Warning
Alarm
Error
Fault Name
Reason Description
Suggested Handling
u.41
A.41
Rectifier
Temperature
High
Too high load or the
cooling condition beyond
the specification
1. Check the load
2. Check the cooling
condition, include to clean
the airduct or replace the
fan
u.42
A.42
Rectifier
Temperature
Sensor Error
Contact our local support or
ABC Company to repair
u.43
A.43
Power Board
Over
Temperature
Too high load or too high
ambient temperature
1. Check the load
2. Check the cooling
condition, include to clean
the airduct or replace the
fan
u.45
A.45
Over Current
1. Motor parameters
and/or motor control
parameters are not set
appropriately; 2. The
power size of inverter is
too small comparing to
the motor or the load
3. The power supply
voltage is too low; 4. The
inverter failed to catch a
spinning motor at fly
1.Adjust relevant
parameters
2.Select inverter with
higher power rating
3.Check the power supply
voltage
4.Contact our local support
or ABC Company
u.46
A.46
Drive Overload
1. Too heavy load or too
low power supply voltage
2. The power size of
inverter is too small
comparing to the motor
or the load
3. Motor parameters
and/or motor control
parameters are not set
appropriately;
1.Correctly set relevant
parameters especially the
motor parameters
2.Select inverter with high
power rating.
3. Contact the local
distributor or ABC
Company
u.48
A.48
Motor Over
Temperature
1. Too heavy load on the
motor
2. Cooling condition for
the motor is not good
enough
3. Thermistor for motor
temperature sensing is
not used correctly
1.Check selection
/installation of the
thermistor for motor
temperature sensing
2.Check the cooling
conditions for motor
3. Check the load versus
rated power of the motor
u.49
A.49
Motor Overload
1. Motor parameters
and/or motor control
parameters are not set
appropriately; 2. Too
heavy load on the motor
1. Correctly set relevant
parameters especially the
motor parameters
2. Check the load versus
rated power of the motor
u.50
A.50
Current Limit
Current exceeds the
parameter set max.
current (P5-07) due to:
1. Too heavy load
comparing to the power
size of the inverter 2. Too
fast ramp with inertia
3. Too low power supply
voltage
4. Motor parameters
and/or motor control
parameters are not set
appropriately;
Adjust P5-07 or try A.45
solution
u.51
A.51
Torque Limit
Torque exceeds the
parameter set max. torque
(P5-04/P5-05).
Adjust P5-04/P5-05 or try
A.45 solution
Содержание PU00
Страница 3: ...1 CU PU AD800 1 AD800 PU CU 2 4 22kW 15 30kW R S T R L S T N U V W P1 13 1 2...
Страница 5: ...3 4 PU00 PU01 PU01 4 1 PU00 PU01 U V W DC BR R L S T N R L T N PU00 PU01 0 37 7 5kW PU00 PU01 11 22kW...
Страница 6: ...4 PU00 30 45kW PU00 55kW 90kW PU00 110 500kW...
Страница 9: ...7 1 FWD REV 2 FWD REV...
Страница 35: ...33 EN PU00 30 45kW PU00 55kW 90kW PU00 110kW 500kW...
Страница 63: ...61 RU 1 PU AD800 CU 2 22kW 4 30kW 15 R S T R L S T N U V W P1 13 1 2 CU C PU AD800...
Страница 65: ...63 RU 4 PU00 PU01 PU01 4 1 PU00 PU01 U V W P BR R S T 1 R L T N PU00 PU01 0 37 7 5 PU00 PU01 11 22 PU00 30 45...
Страница 66: ...64 RU PU00 55 90 PU00 110 500 PU00 560 630...
Страница 69: ...67 RU 1 DI FWD DI REV 2 FWD REV 1 DI FWD REV DI1...
Страница 70: ...68 RU 2 DI FWD DI REV DI DI1 5 2 2 1 AI1 0 10 AI1 A 2 P0 11 5 DI4 P2 10 40 DI4 3 DI DI...
Страница 72: ...70 RU 5 P4 07 P4 08 PID P4 07 P4 08 PID AI1 5 4 AD800 P0 03 1 P0 30 30 0 10 0 30 30 3 P3 04 7V AI1 AI1 7V...
Страница 73: ...71 RU PID PID P4 07 P4 08 5 5 Modbus 1 P0 80 P 0 82 P0 80 1 P0 81 9600 P0 82 2 9999 10000...
Страница 95: ...P0100946 V5 1 2022 11 08...