5.3
POSITIONING AND MINIMUM TECHNICAL CLEARANCES
All models of the
HPE R32
range are designed and constructed for outdoor installations.
It is advisable to create an adequately sized support base for the unit. The units transmit a small amount of vibrations to the
ground: it is nonetheless advisable to apply vibration dampers between the base frame and support surface.
In the case of hanging installation it is necessary to ensure that the wall is made of solid bricks, concrete or materials
with similar resistance characteristics. The load-bearing capacity of the wall must be sufficient to support at least
four times the weight of the unit.
To reduce vibrations and noise, we recommend the use of rubber gaskets for wall installation.
We always invite you to make an environmental impact assessment based on the power and sound pressure data shown in
chapter 11 "Technical data" and the sound emission limits based on the installation area of the unit, with reference to local
regulations. An assessment must also be made if the unit is installed near workers, according to local regulations.
At least 5 m from the appliance there must be no shafts or manholes where gases might build up and generate an
explosive atmosphere.
It is very important to avoid recirculation between intake and delivery air, so as not to downgrade performance of the unit or
even to interrupt its normal operation.
This is why the Minimum clearances shown below must be strictly guaranteed.
MODEL
A [mm]
B [mm]
C [mm]
D [mm]
E [mm]
HPE R32
04
1500
500
400
400
500
HPE R32
06
1500
500
400
400
500
HPE R32
08
1500
500
400
400
500
HPE R32
10
HPE R32
10T
1500
500
400
400
500
HPE R32
12
HPE R32
12T
1500
500
400
400
500
HPE R32
14
HPE R32
14T
1500
500
400
400
500
HPE R32
16
HPE R32
16T
1500
500
400
400
500
HPE R32
18T
1500
500
400
400
500
MODEL
L [mm]
HPE R32
04
500
HPE R32
06
500
HPE R32
08
500
HPE R32
10
HPE R32
10T
500
HPE R32
12
HPE R32
12T
500
HPE R32
14
HPE R32
14T
500
HPE R32
16
HPE R32
16T
500
HPE R32
18T
500