www.accuenergy.com
V: 1.0 Revised: Jan. 2018
Chapter 5: Communication
101
Meter Clearance Event
Table 5-27 Meter Clearance Address
Modbus Address
Parameter
Description
Data
Type
R/W
Range
Default
Model
Register
Number
Hex
Decimal
1E00H-1E01H
7680-7681
Total meter clear-
ance time
Word
R
0-999999
2~4
2
Last time meter cleared record
1E02H-1E04H
7682-7684
Occur time
Word
R
YYMMDDhhmmss
2~4
3
Last 2
nd
– 3
rd
time
1E05H-1E0AH
7685-7690
2~4
6
RO Control Function (01H read, 05H write)
RO state read (01H)
Table 5-28 RO Control Function-01H Read
Modbus Address
(HEX)
Parameter
Description
Data Type
R/W
Data Range
Default
Model
Register
Number
0000H
RO state
Word
R
1: ON 0: OFF
1
RO control (05H)
Table 5-29 RO Control function-05H Write
Modbus Address
(HEX)
Parameter
Description
Data Type
R/W
Data Range
Default
Model
Register
Number
0000H
RO control
Word
W
FF00: ON
0000: OFF
1