Technical Information
9.3 MAINTENANCE METHOD FOR NORMAL MALFUNCTION
1. Air Conditioner Cant be Started Up
Possible Causes
Discriminating Method
(Air conditioner Status)
Troubleshooting
No power supply, or poor connection for
power plug
After energization, operation indicator isnt
bright and the buzzer cant give out sound
Confirm whether its due to power failure. If yes, wait for
power recovery. If not, check power supply circuit and make
sure the power plug is connected well.
Wrong wire connection between indoor
unit and outdoor unit, or poor connection
for wiring terminals
Under normal power supply circumstances,
operation indicator isnt bright after
energization
Check the circuit according to circuit diagram and connect
wires correctly. Make sure all wiring terminals are connected
firmly
Electric leakage for air conditioner
After energization, room circuit breaker trips
off at once
Make sure the air conditioner is grounded reliably
Make sure wires of air conditioner is connected correctly
Check the wiring inside air conditioner. Check whether the
insulation layer of power cord is damaged; if yes, place the
power cord.
Model selection for air switch is improper
After energization, air switch trips off
Select proper air switch
Malfunction of remote controller
After energization, operation indicator is
bright, while no display on remote controller or
buttons have no action.
Replace batteries for remote controller Repair or replace
remote controller
2. Poor Cooling (Heating) for Air Conditioner
Possible Causes
Discriminating Method
(Air conditioner Status)
Troubleshooting
Set temperature is improper
Observe the set temperature on remote
controller
Adjust the set temperatur
Rotation speed of the IDU fan motor is set
too low
Small wind blow
Set the fan speed at high or medium
Filter of indoor unit is blocked
Check the filter to see its blocked
Clean the filter
Installation position for indoor unit and
outdoor unit is improper
Check whether the installation postion is
proper according to installation requirement
for air conditioner
Adjust the installation position, and install the rainproof and
sunproof for outdoor unit
Refrigerant is leaking
Discharged air temperature during cooling
is higher than normal discharged wind
temperature; Discharged air temperature
during heating is lower than normal discharged
wind temperature; Units pressure is much
lower than regulated range
Find out the leakage causes and deal with it. Add
refrigerant.
Malfunction of 4-way valve
Blow cold wind during heating
Replace the 4-way valve
Malfunction of capillary
Discharged air temperature during cooling
is higher than normal discharged wind
temperature; Discharged air temperature
during heating is lower than normal discharged
wind temperature; Unitt pressure is much
lower than regulated range. If refrigerant isnt
leaking, part of capillary is blocked
Replace the capillary
Flow volume of valve is insufficient
The pressure of valves is much lower than that
stated in the specification
Open the valve completely
Malfunction of horizontal louver
Horizontal louver cant swing
Refer to point 3 of maintenance method for details
Malfunction of the IDU fan motor
The IDU fan motor can’t operate
Refer to troubleshooting for H6 for maintenance method in
details
Malfunction of the ODU fan motor
The ODU fan motor can’t operate
Refer to point 4 of maintenance method for details
Malfunction of compressor
Compressor cant operate
Refer to point 5 of maintenance method for details
3. Horizontal Louver Cant Swing
Possible Causes
Discriminating Method
(Air conditioner Status)
Troubleshooting
Wrong wire connection, or poor connection
Check the wiring status according to circuit
diagram
Connect wires according to wiring diagram to make sure all
wiring terminals are connected firmly
Stepping motor is damaged
Stepping motor cant operate
Repair or replace stepping motor
Main board is damaged
Others are all normal, while horizontal louver
cant operate
Replace the main board with the same model