Installation –
Specifications for the mechanical and electrical installation of the wallboxes |
19
Specifications for the mechanical and electrical installation of the wallboxes
The mechanical and electrical installation of the wallbox on the POLEMH6 must be carried out by qualified electri-
cians: It is recommended that the installation be carried out by two persons.
DANGER!
Dangerous electrical currents
Always observe the 5 safety rules:
1
Cut power source
2
Secure all cut-off devices
3
Verify absence of voltage
4
Ground and short-circuit
5
Cover or bar access to adjacent components under voltage
The supply cable must not be reconnected to the electricity grid until
Step 4
in the section “Electrical connection
For mechanical and electrical installation, you will need the following components included with the POLEMH6:
Key for unlocking the housing
cover
M8×25 rounded-head screw
for fastening the mounting
plate (4 pieces per wallbox)
In addition, you will need the following components and tools:
PG 13.5 cable gland (for each
M20 cable entry)
Triangular key
(included with the wallbox)
×
2
×
1
Torx screwdriver
Slotted screwdriver
Phillips screwdriver
Hexagon screwdriver
Stripping tool
Hammer
Voltage tester