set point 2 Quarter revolution in either direction corresponds to a 22 5 F 5 3 C adjustment Be sure to make small adjustments about 1 16 of a turn 6 F or less at one time 3 Do not exceed more than one half revolution ...

Страница 8: ...D red PR purple FIELD WIRING BK black BL blue UNLESS SPECIFIED BR brown FACTORY WIRING Shunt Trip Breaker Neutral Starter Switch Light Ground Fire MicroSwitch Exhaust Fan Supply Fan Overload Contactor TDR TS1 12 Time Delay Relay Temperature Sensor LABEL DESCRIPTION WIRE COLOR ALL WIRING 90 C 14 GA USE MINIMUM 60 Copper Wire FIELD WIRING S1 CP1 CP2 FS FIELD WIRE FIRE SYSTEM MICROSWITCH NO NC C ST T...

Страница 9: ...a note as to where the time relay was originally set 3 Heat up cooking equipment with fans off Once the temperature reaches the set point of the thermostat the fans will start preferably within 5 to 10 minutes If the fans take more than 15 minutes to start decrease the temperature set point by turning the adjustment screw 1 16 turn clockwise Do not apply direct flame to the thermostat 4 If an adjus...

Страница 10: ...y Fans do not turn on quick enough Decrease temperature set point Maintenance Daily Clean thermostat with cloth and degreaser Keep clean for best performance Can clean weekly depending upon grease accumulation Weekly Dependant on grease production and grease filter type clean thermostat Seasonal May have to change temperature setting on back of thermostat if ambient kitchen temperatures fluctuate be...

Страница 11: ...se one control box for multiple hood systems This can be done however it is not recommended Any one of the thermostats would turn on all hoods running on that control box It is better to have one hood fan per control box plus a significant energy savings can be obtained if one or more of the hoods is not in operation Can I still turn my fan on and off Yes the temperature interlock is designed to be...

Страница 12: ... Accurex reserves the right to change specifications without notice Product warranties can be found online at accurex com either on the specific product page or in the Warranty section of the website at Accurex com Resources Warranty Our Commitment P O Box 410 Schofield WI 54476 Phone 800 333 1400 Fax 715 241 6191 Parts 800 355 5354 accurex com ...

Отзывы: