33
AcuRev
1200
Time setting demands:
1. Season setting parameter: The calendar year will be divided up into different
seasons depending on the season setting parameter. The parameter can be selected from
any integer between 1 to 14. User must enter the correct value for the season setting
parameter in accordance to the TOU season table. For example, if the season setting
parameter is set as 2, the first 2 slots of the TOU season table must be set, otherwise it will
be considered as an invalid input (TOU function will be disabled).
2. TOU season format: Enter the start date into the TOU season table slot following this
format “MM-DD ID” - MM stands for the month, DD stands for the day and ID stands for the
TOU schedule ID (available from 01 to 14). The dates should be organized so that they are
in sequence according to the calendar year (the earlier date comes first and the later date
comes last). For example, if 3 seasons are selected, the date parameters are January 1, June
6 and September 7, and TOU schedule 02, 01, 03 will be used respectively, the first TOU
season table slot shall enter 01-01 02, the second slot shall enter 06-06 01, and the third
slot shall enter 09-07 03. Entering 01-01 02 for the first slot, 09-07 03 for the second slot and
06-06 01 for the third slot is considered invalid.
3. Schedule setting parameter: The number of available TOU schedules depends on
the schedule setting parameter. The parameter can be selected from any integer between
1 to 14. This parameter determines the number of TOU schedules available for the TOU
calendar setting. A maximum of 8 TOU schedules (from TOU Schedule #1 to TOU Schedule
#8 ) can be used.
4. Segment setting parameter: Each TOU schedule consists of various timing
segments. The number of segments depends on the segment setting parameter setup. The
parameter can be selected from any integer between 1 to 14 (inclusively). User must enter
the correct value for the segment setting parameter in accordance to the TOU schedule
table. If the segment setting parameter is set as 3, the first 3 slots of the TOU schedule
table must be set, otherwise, it will be considered as an invalid input (TOU function will be
Содержание AcuRev 1200 Series
Страница 1: ...User s Manual AcuRev 1200 Energy Meter...
Страница 2: ......
Страница 8: ...VI AcuRev 1200...
Страница 9: ...1 AcuRev 1200 1 1 Meter Overview 1 2 Areas of Application 1 3 Product Features Chapter 1 Introduction...
Страница 13: ...5 AcuRev 1200 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Страница 32: ...24 AcuRev 1200 Choose Choose...
Страница 35: ...27 AcuRev 1200 Figure 4 1 Basic setting parameters in the software...
Страница 52: ...44 AcuRev 1200...
Страница 86: ...78 AcuRev 1200...
Страница 93: ......