34
A
cu
Re
v
12
00
disabled).
5. Tariff setting parameter: This parameter corresponds to the number of tariffs
available for the TOU calendar and can be selected from any integer from 1 to 4. The
four tariffs: sharp, peak, valley and normal are represented by 4 integers: 1,2,3 and 4
respectively. If the tariff setting parameter is set to 4, all of the 4 tariffs will be available for
the TOU calendar; if the parameter is set to 2, only the first 2 tariffs (sharp and peak) will be
available.
6. Holiday setting parameter: This parameter can be set from any integer between 1
and 30, meaning a maximum of 30 holidays can be programmed to the TOU calendar. If the
holiday setting parameter is set as 3, the first 3 slots of the holiday schedule must be set,
otherwise it will be considered as an invalid input (TOU function will be disabled).
Note
: User can either customize the TOU calendar factory settings or use the
default factory settings. User can reset the TOU calendar to its default value either via
communication or from the meter front.
The use of TOU energy holidays: In the TOU energy parameter setting part, firstly we
should set the number of holidays, then set the demanded holiday in the holiday setting
bar, the format is xx month- xx date. At this time, through setting the meter operate time,
when the meter’s operation time is during the setting time segment, the energy would
increase under the corresponding tariff.
Note:
TOU energy is with the highest priority on holidays, when the set of special date
is valid, the measurement of energy would consider the holidays at first.
Weekly rest funtion.
7. Weekend Schedule: Weekend Setting ( bit0: Sunday; bit1-bit6: Monday to Saturday;
1 means not effective, and 0 means effective). For example, when the Weekend Setting
bit0 is 0 means Sunday is effective. When the Weekend Setting bit1 is 0, it means Monday
is effective. When the meter clock is within the preset Weekend Schedule, the energy will
Содержание AcuRev 1200 Series
Страница 1: ...User s Manual AcuRev 1200 Energy Meter...
Страница 2: ......
Страница 8: ...VI AcuRev 1200...
Страница 9: ...1 AcuRev 1200 1 1 Meter Overview 1 2 Areas of Application 1 3 Product Features Chapter 1 Introduction...
Страница 13: ...5 AcuRev 1200 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Страница 32: ...24 AcuRev 1200 Choose Choose...
Страница 35: ...27 AcuRev 1200 Figure 4 1 Basic setting parameters in the software...
Страница 52: ...44 AcuRev 1200...
Страница 86: ...78 AcuRev 1200...
Страница 93: ......