ELECTRICAL CONNECTION
8
8.1 General
For the warranty to apply, a qualified person must carry out all the electrical wiring in
accordance with local regulations. If the filter unit is equipped with extra electrical equipment,
this equipment shall be wired according to the wiring diagram supplied.
The Absolent oil mist
filter unit can be customized to meet your needs. The range of accesso
-
ries includes starting equipment and other electrical periphery equipment. The most common
accessories are described under the heading ”Accessories”.
The models A•mist
10S
, A•mist
20S
and A•mist
20HPS
cover also oil smoke.
8.2 Electrical connection of the fan motor
for direct start
All Absolent filter units with integrated fan are standardly equipped with wired cables from the
fan to the terminal blocks on the side of the filter unit.
Warning - Dangerous voltage
All electrical work must be carried out by qualified electricians.
Electrical data can be read from the rating
plate on the right-hand side of the filter unit.
Filter unit
400V, 50Hz
Standard fan motor
400V, 50Hz
Type of
fuse
Fuse
settings
Comment
A•mist
6C
, A•mist
10
0.55kW; 1.4A; 400V; 50Hz
10 A
1.4A
Direct start
A•mist
20
2.2kW; 4.6A; 400V; 50Hz
10 A
4.6A
Direct start
A•mist
60
3 motors à 2.2kW; 4.6A; 400V;
50Hz
35 A
13.8A
Direct start
A•mist
40TF
4,0kW; 7,8A; 400V; 50Hz
20 A
7,8A
Direct start
A•mist
80TF
7,5 kW; 13,8A; 400V; 50Hz
35 A
13,8A
Direct start
Filter unit
480V, 60Hz
Standard fan motor
480V, 60Hz
Type of
fuse
Fuse
settings
Comment
A•mist
6C
, A•mist
10
0.85hp; 0.55kW; 1.4A; 480V;
60Hz
10 A
1.4A
Direct start
A•mist
20
3.5 hp; 2.2kW; 4.6A; 480V;
60Hz
10 A
4.6A
Direct start
A•mist
60
3 motors à 3.5 hp; 2.2kW;
4.6A; 480V; 60Hz
35 A
13.8A
Direct start
A•mist
40TF
5.4hp; 4,0kW; 7,8A; 480V;
60Hz
20 A
7,8A
Direct start
A•mist
80TF
10hp; 7,5 kW; 13,8A; 480V;
60Hz
35 A
13,8A
Direct start