www.accuenergy.com
V: 1.0 Revised: Jan. 2018
Chapter 5: Communication
73
20DH
525
Meter Data Reset
Word
W
Bit0: Reset Demand Record
Bit1: Reset Event Record
Bit2: Reset System Event Record
Bit3: Reset Meter Opening Record
Bit4: Reset Demand Event
Bit5: Reset Alarm Event
Bit6: Reset Meter Operation Time
Bit7: Reset Time of Meter Opera-
tion with Load
Bit8: Reset Meter Record (Reset
Energy record, demand peak and
happening time record, system
event record, etc)
0:Reset
1: NO
Note: Reset not valid without
Communication Revise Opera-
tion Authority
2~4
1
20EH
526
Optional Display
Symbol 1
Please see Appendix “Optional
Display Symbol Setting”
2~4
1
20FH
527
Optional Display
Symbol 2
2~4
1
210H
528
Parameter Mea-
surement Side
Word
R/W
0: Primary Side
1: Secondary Side
0
2~4
1
211H
529
Wiring Mode
Word
R/W
0:3LN
1:2LL
2:1LL
3:1LN
0
2~4
1
212H
530
CT2 Value
Word
R/W
1; 5; 100; 200; 333
Accord-
ing to
the order
2~4
1
213H
531
CT1 Value
Word
R/W
1~50000/5~50000
5
2~4
1
214H
532
CTN Value
Word
R/W
1~50000/5~50000
5
4
1
215H
533
PT2 Value
Word
R/W
50.0~400.0 (Communication val-
ue is 10 times of the real value)
220.0
2~4
1
216H
-217H
534
-535
PT1 Value
Word
R/W
50.0~999999.9 (Communication
Value is 10 times of the real
value)
220.0
2~4
2
218H
536
Energy Pulse
Constant
Word
R/W
1-60000
5000
2~4
1
219H
537
Energy Pulse
Width
Word
R/W
20-100 ms
80
2~4
1
21AH
538
Energy Display
Decimal
Word
R/W
0,1,2,3
1
2~4
1
21BH
539
Relay Operating
Mode
Word
R/W
0: Relay Control
1: Alarm Output
0
2~4
1
21CH
540
Connection De-
tection Enable
Word
R/W
0: No Enable
1: Enable
1
2~4
1