CALIDO1 

DHW heat pump with tank

20

insulation.

3. Install the hydraulic safety group in the water inlet.

4. Install also an exspanion tank suitable sized to absorbe volume variations.

5. The nominal diameter of the pipe must be chosen on the basis of the available water pressure and the expected pressure drop within the 

pipe system.

6. Water pipes can be flexible. To avoid corrosion damage, ensure that the materials used in the pipe system are compatible.

7. During the installation of the pipes in situ, any contamination of the pipe system must be avoided.

9.6.2 

Water loading

If the unit is used for the first time or used again after emptying the tank, please make sure that the tank is full of water before turning on the 

power.

• 

Flush the sysem carefully.

• 

Open the cold water inlet and hot water outlet.

• 

Start the water loading. When water flows out of the hot water outlet normally, the tank is full.

• 

Close the hot water outlet valve: the water load is finished.

ATTENTION: Operation without water in water tank, may cause damages the auxiliary electric heater.

9.6.3 

Water draining

If the unit needs cleaning, moving etc, the tank should be emptied.

• 

Close the cold water inlet.

• 

Open the hot water outlet and open the manual valve of the drainage pipe.

• 

Start the water emptying.

• 

After emptying, close the manual valve.

9.6.4 Installation of an external recirculation pump and flow switch

If necessary to recirculate solar water or hot sanitary water, an external pump and flow switch must be connected and installed hydraulically 

and electrically. The max available output for the pump is 5 A resistive. Also the optional probe T6 must be connected to the electrical box and 

correctly positioned on the hydraulic plant (see the diagrams here below). The Parameter no. 14 must be configured by the installer (1= hot 

sanitary water circulation, 2= solar water circulation).

The circulation of hot sanitary water is useful to avoid water becomes cold in the sanitary circuit if not used for several time. In this way the hot 

water will be always ready when requested.

The circulation of solar water is possible only if solar panel are installed and only for CALIDO1-S or CALIDO1-D units. In this way solar energy is 

used as secondary heat source to save energy.

In case of solar integration water, the following is required on the relevant circuit:

• 

an expansion tank suitable sized to absorbe volume variations, installed before the solar system.

• 

a pressure safety valve (3 bar) installed after the solar panel.

• 

an air vent valve with manual gate installed near the safety valve.

The outlet of the safety valve must be directed to a special tank for collecting glycol water, and not to normal waste water.

In case of recirculation of solar integration water, a thermal discharge safety valve (85°C) is highly recommended on the hot water outlet, with 

the probe positioned in a ½" thermowell installed in the recirculation water connection.

The CALIDO1 300 litres is equipped with an auxiliary well for the use of a possible external temperature probe for solar management with a sep

-

arate controller. In this case, it is advisable to pass the temperature probe through the auxiliary well (see Section 8.3) and through the channel 

provided behind the front plastic cover, which is connected to the auxiliary well. In this way the cable, entering from the rear of the unit, will not 

be visible, thus preserving the machine's appearance. To remove the front plastic cover, simply unscrew the two lower fixing screws and remove 

the cover from the upper cover. To remove the upper cover, it is necessary to unscrew the three screws fixing the cover to the tank (one at the 

rear and two at the sides).

Содержание GREEN 220

Страница 1: ...GREEN 220 220 S 220 DS Monobloc heat pump water heater with domestic hot water storage tank for internal installation GREEN 220 220 S 220 DS INSTALLATION MANUAL...

Страница 2: ...CALIDO1 DHW heat pump with tank 2 15 11 2021 AL B A R Add data kboll of the tank update layout Rev Date Edited by Approved by Notes Code Serie MUI01110D6120 DHW heat pump with storage tank...

Страница 3: ...IES 10 6 TECHNICAL CHARACTERISTICS 10 7 ITEMS CONTAINED INSIDE THE PACKAGING 10 8 OVERVIEW OF THE UNIT 11 8 1 PARTS AND DESCRIPTIONS 11 8 2 DIMENSIONS 11 8 3 CABLE GLANDS 13 8 4 HOW TO REPLACE THE MAG...

Страница 4: ...ALFUNCTION AND ERROR CODES 30 12 MAINTENANCE AND PERIODICAL CONTROLS 31 12 1 ENVIRONMENTAL PROTECTION 31 13 TROUBLESHOOTING 32 14 DECOMISSIONING 32 15 TECHNICAL CHARACTERISTICS 33 16 HEAT PUMP OPERATI...

Страница 5: ...sent to the customer must be kept as an annex to this manual regarding the use and maintenance of its machines 1 2 GRAPHIC SYMBOLS USED IN THE MANUAL ment in complete safety 2 NORMATIVE REFERENCES ise...

Страница 6: ...and or lean on any type of object Do not spray or pour water directly on the device supply Do not place your hands or insert screwdrivers spanners or other tools on moving parts 4 1 WORKERS HEALTH AND...

Страница 7: ...mask and protective goggles must be used during cleaning operation 4 3 SAFETY SYMBOLS The unit includes the following safety signs which must be followed by personnel General hazards Electric shock h...

Страница 8: ...rameters AEL 8 h and 12 h TWA 1000 ml m3 Respiratory protection Use self contained breathing apparatus for rescue and maintenance work in tanks Vapours are heavier than air and can cause choking by re...

Страница 9: ...vviso CALIDO Air inlet Air outlet GREEN Air inlet Air outlet Storage room cooling the unit can be placed in the storage room as the low temperature helps to keep the food fresh the unit can be located...

Страница 10: ...ACCESSORIES ONE FL ONE SAS temperature probe with 5 m cable GREEN S and GREEN 2S 6 TECHNICAL CHARACTERISTICS Safety devices for high and low gas pressure even in extreme cold winters 7 ITEMS CONTAINE...

Страница 11: ...CALIDO1 DHW heat pump with tank 11 8 OVERVIEW OF THE UNIT 8 1 PARTS AND DESCRIPTIONS 8 2 DIMENSIONS GREEN 200 GREEN 200 S GREEN 200 2S I A B C F E D H G L O N M Q P...

Страница 12: ...124 1124 1124 C 1062 1062 1062 D 262 E 747 747 747 F 932 932 932 G 30 H 160 I 706 L 655 M 258 258 N O 692 692 P 787 Q 927 AIR CONNECTION QUOTAS 318 80 148 170 GREEN 220 GREEN 220 S GREEN 220 2S POS DE...

Страница 13: ...ature 15 Solar water inlet G 1 female 16 Solar exchanger coil 1 2 m2 17 Auxiliary heat source outlet G 1 female 18 Auxiliary heat source inlet G 1 female 19 Auxiliary heat source coil 0 5 m2 8 3 CABLE...

Страница 14: ...astic frontal cover Such control allows a variation of temperature between 15 and 75 C each notch corresponds to a temperature variation of 10 C The factory setting is set to its maximum value 75 C a...

Страница 15: ...s of the extent of the damage The Customer should prepare a written statement of any severe damage Please note that all the installation diagrams shown in this chapter are only a guide The correct ins...

Страница 16: ...supply must always be OFF when cleaning or servicing the unit Failure to do so may result in injury due to high fan speed or electrical shock In case the unit is used without an exhaust air duct chec...

Страница 17: ...unit can be inclined only on the opposite side of the handle see above drawing namely only on the left hand side of the control panel The unit is equipped with a handle to make easy the transport The...

Страница 18: ...oss will be larger So if there are two bending pipes the total lenght of the ducts should not be longer than 2 m Please note that the performance of the unit are reduced in the case the air inlet is c...

Страница 19: ...of the hydraulic circuit All hydraulic connections must be insulated using closed cell material of adequate thickness The units should be connected to the piping using flexible couplings It is recomme...

Страница 20: ...here below The Parameter no 14 must be configured by the installer 1 hot sanitary water circulation 2 solar water circulation The circulation of hot sanitary water is useful to avoid water becomes col...

Страница 21: ...ly for GREEN 200 units it s possible to connect a third energy source for example an external boiler In this case the installer must discon an external relay not supplied to the external heat source o...

Страница 22: ...ts otherwise the warranty will expire immediately Before ATTENTION The supply voltage must not change by more than 10 of the nominal value If this tolerance is not respected please contact our technic...

Страница 23: ...ulations in force including grounding Check that the electrical voltage is within the tolerance 10 of the rating plate value Check that there are no gas leaks Before switching on the unit check that a...

Страница 24: ...creen 2 Button Pressing this button for 2 when the unit is in standby mode the unit switches on and operates in the selected mode The operating mode temperature set point and water temperature time an...

Страница 25: ...t the same time and for 5 seconds again the and buttons all the buttons are unlocked 4 Buttons and Clock setting Press button to entry the clock setting interface hour icon 88 88 flashes Press the and...

Страница 26: ...active This is an automatic function the system will enter or exit defrosting according to its own internal control logic Defrosting parameters cannot be changed on site And the unit does not support...

Страница 27: ...nk water goes up to 85 C the unit will stop and the relating error code will be shown on the controller This is an auto reset protection When tank water temperature goes down the unit can start again...

Страница 28: ...water The user is RESPONSIBLE to periodically check the correct operation of the anti legionella cycle and to verify that during the disinfection the setting temperature parameter is put to be 4 and...

Страница 29: ...Adjustable 5 l High temperature disinfection time t2 30 90 min 30 min Adjustable 13 l Start disinfection time 0 23 23 Adjustable 14 l Pump use 0 1 2 0 Adjustable 0 disabled 1 hot water recirculation 2...

Страница 30: ...t working properly 1 P8 appears at 125 C and disappears at 120 C 2 Check and replace the sensor if necessary High pressure protection Pressure switch HP E1 6 flashes 1 off 1 Air inlet temperature too...

Страница 31: ...nge x Check the correct operation of the electrical resistance for the anti legionella cycle It is advisable to carry out a diagnostic of all the hydraulic system with sampling of the system water at...

Страница 32: ...operations are recommended the refrigerant must be recovered by qualified personnel and sent to collection centres lubricating oil from compressors should also be recovered and sent to collection cen...

Страница 33: ...ace m2 Auxiliary exchange coil surface m2 m3 h m3 h Maximum exchange coil pressure bar Exchange coil material Cold water inlet inch Hot water inlet inch inch inch Condensate water outlet Condensate dr...

Страница 34: ...65 C 1 Technical label values referred to integration with boiler in accordance with DIN 4708 norms primary 80 60 C secondary 10 45 C 2 Measured according to EN 12102 standard in the conditions of EN...

Страница 35: ...CALIDO1 DHW heat pump with tank 35 17 WIRING DIAGRAM Please refer to the wiring diagram inside the electrical box cover 17 1 STANDARD CONNECTION...

Страница 36: ...CALIDO1 DHW heat pump with tank 36 17 2 CONNECTION OF AN AUXILIARY POWER SOURCE...

Страница 37: ...CALIDO1 DHW heat pump with tank 37 17 3 CONNECTION OF AN AUXILIARY ENERGY SOURCE VIA AN EXTERNAL SELECTOR SWITCH...

Страница 38: ...200 2S L A 129 119 111 104 796 kWh 862 kWh 921 kWh 983 kWh 55 C 58 dB A the dedicated chapters in the user installer manual 19 TECHNICAL PARAMETERS EU REGULATION 814 2013 Models Qelec Indor air 20 C I...

Страница 39: ......

Страница 40: ...tolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d An...

Отзывы: