AcuRev 1310
36
DIN-Rail Power Meter
are being used, enter in the primary rating of the CT here.
•
Press “SET” to enter the edit mode and to move to the next digit.
•
Press “SCROLL” to change the value of the digit.
•
Press “SET” to confirm the setting and move to the next page.
•
The next page will correspond to the PT2 setting. If no PT’s are being used, leave this set-
ting as the default and press the “SCROLL” key to go to the next page. If you are using PT’s,
enter the secondary value of the PT here.
•
Press “SET” to enter the edit mode and to move to the next digit.
•
Press “SCROLL” to change the value of the digit.
•
Press “SET” to confirm the setting and move to the next page.
•
The next page will be “S-12” for the primary rating of the PT if it is being used.
•
Press the “SET” key to enter edit mode and to move to the next digit.
•
Press the “SCROLL” key to change the value of the digit.
•
Press the “SET” key to confirm the setting and move to the next page.
Once all of the initial meter configurations are set, the meter should now begin to read data cor-
rectly.
3.6 Energy Pulse Output
The AcuRev 1310 series supports the transmission of energy pulses through the P1 and P2 ter-
minals of the meter. The AcuRev 1310 series uses the KYZ output to transmit test pulses that are
proportional to the accumulated energy that the meter is measuring.
The maximum output voltage and current of the pulse output circuit in the AcuRev 1310 series
is 250V and 100mA respectively.
Configuration
Ensure that the following configurations in the meter are correct to make certain the accuracy of
the meter.
•
Wiring Mode
•
CT2
•
CT1
•
PT2
•
PT1
To check these settings refer to section 3.5 in the meter configurations section of the manual.