Read Data (Function Code 03)
Query
This function allows the user to obtain the measurement results of the Acuvim L series meter.
Below is an example to read 6 registers corresponding to the device clock of the meter, starting
at 1040H.
Transaction
identifier hi
Transaction
identifier lo
Protocol
identifier hi
Protocol
identifier lo
Length hi
Length lo
Unit
identifier
00H
00H
00H
00H
00H
06H
01H
Fun
Data start reg hi
Data start reg lo
Data #of regs hi
Data #of regs lo
03H
10H
40H
00H
06H
An example response is provided to read the time (2006-12-18 14:15:20).
Transaction
identifier hi
Transaction
identifier lo
Protocol
identifier hi
Protocol
identifier lo
Length hi
Length lo
Unit
identifier
00H
00H
00H
00H
00H
0FH
01H
Fun
Byte
count
Data1
hi
Data1
lo
Data2
hi
Data2
lo
Data3
hi
Data3
lo
Data4
hi
Data4
lo
Data5
hi
Data5
lo
Data6
hi
Data6
lo
03H 0CH 07H D6H 00H 0CH 00H 12H 00H 0EH 00H 0FH 00H 14H
Preset/Reset Multi-Register(Function Code 16)
Query
This function code allows the user to modify the contents of a register. The example below is
a request to an Acuvim L series meter with device address 1 to preset the CT1(500) and CT2(5)
registers. The CT1 data address is 1008H and CT2 is at 1009H.