57
AcuRev
1200
Table 5-17 System Parameters address table
Modbus
address(HEX)
Parameter
description
Data
type
R/W
Data range
Default
value
Model Register
number
200H
Meter address
Word R/W 1-247
1
1,2,3,4
1
201H
Line-side choice
Word R/W
0x00: On the side
line; 0xAA: The lower
side of the line
0
1,2,3,4
1
202H
Reserved
203H
RS485
Communication baud
rate
Word R/W
1200
2400
4800
9600
19200
38400
Other invalid
19200
1, 2
3, 4
1
204H
RS485
Communication
check
Word R/W
0: Even
1: Odd
2: Non2
3: Non1
3
1, 2
3, 4
1
205H
Reserved
206H
Reserved
207H
Reserved
208H
Reserved
209H
Pulse option
Word R/W 0:Real energy
1: Reactive energy
0
3, 4
1
20AH
Demand calculate
way option
Word R/W
0: Slid
1: Fixed
2: Roll
3: Thermal demand
0
3, 4
1
20BH
Demand calculate
cycle
Word R/W 1-30min
15
3, 4
1
20CH
Demand calculate slip
time
Word R/W 1-30min
1
3, 4
1
Содержание AcuRev 1200 Series
Страница 1: ...User s Manual AcuRev 1200 Energy Meter...
Страница 2: ......
Страница 8: ...VI AcuRev 1200...
Страница 9: ...1 AcuRev 1200 1 1 Meter Overview 1 2 Areas of Application 1 3 Product Features Chapter 1 Introduction...
Страница 13: ...5 AcuRev 1200 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Страница 32: ...24 AcuRev 1200 Choose Choose...
Страница 35: ...27 AcuRev 1200 Figure 4 1 Basic setting parameters in the software...
Страница 52: ...44 AcuRev 1200...
Страница 86: ...78 AcuRev 1200...
Страница 93: ......