www.accuenergy.com
V: 1.0 Revised: Jan. 2018
AcuRev 1310
62
DIN-Rail Power Meter
I XXXXXX, where X is either ‘1’ or ‘0’
• ‘0’ represents the connection is correct
• ‘1’ represents the connection is incorrect
On the meter display digits 1~3 (from left to right) represent Phase A CT, Phase B CT, Phase C
CT being in the reverse direction . Digits 4~6 represent Phase A CT, Phase B CT, Phase C CT being
connected incorrectly.
4.8 Sealing Function
The AcuRev 1310 series meter supports a sealing function. When the seal is open, the read write
functions are available. When the seal is closed some of the meters functions which include
parameters and optional parameters will be blocked and limited. These parameters can still be
accessed by keys communication, but cannot be modified (Write function not available when
seal is closed) when sealed status is present.
Address 209H corresponds to parameters blocked by the seal, which can be configured by users
through communication. These settings will be valid only when the seal is in sealed status.
From 101H, we can check if the sealing state is opened or closed. When the seal status is open
the address displays open sealing state. When the seal status is closed, the address displays
closed sealing state, and the corresponding content will be blocked.
Note:
‘X’ means that these addresses will be blocked for keys and communication, and
‘- ‘means this function is unavailable.
Seal Standard Content:
Table 4-3 Seal Standard Content
Address
Parameter Description
Communication
Key
203H
Pulse Quantity choice
X
X
204H
Demand Calculation
X
-
205H
Demand Calculation Cycle
X
-
206H
Slip Time Demand Calculation
X
-
207H
Reactive Power Calculation Method
X
X
208H
VAR/PF Convention
X
-
209H
Seal Optional Content
X
-
213H
Remove Electric Meter Data (Except Demand Data)
X
-
216H
Measurement Side
X
X
217H
Wiring Mode
X
X
218H
CT2
X
X
219H
CT1
X
X