44
EN
Warning
Alarm
Error
Fault Name
Reason Description
Suggested Handling
u.57
A.57
Analogue input
terminals Error
1. Wire connection
problem
2. The parameters for
AI1/AI2 live zero are not
correctly set
1. Check the wire
connection
2. Adjust the relevant
parameter setup
u.62
A.62
Communication
Timeout
Drive communication
timeout (with external
controller PC/PLC/HMI
etc.)
1. External controller
abnormal
2. communication line
connection problem
3. communication
Parameters(P0-8X)
incorrect.
4.EMC problem.
1.
Check external
controller PC, PLC, HMI
etc. 2.Check
communication line
connection 3.Correctly set
communication
parameters(P0-8X) 4.
wiring the communication
cables correctly, including
shielding and grounding
5.Contact our local support
or Company
u.66
Motor Loss
Motor cable connection
or motor problems;
Check motor cable or motor
phase
A.69
Mechanic Brake
Current Low
Actual motor current
cannot exceed release
brake current
(P1-97~P1-98) within
start delay time.
Correctly set mechanical
brake
parameters(P1-97~P1-98)
u.75
Drive License
Timeout
Drive License Timeout
function activated
Contact our local support or
ABC Company
u.76
A.76
External alarm
DI terminals select
external alarm function
Check external alarm
source
Er.90
CU
communication
Timeout
CU Failed to
communicate with PU
1.Power off, then confirm
the installation between PU
and CU
2.Contact our local support
or ABC Company
Er.93
Parameter change
disabled
1. They keypad was
locked when changing
the parameters
2. parameters over the
range
1. deblock the keypad
2. set the parameters
correctly
Err
Parameter change
disabled
The parameter cannot be
changed when Drive
running
Change the parameter after
Drive stop
A.99
AMA Error
Failed to finish the motor
parameter auto tuning
Correctly set motor
parameters according to
motor nameplate
7. List of Parameters
Parameter
Number
Parameter Name
Value Range
Unit
Factory
Default
Parameter Group 0
:
General Control Mode and Commands
P0-01
Control Mode
0: Speed Mode Speed Sensor less
1: Speed Mode with Speed Sensor
2: Torque Mode Speed Sensor less
3: Torque Mode with Speed Sensor
0
*P0-02
Motor Control
Principle
0: V/F; 1: Vector Control 1;
2: Vector Control 2
1
P0-03
Macro-program
0
:
Invalid
;
1
:
Pump Control
;
2: Easy PLC
0
*P0-04
Torque Characteristics
0
:
CT; 1
:
VT; 9
:
AEO
0
*P0-05
Motor Speed
Direction
0
:
Clockwise; 1
:
Anticlockwise
2
:
Bidirectional
2
Содержание PU00
Страница 3: ...1 CU PU AD800 1 AD800 PU CU 2 4 22kW 15 30kW R S T R L S T N U V W P1 13 1 2...
Страница 5: ...3 4 PU00 PU01 PU01 4 1 PU00 PU01 U V W DC BR R L S T N R L T N PU00 PU01 0 37 7 5kW PU00 PU01 11 22kW...
Страница 6: ...4 PU00 30 45kW PU00 55kW 90kW PU00 110 500kW...
Страница 9: ...7 1 FWD REV 2 FWD REV...
Страница 35: ...33 EN PU00 30 45kW PU00 55kW 90kW PU00 110kW 500kW...
Страница 63: ...61 RU 1 PU AD800 CU 2 22kW 4 30kW 15 R S T R L S T N U V W P1 13 1 2 CU C PU AD800...
Страница 65: ...63 RU 4 PU00 PU01 PU01 4 1 PU00 PU01 U V W P BR R S T 1 R L T N PU00 PU01 0 37 7 5 PU00 PU01 11 22 PU00 30 45...
Страница 66: ...64 RU PU00 55 90 PU00 110 500 PU00 560 630...
Страница 69: ...67 RU 1 DI FWD DI REV 2 FWD REV 1 DI FWD REV DI1...
Страница 70: ...68 RU 2 DI FWD DI REV DI DI1 5 2 2 1 AI1 0 10 AI1 A 2 P0 11 5 DI4 P2 10 40 DI4 3 DI DI...
Страница 72: ...70 RU 5 P4 07 P4 08 PID P4 07 P4 08 PID AI1 5 4 AD800 P0 03 1 P0 30 30 0 10 0 30 30 3 P3 04 7V AI1 AI1 7V...
Страница 73: ...71 RU PID PID P4 07 P4 08 5 5 Modbus 1 P0 80 P 0 82 P0 80 1 P0 81 9600 P0 82 2 9999 10000...
Страница 95: ...P0100946 V5 1 2022 11 08...